Product Installation Document

This product follows under the UL1481 Fire Alarm Systems, UL603 Burglary Alarm Systems and UL294 Access Control 
Systems. The HP400ULM unit is to be installed in a fail safe mode unless authorized by the local AHJ. This product must 
be installed in compliance with Article 760 of the National Electrical Code, NFPA70, as well as NFPA72 National Fire 
Alarm Code and all applicable local codes. 

1 Description

The HP400ULM is a 12VDC or 24VDC power supply with an HPMOM6 distribution controller to be used with Card 
Access Systems. It provides 12/24VDC through 6 power-limited outputs. The 6 outputs will switch ON or OFF security 
devices such as Magnetic Locks, Door Strikes, Magnetic Fire Door Holders, etc. The HPMOM6 offers a choice of two (2) 
outputs, “Fail Safe or Fail Secure” and a choice of two (2) Fire inputs, N/O or N/C, and Reverse Polarity triggered by the 
FACP. The Controller also has 2 Trouble/ Alarm dry contact outputs type “Form C”; 1) Power Fail/ PTC Activated, and 2) 
FACP Triggered. The unit has not been evaluated as elevator equipment, and is not authorized for bell output in 
Mercantile applications.

2 Specifications

A) Power Supply Board

1. Input voltage: 120VAC 60Hz; Current: 2.50A max.
2. Output Voltage: 12VDC or 24VDC, jumper selectable; Current: 4.0A continuous output maximum, 3.5A plus battery 

charger (not supervised).

3. Fail safe dry contact output on AC Failure (within one minute).
4. Built-in charger for sealed lead acid or gel cell type batteries.
5. Instantaneous transfer to stand-by battery on AC failure.
6. Battery presence detection (within 1 minute)
7. Battery low disconnect at 9.90VDC or 19.90VDC.
8. High voltage disconnect at 15VDC or 30VDC.
9. Yellow LED (L3) indication for battery disconnected and battery low.
10. Fail safe dry contact output for Battery trouble (Fail Safe).
11. Battery polarity reversal protection.
12. Thermal overload and short circuit protection.
13. DC output PTC activated indication by Red LED (L2).
14. DC output failure indication by Red LED ( L4 ).
15. AC presence indication by Green LED ( L1 ).
16. DC output indication by Red LED ( L5 ).
17. Battery Leads included.
18. Power Board Dimensions: 6.2”L x 4.7”W x 2.5”H.
19. Enclosure Dimension: 17”L x 13.5”W x 4.75”H.  Accommodates two 12 Volt 12AH batteries. When using larger 

batteries, a UL approved enclosure must be used.  

B) Distribution Controller Board

Outputs

– 6 Fail Safe or Fail Secure

Continued on next page...

Summary of Contents for HP400ULM

Page 1: ...Triggered The unit has not been evaluated as elevator equipment and is not authorized for bell output in Mercantile applications 2 Specifications A Power Supply Board 1 Input voltage 120VAC 60Hz Current 2 50A max 2 Output Voltage 12VDC or 24VDC jumper selectable Current 4 0A continuous output maximum 3 5A plus battery charger not supervised 3 Fail safe dry contact output on AC Failure within one m...

Page 2: ...tput Connections There are 6 outputs selectable together as Switched Normally Open NO or Switched Normally Closed NC There are 2 possible output type connections in either case connect device negative to Neg terminal on HPMOM6 1 For Fail Safe operation connect device positive to DC STANDBY OUTPUT on HPMOM6 DC power is present in normal condition and will switch OFF when the FACP is triggered Fail ...

Page 3: ...ute Connect the Battery Fail output Form C dry contacts to the monitoring device If a Battery is not connected or improperly connected the Yellow LED L3 will turn ON within one 1 minute and the Battery Fault output relay which is Fail Safe will de energize 9 Power Up When all wiring is complete and checked switch ON the AC Power The Green Led L1 will come ON indicating AC presence and the AC relay...

Page 4: ...Hr Stand By 15Mins ALRM 60Hr Stand By 5Mins ALRM 12Ah 12V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 12V STBY 2 00A 200mA N A ALRM 3 50A 2 00A N A 55Ah 12V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A 12Ah 24V STBY 2 00A N A N A ALRM 3 50A N A N A 17Ah 24V STBY 2 00A 200mA N A ALRM 3 50A 3 50A N A 55Ah 24V STBY 3 50A 1 50A 300mA ALRM 3 50A 3 50A 3 50A UL Listing UL294 UL603 UL294 UL603 UL1481 UL1...

Page 5: ...HP400ULM Installation Document P N 52390 A 1 05 06 5 Continued on next page ...

Page 6: ...00ULM Installation Document P N 52390 A 1 05 06 For additional information Visit our website at http www honeywellpower com Contact Technical Support at 1 877 HPP POWR E mail us at hpp techserv honeywell com ...

Reviews: