Instructions

These installation instructions assume the damper is already 

mounted in a duct or sleeve with the damper shaft extending 

beyond the duct or sleeve a minimum of 6 inches (152mm).
  1.  INSTALL THE STANDOFF BRACKET
Dampers with a jackshaft 

 

   Jackshaft supplied is typically 1 inch (25mm) diameter. 

For these applications the bearing must be removed 

from stand-off bracket (item #6). Mount the stand-off 

bracket with [4] thread studs (item #8) and [4] 

1

4

 -20 

splinlock nut (item #2). Orient the stand-off bracket so 

the hole is centered on the jackshaft.

Dampers without jackshaft (Shaft Extension) 

 

    Mount the stand-off bracket (item #6) spanning across 

the damper frame flanges. Fasten to the damper frame 

with [4] #14 x 

3

4

 Tek screws (item #3). Be sure not to run 

the screws into the damper linkage, which is between 

the flanges.

  2.  MOUNT ACTUATOR BRACKET
 

   Mount actuator bracket (item #7) using [4] thread studs 

(item #8) and [4] 

1

4

 - 20 nuts (item #2).

 

   NOTE: The mounting bracket may be attached in three 

positions: parallel with the duct, perpendicular up 

from the duct, or perpendicular down from the duct. 

Choose a position that offers the most clearance for the 

application.

  3.  ACTUATOR ROTATION
 

   If the fail rotation of the damper is counter clockwise the 

universal clamp should be on the side of the actuator 

showing the power direction as clockwise rotation 

(usually shipped in this orientation).

 

   To change the universal clamp to the other side, remove 

the retaining clip and then the universal clamp from the 

actuator. Move the universal clamp onto the actuator. 

When the clamp is installed, then lock in place using the 

retaining clip.

 

   NOTE: All fail rotations refer to the damper shaft rotation 

needed to achieve the desire blade fail position. If fail 

position is closed, make sure damper blades are fully 

close and ensure blade seals are compressed prior to 

tightening the actuator clamp to the damper extension 

pin or jackshaft. Inspect the damper blades and the 

damper shaft to determine the proper damper shaft 

rotation for the desired fail position. 

  4.  MOUNTING ACTUATOR
 

   Slide the actuator (item #1) over damper drive shaft. 

Install thread stud through the mounting lug on the back 

of the actuator and through the corresponding hole of 

the actuator bracket (item #7). 

Secure the thread stud to actuator bracket with #10- 

 

24 nut. Verify that the damper is in its fail position. 

Secure actuator to the damper shaft by torquing the 

screw on the actuator universal clamp to 88 in. lbs. .

5.    The wiring illustration below identifies actuator electrical 

requirements and connections. Wiring must comply 

with all applicable electrical codes.

  6.   Apply power to the actuator. The damper blades 

should fully open or close and return to the fail 

position when power is disconnected.

Orientation of Stand-off 

Bracket for a jackshaft 

driven dampers

Orientation of Stand-off 

bracket for a directly 

driven damper

Black

White

120 Volt or
24 volt

M

Wiring Illustration

Wiring Illustration

Important

A break in power of less than one second can cause the 
actuator to spring-return 5 degrees or less and remain in 
place until a break in power of longer duration

.

Model

Volts

Running

Holding

MS4120F1006

120 VAC

35W

10W

MS4120F1204
MS4620F1005

230 VAC

35W

10W

MS4620F1203
MS7510A2008

24 VAC/VDC

14W

5W

MS7510A2206

14W

MS7520A2007

16W

MS7520A2015

22W

MS7520A2205

16W

MS7520A2213

22W

MS8110A1206

24 VAC/VDC

30W

8W

MS8120F1002

24 VAC

45W

10W

MS8120F1200

464287 • MS4120 MS4620 MS8120, Rev. 9, January 2019 

Copyright 2019 © Greenheck Fan Corporation

2

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications 
without notice.

Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature 
section of the website at Greenheck.com/Resources/Library/Literature.

®

Phone: 715.359.6171 • Fax: 715.355.2399 • Parts : 800.355.5354 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

Reviews: