background image

External wiring

The external cables are routed into the back box using the
cable entry points on the back box. The left 4 entry points
are for the loop cables that connects to terminal block P16.
The right cable entry point is for the mains cable which is
connects to the terminal block P9.

"

All the other parts supplied with the A3 mimic

panel are fitted during the commissioning stage, however
the procedures are described here for completeness.

How to fit the inner door assembly

The following procedures describe how to fit the inner
door assembly to the backbox.

Align the inner door assembly

v

to the two hinge pin

positions

j

on the back box

u

and slide the door down

until it is seated correctly. Insert the top (removable) hinge
pin

k

and secure it by rotating the pin into the back box.

Close the inner door assembly

l

and lock it using the

fastners at position

m

. For minor adjustment of the inner

door, open the fixing screw

†

and adjust the hinge plate

…

to a required position and then secure the plate to the

backbox by tightening the screw

†

.

Where to connect the internal cables

Remove the protective cardboard cover from the Master
Repeat Card. Connect the earth lead

j

from the back box

to the inner door assembly. Connect the flat flexible cable

k

to socket P13 on the Master Repeat Card , see details

on fitting and remove of flat flexible cable.

How to disconnect a flat flexible cable

Hold the locking tab by the

edges at positions

j

and

lift it upwards one side at a

time

k

to disengage the flat

flexible cable. Then remove
the cable

l

from the

socket.

How to connect a flat flexible cable

Hold the locking tab by the
edges and lift it upwards a
little

j

and insert the flat

flexible cable

k

into the

socket. Ensure the cable
contacts are on the opposite
side to the locking tab. Push
down the locking tab

l

to

lock the cable.

Setting the switch SW3

A Customised Mimic panel or Zonal
Mimic panel requires the switch SW3
located on the Master Repeat Card to
be set to position

'0'.

4188-945_issue 2_05/10_pt1_A3 Mimic

3

A3 Mimic Panel

Data and installation

Inner door assembly

Hinge pin

Back box
assembly

Magnetic strip

Adjustable Hinge Plates

P9

L

N

FS4

3.15A(T)

mains fuse

01 L1 02 L2

0C LC

P16

Loop IN

Loop OUT

From

Mains fused spur

Loop COM

Master Repeat Card

01 L1 02 L2

0C LC

P9

L

N

N

P17

DANGER

WRITE PROTECT

L

N

FS4

P16

P4

RESET

Inner door

Back box

Fit earth lead
from back box
to inner door

Connect the flat
flexible cable from
inner door to MRC

Master Repeat Card (MRC)

P13

Top right of the new MRC

Top right of the new MRC

P13

SW3

Summary of Contents for Gent Vigilon A3 Mimic

Page 1: ...ast fire flashing option with in phase or anti phase flash The panel has its own mains derived power supply with battery for standby power in the event of mains supply failure Technical Data Panel dimensions height 403mm width 338mm depth 101mm Weight 7 9Kg without batteries 10 5Kg with batteries Storage temperature 10 to 55ºC Operating temperature 0 to 45ºC Relative humidity Non condensing Up to ...

Page 2: ...to the top side of the inner door 1 Set Mounting the backbox The A3 Customised Mimic panel can be mounted either landscape or portrait while an A3 Zonal mimic panel must only be mounted landscape when using the overlay supplied a Locate the package Back box assembly u Landscape orientation Portrait orientation b Knock out the required cable entry points from the back box c Mark out the 4 back box ...

Page 3: ...d j from the back box to the inner door assembly Connect the flat flexible cable k to socket P13 on the Master Repeat Card see details on fitting and remove of flat flexible cable How to disconnect a flat flexible cable Hold the locking tab by the edges at positions j and lift it upwards one side at a time k to disengage the flat flexible cable Then remove the cable l from the socket How to connec...

Page 4: ...he overlay in place using the magnetic strip The overlay is secured in place when the outer cover is fitted to the panel How to fit the outer cover Hook the Outer Cover over the top edge of the Back Box Close the bottom of the Outer Cover onto the Back box and secure the Outer Cover by the two captive screws on the cover using the key supplied Ensure the zonal mimic or customised mimic plan is loc...

Reviews: