Section 2: Installation
The standard cabinet may be either semi-flush or surface mounted. Fire Alarm Control Panel
(FACP) cabinets can only be wall mounted. Each cabinet mounts using two or three key slots and
two 0.250" (6.35 mm) diameter holes in the backbox. The key slots are located at the top of the
backbox and the two securing holes at the bottom.
Carefully unpack the system and check for shipping damage. Mount the cabinet in a clean, dry,
vibration-free area where extreme temperatures are not encountered. The area should be readily
accessible with sufficient room to easily install and maintain the panel. Locate the top of the cabinet
approximately 5 feet (1.5 m) above the floor with hinge mounting on the left. Determine the
number of conductors required for the devices to be installed. Sufficient knockouts are provided for
wiring convenience. Select the appropriate knockout(s) and pull the conductors into the box. All
wiring should be in accordance with the National and/or Local codes for fire alarm systems and
power supplies.
2.1 Backbox Mounting
To prevent damage to the circuit board and to facilitate backbox mounting, the chassis with the
24 VDC power supply and the Control circuit board can be easily removed. Loosen the two #8-32
nuts securing the top flanges of the chassis, then slide the chassis up to free it from the lower tabs.
Place the chassis assembly in a safe location until it can be reinstalled in the backbox.
1. Mark and predrill a hole in the wall for the center top keyhole mounting bolt using the
dimensions illustrated in Figure 2.2, “Standard Cabinet: Dimensions for Wall-mounting”
on page 19 or Figure 2.3, “FACP Cabinet-Mounting Details: Backbox-Mounting Holes
and Chassis-Mounting Studs (EQBB-D4 shown)” on page 20.
2. Install the center top fastener in the wall with screw head protruding.
3. Place backbox over the top screw, level and secure.
4. Mark and drill the left and right upper and lower mounting holes.
5. Note: outer holes (closest to sidewall) are used for 16" O.C. stud mounting.
6. Install remaining fasteners.
!
CAUTION:
THE CIRCUIT BOARD CONTAINS STATIC-SENSITIVE COMPONENTS.
ALWAYS GROUND YOURSELF WITH A STATIC STRAP BEFORE HANDLING ANY BOARDS
SO THAT THE STATIC CHARGES ARE REMOVED FROM THE BODY. USE STATIC
SUPPRESSIVE PACKAGING TO PROTECT ELECTRONIC ASSEMBLIES.
NOTE:
See
EQ Series Install Sheet
PN 53412 for door-mounting details and
measurements for B-size and C-size backboxes.