Testing and Troubleshooting
13-2
13.3 Periodic Testing and Maintenance
To ensure proper and reliable operation, it is recommended that system inspection and testing be scheduled
monthly or as required by national and/or local fire codes. Testing should be done by a qualified service
representative if a malfunction is encountered.
Before testing:
1.
Notify the fire department and/or central alarm receiving station.
2.
Notify facility personnel of a test so that alarm sounding devices are ignored during the test period.
3.
When necessary, activation of Notification Appliances can be prevented by the DISABLE function.
Testing:
1.
Activate a input via an alarm initiating device and check that the correct outputs activate (Notification
Appliances sound/flash, relays activate, alarm indicator lights). Reset system. Repeat for each alarm initiat
-
ing device.
2.
Momentarily open the following circuits one at a time and check for a trouble sign:
- Notification Appliance Circuits
- Initiating devices
3.
If new batteries were installed, wait 48 hours before completing this step. Remove AC power, activate initi
-
ating device and check that:
- The alarm indicator lights
- All active Notification Appliances sound
5815XL module that has been physically
connected to the panel but is not being
recognized.
Check the status of the 5815XL green LED. If it flashes in the pattern .5 sec. on
/ .5 sec. off, it is likely that the 5815XL has not been added to the system
through programming. JumpStart will add any 5815XLs connected to the panel.
5815XLs can be added manually (see Section 9.2.2).
Check that the correct ID for the 5815XL module has been set through the DIP
switches. Assign ID#1 to the first 5815XL and ID#2 to the second 5815XL. See
Section 4.13.1 for complete details.
If the wiring between the 5815XL and the panel is correct, measure the voltage
from 5815XL Terminal (+) to Terminal (-). Voltage should be in the range 27.2-
27.4V when AC power is present.
If the green LED is not flashing, the likely cause is incorrect wiring from
between the 5815XL and the panel. See Section 4.8.1 for wiring details.
Note:
5815XL will only support SD devices
6815 module that has been physically
connected to the panel but is not being
recognized.
Check the status of the 6815 green LED. If it flashes in the pattern .5 sec. on /
.5 sec. off, it is likely that the 6815 has not been added to the system through
programming. JumpStart will add any 6815s connected to the panel. 6815s can
be added manually (see Section 9.2.2).
Check that the correct ID for the 6815 module has been set through the DIP
switches. Assign ID#1 to the first 6815and ID#2 to the second 6815. See
Section 4.13.1 for complete details.
If the wiring between the 6815 and the panel is correct, measure the voltage
from 6815 Terminal (+) to Terminal (-). Voltage should be in the range 27.2-
27.4V when AC power is present.
If the green LED is not flashing, the likely cause is incorrect wiring from
between the 6815 and the panel. See Section 4.8.1 for wiring details.
Problem
Possible Cause / Suggested Actions