Replacement

a.

The external mains cable should be rewired so that it enters the enclosure above the Mains terminal
block on the

Replacement Mains Interface Board

, this ensures there is segregation between mains and

extra low voltage cables. Also, each unused cable entry point must be fitted with a plastic bung.

b.

Fit the

Replacement Mains Interface Board

on a carrier into the enclosure

o

using the screws supplied.

&

Ensure the board fixing screws are securely fitted as they form part of an earth continuity path to

the metal enclosure, this is necessary for electrical safety and for EMC compliance.

c.

Reconnect the external wiring to the terminal blocks

p

and

q

on the

Replacement Mains Interface

Board

.

d.

Check and ensure the correct End Of Line units are fitted for the respective Zone and Sector circuits.

e.

Switch ON the mains supply to the Unit and then connect the battery lead to the batteries and to
connector P7 on the

Replacement Mains Interface Board

.

f.

Using the

[Test/Eng]

menu at the control panel

[Allocate]

the loop circuit, on which the Interface unit is

connected. The interface unit should then be tested to site specific requirements.

g.

Close the enclosure door and lock it using the key.

4188-1005 issue 1_03/11_Replacement Board for 34440 MPI

3

Replacement Mains Interface Board

Installation

PB1

0C LC 01 L1 02 L2

LOOP

LOOP OUT

LOOP IN

LOOP
SPUR

PB6

+

+ -

-

AUX O/P

External
Equipment

PB2, PB3,
PB4 or PB5

S+ S-

SECTOR 1, 2, 3 or 4

10K

EOL

W

IS Sector Output

IS Galvanic
isolator (02518-10)

PB2, PB3,
PB4 or PB5

Z+ Z-

ZONE 1, 2, 3 or 4

22uF EOL

Zone Input

PB2, PB3,
PB4 or PB5

Z+ Z-

ZONE 1, 2, 3 or 4

5K6 EOL

IS Zone Input

PB2, PB3,
PB4 or PB5

S+ S-

SECTOR 1, 2, 3 or 4

10K

EOL

W

Sector Output
with Sounders

PB2, PB3,
PB4 or PB5

S+ S-

SECTOR 1, 2, 3 or 4

10K

EOL

W

Flyback

diode

Sector Output
with Inductive
load (eg Relay)

IS Galvanic
isolator (17740-30)

Auxiliary Output: 0.25A

11+

12-

1+

2-

12

11

2

1

Connected to
metal enclosure

End-of-line units

Capacitor 22uF

Resistor 470

W

yellow, violet, brown

Resistor 5K6K

W

green, blue, red

Resistor 10K

W

Brown, black, orange

To avoid damage to equipment always
configure the interface inputs and
outputs before connecting the external
circuits.

Intrinsically

safe devices

Intrinsically

safe devices

cable

length

max.

150m

cable

length

max.

150m

cable

length

max.

150m

cable

length

max.

150m

cable

length

max.

150m

The combined maximum total current
load for sectors and auxiliary output
is 0.5A.

Summary of Contents for GENT VSINTM-PCB-UPG

Page 1: ...Voltage rating 230VAC Rated Frequency 50 60Hz Rated Current 0 7A Manufacture Date XX XX L N P3 P7 DIN RAIL FOR OPTIONAL OCTAL TYPE RELAYS 34440 Mains Interface Board MAINS TERMINAL BLOCK EARTH TO DOOR DOOR BATTERY RESTRAINT FIXING POINT 2 OFF 12V 2 1Ah BATTERIES N E L P3 P4 P5 P6 P2 AC AC P7 Aux P9 Battery P8 FS1 FS2 FS3 FS4 FS5 FS6 S5 PB2 S Z Z S SECTOR ZONE1 PB3 S Z Z S SECTOR ZONE2 PB4 S Z Z S ...

Page 2: ...efore disconnecting them from their terminal blocks m this will help identify the cables for reconnection to the Replacement Mains Interface Board d Remove 34440 Mains Interface Board from the unit n and discard it safely Programming The Replacement Mains Interface Board is factory configured with all four channels as Sector outputs Use the S4 Interface Programmer kit S4 INTERFACE PROG V1 03 or gr...

Page 3: ...ould then be tested to site specific requirements g Close the enclosure door and lock it using the key 4188 1005 issue 1_03 11_Replacement Board for 34440 MPI 3 Replacement Mains Interface Board Installation PB1 0C LC 01 L1 02 L2 LOOP LOOP OUT LOOP IN LOOP SPUR PB6 AUX O P External Equipment PB2 PB3 PB4 or PB5 S S SECTOR 1 2 3 or 4 10K EOL W IS Sector Output IS Galvanic isolator 02518 10 PB2 PB3 P...

Page 4: ...eful life the packaging product and batteries should be disposed of via a suitable recycling centre and in accordance with national or local legislation Do not dispose of with your normal household waste Do not burn WEEE Directive At the end of their useful life the packaging product and batteries should be disposed of via a suitable recycling centre 24V 2 1Ahr BATTERIES PB2 S Z Z S SECTOR ZONE1 P...

Reviews: