Replacement
a.
The external mains cable should be rewired so that it enters the enclosure above the Mains terminal
block on the
Replacement Mains Interface Board
, this ensures there is segregation between mains and
extra low voltage cables. Also, each unused cable entry point must be fitted with a plastic bung.
b.
Fit the
Replacement Mains Interface Board
on a carrier into the enclosure
o
using the screws supplied.
&
Ensure the board fixing screws are securely fitted as they form part of an earth continuity path to
the metal enclosure, this is necessary for electrical safety and for EMC compliance.
c.
Reconnect the external wiring to the terminal blocks
p
and
q
on the
Replacement Mains Interface
Board
.
d.
Check and ensure the correct End Of Line units are fitted for the respective Zone and Sector circuits.
e.
Switch ON the mains supply to the Unit and then connect the battery lead to the batteries and to
connector P7 on the
Replacement Mains Interface Board
.
f.
Using the
[Test/Eng]
menu at the control panel
[Allocate]
the loop circuit, on which the Interface unit is
connected. The interface unit should then be tested to site specific requirements.
g.
Close the enclosure door and lock it using the key.
4188-1005 issue 1_03/11_Replacement Board for 34440 MPI
3
Replacement Mains Interface Board
Installation
PB1
0C LC 01 L1 02 L2
LOOP
LOOP OUT
LOOP IN
LOOP
SPUR
PB6
+
+ -
-
AUX O/P
External
Equipment
PB2, PB3,
PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K
EOL
W
IS Sector Output
IS Galvanic
isolator (02518-10)
PB2, PB3,
PB4 or PB5
Z+ Z-
ZONE 1, 2, 3 or 4
22uF EOL
Zone Input
PB2, PB3,
PB4 or PB5
Z+ Z-
ZONE 1, 2, 3 or 4
5K6 EOL
IS Zone Input
PB2, PB3,
PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K
EOL
W
Sector Output
with Sounders
PB2, PB3,
PB4 or PB5
S+ S-
SECTOR 1, 2, 3 or 4
10K
EOL
W
Flyback
diode
Sector Output
with Inductive
load (eg Relay)
IS Galvanic
isolator (17740-30)
Auxiliary Output: 0.25A
11+
12-
1+
2-
12
11
2
1
Connected to
metal enclosure
End-of-line units
Capacitor 22uF
Resistor 470
W
yellow, violet, brown
Resistor 5K6K
W
green, blue, red
Resistor 10K
W
Brown, black, orange
To avoid damage to equipment always
configure the interface inputs and
outputs before connecting the external
circuits.
Intrinsically
safe devices
Intrinsically
safe devices
cable
length
max.
150m
cable
length
max.
150m
cable
length
max.
150m
cable
length
max.
150m
cable
length
max.
150m
The combined maximum total current
load for sectors and auxiliary output
is 0.5A.