HPF24S Series Power Supplies —
P/N 52751:D3 5/11/2010
35
Master FACP With Slave HPF24S Power Supply
Applications
5.5 Master FACP With Slave HPF24S Power Supply
In this application, an HPF24S power supply, configured as a Slave unit, is connected to a master
FACP NAC programmed for synchronized output. The power supply should be set for
synchronization which matches the FACP programming.
Notes: The following notes apply to Figures 5.5.
1. Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2. Use only devices from the same manufacturer in each system.
3. Some FACPs do not provide sync capability from the NAC output. Refer to the FACP user
manual to determine the source of the sync signal.
4. If the FACP has a dedicated sync output connector, wire the sync output connnector to the
HPF24S Sync In terminals, terminals 1 and 2 on TB4. Refer to the Supervised Master/Slave
Connections (Remote Sync Source) in 5.5b.
Standby Polarity Shown
Horn/Strobes
HPF24S
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
5.5a: Supervised Master/Slave Connections (Filtered, Synchronized NAC Source)
general alarm
24
fs
ap
p1
.w
mf
See note #3.
Standby Polarity Shown
SW1 Switch Settings
1 & 2 = sync (any setting
but OFF/OFF)
3 = ON (slave)
4 = OFF (no AC Fail
reporting delay)
5 = OFF
6 = OFF
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)
24
fsap
p1b
.w
m
f
Figure 5.5 Supervised Master/Slave Connections
5.5b: Supervised Master/Slave Connections (Remote Sync Source)