Honeywell H7625A Installation Instructions Manual Download Page 2

H7625A, H7635A HUMIDITY/TEMPERATURE SENSORS

62-0208—3

2

Output Settings (Table 1)

The board has three switch blocks:
— A six DIP switch block.
— A four DIP switch block.
— A white gang switch on a blue block.

1.

Adjust the 4-switch block according to Table 1.

NOTE: The 6-switch block normally requires no 

adjustment. (See the Appendix.)

2.

Set the gang switch (white switch in blue block) to 
correspond with the output (mA or Vdc).

NOTE: See Fig. 2 for DIP switch locations.

Table 1. Controller Compatibility 

and Output Settings.

Fig. 2. DIP switch locations and settings.

WIRING

For voltage output, shielded cable (16-22 AWG) should 
be used.

For current output, either shielded cable or twisted pair 
(16-22 AWG) can be used.

IMPORTANT

When using shielded cable, ground the shield 
only at the controller end (see Fig. 3). Grounding 
both ends can cause a ground loop.

NOTE: See Table 2 for terminal designations.

Table 2. Terminal Designations.

Fig. 3. Typical wiring diagram for transducer with two-

wire mA output with external DC power supply.

Controller

Required 

Sensor 

Output 

Setting

4-Switch Block

 Settings

Blue and 

White 

Output 

Switch

L

ON

S

PEC

Setting

4 3 2 1

W7750, W7760, 

W7761

4-20 mA — On — — 4-20 mA C7600C

W7750B,C 

W7760C, 

W7753, W7760

0-10 Vdc 

(default)

On — — On Vout

H7621/31

T7350, XL50, 

XL100, 

XL500 XF 

Modules, XFL

0-10 Vdc 

(default)

On — — On Vout

n/a

Non-Honeywell 0-5 Vdc

On — On — Vout

n/a

M22659A

NORMAL

OPERATION

OFF     ON

OFF  

ON

0-10 VDC

OFF  

ON

4-20 MA

0-5 VDC

OFF  

ON

Terminal

Designation

1

mA  out

2

Vin  (power)

3

GND (common)

4

Vdc (out)

5

20K  NTC

6

20K  NTC

mA OUTPUT

TRANSDUCER

ONLY

18 TO 36 Vdc

POWER SUPPLY

CONTROLLER, METER 
OR RECORDER

INPUT SIGNAL

COMMON

Vin

+

+

Io

M22528

GROUND

Summary of Contents for H7625A

Page 1: ...ician 4 After installation is complete check out product operation as provided in these instructions CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation CAUTION Equipment Damage Hazard Improper wiring can damage the sensor beyond repair Follow the wiring instructions carefully Location Install the device...

Page 2: ...g shielded cable ground the shield only at the controller end see Fig 3 Grounding both ends can cause a ground loop NOTE See Table 2 for terminal designations Table 2 Terminal Designations Fig 3 Typical wiring diagram for transducer with two wire mA output with external DC power supply Controller Required Sensor Output Setting 4 Switch Block Settings Blueand White Output Switch LONSPEC Setting 4 3...

Page 3: ...ISCHARGE AIR SENSOR OUTDOOR AIR SENSOR MOTION SENSOR HUMIDITY SENSOR M OS OS AS AS M HC HP HS Gnd Vin Vo 1 4 L1 HOT L2 COMPRESSOR CONTACTOR 1 COMPRESSOR CONTACTOR 2 HEAT RELAY 1 1 2 3 4 5 6 7 8 9 FAN RELAY ECONOMIZER HEAT RELAY 2 COMPRESSOR CONTACTOR 3 COMPRESSOR CONTACTOR 4 E GND OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 DI 1 DI 2 DI 3 DI 4 GND GND 24 VAC COM 24 VAC COM 24 VAC 24 VAC 24 VAC...

Page 4: ...nverting Output Signal to Percent RH 4 to 20mA Signal Example 12 mA output signal 12 4 0 16 50 RH 0 to 10 Vdc Signal Example 8 VDC transmitter signal output 8 Vdc 0 10 80 RH Table 3 Troubleshooting signal in mA 4 0 16 percent RH Problem Items to Check No reading Verify correct supply voltage at the power terminal blocks Verify correct wiring configuration and DIP switch settings Verify that termin...

Page 5: ...mitter always outputs a signal of 4 mA or 0 Vdc The sensor does not affect the transmitter output 50 RH Output for Testing Only Transmitter always outputs a signal of 12 mA 2 5 VDC or 5 VDC The sensor does not affect the transmitter output 100 RH Output Transmitter always outputs a signal of 20 mA 5 VDC or 10 VDC The sensor does not affect the transmitter output Sensor doesn t affect the transmitt...

Page 6: ...that if your humidity has drifted 1 lower over a certain time period you will be able to toggle the Increment RH Output switch 2 times in order to slide the whole curve upward 1 Decrement RH Output This DIP switch allows calibration in the same way as the Increment RH The difference is that each toggle results in a decrease of 0 5 RH Using Calibration Trim Potentiometers IMPORTANT Due to the sensi...

Page 7: ...H7625A H7635A HUMIDITY TEMPERATURE SENSORS 7 62 0208 3 ...

Page 8: ...national Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 62 0208 3 B B Rev 01 05 LonSpec is a trademark of Echelon Corporation ...

Reviews: