CM900 Wireless - Programmable Room Thermostat

4.5.2 Category 2 - System Settings

Notes

1) Remember to always press the green   button to confirm that you want to store your new Installer Set-

Up setting. To exit the Installer Mode move the slider switch to the 

AuTO

 or 

MAN

 position.

2) These parameters are set centrally for the zoning system at the room thermostat configured as the 

system synchroniser.

3) Minimum on-time setting applies only to the boiler controller. All receiver box zone controllers will work 

with the minimum on-time of 30 seconds.

Parameter

Parameter 

No.

Factory Default Setting

Optional Setting

Category 2 Parameters – System Settings (press the 

 button to access this category)

Display

Description

Display  Description

Minimum boiler 
ON time

1:Ot

1

1 minute minimum 
ON time

2 to 5

Selection of 2, 3, 4 or 5 minutes 
minimum ON time

Cycle Rate

2:Cr

6

6 cycles per hour 
(cph)

3,9 or 

12

Selection of 3, 9 or 12 cph

Heat/Cool Change

4:HC

0

Disabled

1

Enabled

Pump Exercise

5:PE

0

Pump exercise 
disabled

1

Pump exercise enabled

System 
Synchronisation

6:Sn

0

Standard operation of 
the Room Unit

1

Room unit configured as Synchroniser

Loss of 
Communications 
Instruction

7:LC

0

Relay Off

1

Relay 20% on / 80% off

The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating 
controls and Wireless Radiator controls. For more information please contact Honeywell sales.

Room Temperature 
Sensor Use

8:Su

0

HC60 control

1,2,3 

or 4

1 - HR80/HM80 control with own/remote 
sensor (no temperature displayed)
2 - Hr80/HM80/HCE80 control with CM 
sensor
3 - HC60 control and HR80/HM80/
HCE80 control with own/remote sensor
4 – Hr80/HM80/HCE80 control with own/
remote sensor (temperature displayed) 

HR80 Window-
Open Function

9:HO

0

Disabled

1

Enabled

HR80 Local 
Override

10:HL

1

Enabled

0

Disabled

Maximum Flow 
Setpoint

11:uF

55

55°C Maximum Flow 
Temp.

0 to 99

0°C to 99°C adjustment in 1°C steps

Minimum Flow 
Setpoint

12:LF

15

15°C Minimum Flow 
Temp.

0 to 50

0°C to 50°C adjustment in 1°C steps

Mixing Value Run 
Time

13:Ar

150

150 seconds

0 to 
240

0 to 240 sec. adjustment in 1sec steps

Pump Overrun Run 
Time

14:Pr

15

15 minutes

0 to 99

0 to 99 mins adjustment in 1min steps

Summary of Contents for HC60NG

Page 1: ... INCLUDE THIS PAGE IN THE PRINTING Folding Sequence Finished Size 42011076 003 CM900 RF INSTALLATION GUIDE UK English 0024168 08 06 MF BM A3 A4 A5 A6 A7 OTHER SIZE WHEN PRINTED x booklet SIZE WHEN FOLDED X CARTRIDGE x MATT ART WEIGHT 70g 80g 100g 115g 150g OTHER x SINGLE SIDE DOUBLE SIDE x ONE COLOUR TWO COLOUR THREE COLOUR FULL COLOUR X black R2 08 06 Back Front 105mm 148mm 12 page A5 saddle stit...

Page 2: ...d easy but if products from individual system packs are separated or mixed with other pre configured system packs during installations please refer to section 5 1 Binding Rebinding Procedure to bind the desired units together and allow them to communicate with each other Table of Contents Section Page 1 Installation Information 2 2 Installing the CM900 Wireless System 3 2 1 Installing the Receiver...

Page 3: ...ength of the RF signal reaching the receiver box depends on the number of walls and ceilings separating it from the room thermostat as well as the building construction the diagram below illustrates an example of typical signal strength reduction Walls and ceilings reinforced with steel or plasterboard walls lined with metal foil reduce the RF signal significantly more Once a position is selected ...

Page 4: ...performance install in an open space Leave at least 30cm distance from any metal objects including wall boxes and boiler housing Do not mount on metal wall boxes NOTE The receiver box contains no user serviceable parts It should be opened and installed by qualified installer only WARNING Electrostatic sensitive device Do not touch the circuit board NOTE All wiring must be in accordance with IEE re...

Page 5: ...een button to confirm 2 2 2 RF Communication Check Test Mode To check the RF communication hold the room thermostat about 2 3 metres from the installed receiver box Move the slider on the room thermostat to the OFF position then press the and buttons together with the button for 3 seconds The unit will display TEST TRANSMIT and it will send test signals to the receiver box flashing the green LED o...

Page 6: ...lider switch to the MAN mode 4 Adjust the setpoint up to the maximum 35 C by pressing the button The boiler should come on green LED ON on receiver box after a few seconds and the symbol appears on the room thermostat LCD display 5 Set the slider switch to the OFF mode The boiler will go off green LED OFF on receiver box after a few seconds and the symbol disappears 6 Check the system operation by...

Page 7: ...d of 1 hour the red LED will illuminate to indicate that no RF messages have been received during the last hour The receiver box will also enter the failsafe mode as selected in Installer Mode see section 4 2 HC60 Receiver Box Fail Safe Mode Setup To allow manual control of the receiver box output manual override is available in fail safe mode When RF communication is restored the receiver box wil...

Page 8: ...to accept the change 6 Attach appropriate label to the receiver box to indicate the selected fail safe mode IMPORTANT To enable the frost protection when RF communication is lost select the fail safe mode 1 For systems with separate frost protection thermostat or where frost protection is not required select fail safe mode 0 COPY DAY DAY 1 6 CM927 DATE PROG AUTO MAN OFF OFF Move the slider switch ...

Page 9: ...ter 3 tC category 1 to 1 Temperature Offset If the thermostat is located in a particularly hot cold location for reliable signal transmission reasons then the measured displayed temperature can be adjusted by 3 C This is useful if the homeowner wants the reading to match another appliance temperature display Set parameter 12 tO category 1 to the required offset value Upper Lower Temperature Limit ...

Page 10: ...rammed To restore the factory profile set to 1 Auto Summer Winter Time Change 3 tC 1 Auto Summer Winter Time Change Enabled 0 Auto Summer Winter Time Change Disabled LCD Backlighting 5 bL 1 Backlighting Enable 0 Backlighting Disabled Upper Temp Limit 6 uL 35 35 C Upper Temp Limit 21 to 34 21 C to 34 C adjustment in 1 C steps Lower Temp Limit 7 LL 5 5 C Lower Temp Limit 5 to 21 6 C to 21 C adjustme...

Page 11: ...abled 1 Pump exercise enabled System Synchronisation 6 Sn 0 Standard operation of the Room Unit 1 Room unit configured as Synchroniser Loss of Communications Instruction 7 LC 0 Relay Off 1 Relay 20 on 80 off The following Parameters are for the control of other Honeywell Wireless products such as Wireless Underfloor Heating controls and Wireless Radiator controls For more information please contac...

Page 12: ...ED will start flashing at 0 5sec on 0 5sec off to confirm the binding mode has been entered 4 Move the room thermostat slider to the OFF position and press the and buttons together along with the button The unit will display InSt and CONTROL BINDING 5 Press the green button to send the binding signal out to the receiver box The red LED is switched off to confirm successful binding operation If the...

Page 13: ... is on and the green one is flashing once every 3 sec on the receiver box Incorrect or incomplete binding procedure Incorrect position of the room thermostat during binding Repeat the binding procedure Repeat the binding procedure keeping approx 1 m distance between the receiver box and the room thermostat The red LED on the receiver box is illuminated Communication loss The receiver box receives ...

Reviews: