18
LeakFilm MC Technical Manual 3013M5005 Issue 3
MAN0966 04-15
7. Menu and Advanced Configuration
LCD Display & Button Operation
Description
[5. Silent Control]
5. Silent Control
Switch Off
Auto Off
Mute
The user can configure how the buzzer works in alarm
status. The master controller provides three options.
- Switch Off: Once an alarm occurs, the user can mute
the buzzer using the “SILENT” button.
- Auto Off: User cannot mute the buzzer. The buzzer
will stop only when the alarm is removed.
- Mute: The buzzer is not activated in alarm status.
Select an option by moving “→” cursor using the “UP”
and “DOWN” buttons and exit using the “ESC” button.
[6. Modbus Set]
6. Modbus Set
Baud Rate : 9600
Set the communication speed between the master
controller and the host system.
Normal monitoring mode.
Display date and time at normal (no alarm) status.
Table 6: Menu Mode of LeakFilm MC
7.2 Alarm Mode
Once the alarm occurs in one of slave controllers connected to LeakFilm MC, it displays as
below.
LCD & LED Display
Description
[Comm. Error]
LeakFilm
Master Controller
2014-03-10 21:24:10
Module 001 : ComErr
FAULT LEAK COMM.ERR POWER
When communication error occurs, LeakFilm MC
displays “ComErr” and the “COMM. ERR” LED turns
on. The buzzer sounds as set by the “Silent Control”
menu.
[Sensor Broken]
LeakFilm
Master Controller
2014-03-10 21:24:10
Module 001 : Broken
FAULT LEAK COMM.ERR POWER
When a communication error occurs, LeakFilm MC
displays “Broken” and the “FAULT” LED turns on.
The buzzer sounds as set by the “Silent Control”
menu.