LCD-SLP Product Installation Document —

 P/N LS10045-000GF-E:E  12/16/2019

3.2.1  LCD-SLP Wired to the S3 Series Panel 

Figure 3.2.1.1 illustrates terminal connections of the LCD-SLP touchscreen wired to the S3 Series panel.

Figure 3.2.1.1 LCD-SLP Wired to the S3 Series Panel

3.2.2  LCD-SLP Wired to the E3 Series Panel

Figure 3.2.2.1 illustrates the terminal connections of the LCD-SLP wired to the E3 Series panel.

Figure 3.2.2.1 LCD-SLP Wired to the E3 Series Panel

NOTE 1: 

W1 RS-485

TERMINATION 

JUMPER 

SHORT J6 TO DISABLE THE KEYPAD.
OPEN J6 TO ENABLE THE KEYPAD.

NON-RESETTABLE 24 VDC POWER IN (+)

24 VDC COMMON IN (-)

NON-RESETTABLE 24 VDC POWER OUT (+)

24 VDC COMMON OUT (-)

EXTRA GROUND

EARTH GROUND

1

1

OVERLAY 

SWITCHES

OVERLAY 

LEDS

SW1

DBG

ASSY, LCD-SLP
1120-0938 REV ___

KEYSWITCH

J6

1
2
3
4

1
2
3
4
5
6

TB2

DISPLAY

TB1

RS-485

+

ON

OFF

W1

AUX 

TERM

J5

LOCAL

HOST

(SEE NOTE 6)

10

9

2

1

1

NOTE 2:
TO J7 OF THE SLP-E3 MAIN BOARD. 
IF USED, MAKE NO CONNECTIONS 
TO TERMINAL BLOCKS TB1 OR TB2.

RS-485 COM A IN
RS-485 COM B IN

RS-485 COM A OUT
RS-485 COM B OUT

CAUTION! 
USE THESE TERMINALS 
ONLY WHEN THE LCD-SLP 
IS REMOTELY MOUNTED 
OR CONMNECTED TO AN 
ILI-MB-E3 OR ILI95-MB-E3. 
DO NOT USE THESE 
TERMINALS WHEN 
THE J5 RIBBON CABLE IS 
CONNECTED TO J7 OF 
THE SLP-E3 MAIN BOARD.

J1 J2

1

TB2

DISPLAY

O

VERLAY 

SW
IT

CH
ES

1

O

VER

LAY

 LED

S

J1

J2

SW1

DBG

NON-RESETTABLE 24 VDC POWER IN (+) FROM ILI-MB-E3 TB3 TERM 6

24 VDC COMMON IN (-) FROM ILI-MB-E3 TB3 TERM 7

NON-RESETTABLE 24 VDC POWER OUT (+) 

24 VDC COMMON OUT (-)

EXTRA GROUND

EARTH GROUND

RS-485 COM A IN FROM ILI-MB-E3 TB3 TERM 1

RS-485 COM A OUT

RS-485 COM B OUT

RS-485 COM B IN FROM ILI-MB-E3 TB3 TERM 2

ASSY, LCD-SLP
1120-0938 REV ___

1
2
3
4
5
6

TB1

RS-485

1
2
3
4

1

SHORT J6 TO DISABLE THE KEYPAD.
OPEN J6 TO ENABLE THE KEYPAD.

NOTE 1:

TO: ASM-16 TB1 TERM 3

ANU-48 TB1 TERM 3

REMOTE LCD-SLP TB2 TERM 1

LCD-E3 TB1 TERM 1

LCD-7100 TB1 TERM 5

NOTE 2:

TO: ASM-16 TB1 TERM 4

ANU-48 TB1 TERM 4

REMOTE LCD-SLP TB2 TERM 2

LCD-E3 TB1 TERM 2

LCD-7100 TB1 TERM 6

NOTE 3:

TO: ASM-16 TB1 TERM 1

ANU-48 TB1 TERM 1

REMOTE LCD-SLP TB1 TERM 1

LCD-E3 TB1 TERM 3

LCD-7100 TB1 TERM 1

NOTE 4:

TO: ASM-16 TB1 TERM 2

ANU-48 TB1 TERM 2

REMOTE LCD-SLP TB1 TERM 2

LCD-E3 TB1 TERM 4

LCD-7100 TB1 TERM 2

+

KEYSWITCH

J6

ON

OFF

W1

AUX 

TERM

J5

LOCAL

HOST

(SEE NOTE 6)

NOTE 6:
CONNECTOR J5 NOT USED 
WHEN LCD-SLP CONNECTS 
TO AN ILI-MB-E3.
DO NOT CONNECT J5 TO 
ASM-16, J1, J2, OR J3 OR
TO ANU-48 J1 OR J2.

10

9

2

1

NOTE 1: 

W1 RS-485

TERMINATION 

JUMPER 

Summary of Contents for GAMEWELL LCD-SLP

Page 1: ...L POWER REMOVE ALL SOURCES OF POWER BEFORE SERVICING REMOVING OR INSTALLING ANY UNITS S3 Series SLP E3 Smart Loop Panel Main Board E3 Series ILI MB E3 Intelligent Loop Interface Main Board E3 Series ILI95 MB E3 Intelligent Loop Interface95 Main Board NOTE E3 RELEASING PANEL OPERATOR INTERFACE INSTALLATION REQUIREMENTS The LCD SLP display panel includes optional audio visual signaling capabilities ...

Page 2: ...1 lists the systems cabinets and mounting plates that use the LCD SLP E3 Series is a registered trademark and CAMWorks is a trademark of Honeywell International Inc 2020 Copyright by Honeywell International Inc All rights reserved AHJ Authority Having Jurisdiction NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code NFPA 101 Life Safety Code NOTE COLD WATER EARTH GROUND STANDARD All m...

Page 3: ...re refer to the following documents and Section 2 6 thru Section 2 8 S3 Series Small Addressable Fire Alarm Control Panel UL Listing Document P N LS10005 051GF E Specifications LCD SLP Operating Voltage 24 VDC Operating Current 0 030 A Alarm Current 0 065 A Ground fault test impedance Zero Ohms Impedance values and ground faults are annunciated GND Fault LED or LCD SLP Relative Humidity 0 to 93 no...

Page 4: ...on 1 of the figure below 2 Mount the LCD SLP to the inside window of the outer door Insert and secure four nuts 6 32 HEX KEPS into the four hole mounting pattern of the window as shown in Location 2 of the figure below 3 Plug in the keyswitch cable to the J6 jumper on the LCD SLP as shown in Location 3 of the figure below Refer to Note 1 on the LCD SLP Wiring Diagram in Figure 3 2 1 Figure 2 6 1 1...

Page 5: ... the LCD SLP keypad to the E3BB FLUSH LCD Flush Mount Front Cover Insert and secure eight nuts 6 32 Hex Kep into the eight hole mounting pattern as shown in Location 3 of the figure below 4 Plug in the keyswitch cable to the J6 jumper on the LCD SLP touchscreen as shown in Location 4 of the figure below For information on the location of the J6 jumper on the LCD SLP touchscreen refer to Note 1 on ...

Page 6: ...alled to the E3 Series Cabinet B Inner Door 1 Mount the LCD SLP keypad to the inner door Insert and secure eight nuts into the eight hole mounting pattern as shown in Location 1 of the figure below Figure 2 7 2 1 LCD SLP Installed to the Cabinet B Inner Door NUT HEX 6 32 12 PLACES ASM 16 1 1 1 1 2 2 2 2 3 3 1 BONDING WIRE CABINET AA 2 BAY INNER DOOR LCD SLP KEYPAD 1 2 2 1 LC D SLP K EYPA D A SM 16...

Page 7: ...six nuts 6 32 into the six hole mounting pattern as shown in Location 1 of the figure below Figure 2 7 3 1 LCD SLP Installed in a Cabinet C Inner Door Figure 2 7 4 1 LCD SLP Installed in a Cabinet D Inner Door LCD SLP KEYPAD ASM 16 4PLACES MAX TELEPHONEBOX MICROPHONE BOX CABINETC INCC E3 7 BAYINNERDOOR 1 2 2 4 4 3 3 4 1 2 3 NUT HEX 6 32 24PLACES BONDING WIRE THUMBSCREWS TOSECURETHE INNERDOORTO THE...

Page 8: ... Location 5 of the figure below Figure 2 8 1 1 LCD SLP Installed to a B Slim Cabinet Outer Door 2 8 2 LCD SLP Installed to a 600XL Retrofit Display Inner Door 1 Insert the keyswitch snap in plug into the keyhole in the LCD E3 Mounting Plate as shown in Location 1 of the figure below 2 Mount the LCD SLP keypad to the pins on the LCD E3 Mounting Plate Insert and secure eight nuts 6 32 HEX KEPS into ...

Page 9: ... below 1 Mount the LCD SLP keypad to the inner door Insert and secure eight nuts 6 32 into the eight hole mounting pattern as shown in Location 1 of the figure below Figure 2 8 3 1 LCD SLP Installed in a 7200 Cabinet B Retrofit Inner Door Figure 2 8 4 1 LCD SLP Installed in a 7200 Cabinet C Retrofit Inner Door 7200CABINETB RETROFIT INNERDOOR ASM 16 7PLACES MAXIMUM LCD SLP ASM 16 1 1 1 1 2 2 2 2 4 ...

Page 10: ...85 COMM B Communications OUT See Note 3 TB2 1 24 V 24 V non resettable power IN See Notes 1 and 2 TB2 2 GND IN GROUND IN See Notes 1 and 2 TB2 3 24 V OUT 24 V non resettable power OUT See Note 2 TB2 4 GND OUT GROUND OUT See Note 2 TB2 5 GND Extra Ground TB2 6 Earth Ground Earth Ground J5 Local Connection RS 485 communications and power ribbon cable local only See Note 3 J6 Keypad Lock Jumper or Ke...

Page 11: ...CD SLP to connect to COMM A COMM B IN of the ANU 48 ASM 16 LCD E3 LCD 7100 and or RAN 7100 Do not use J5 jumper NOTE 4 Figure 3 1 2 Binary Switches Table 3 2 1 LCD SLP Installation Wiring Designations Continued 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 S W 1 S W 1 S W 1 S W 1 D IS P LA Y 1 D IS P LA Y 2 D IS P LA Y 3 D IS P LA Y 4 O FF O F F O FF O F F O FF TH E P A N E L M U S T B E P R O G R A M M E D TO ...

Page 12: ...ED OR CONMNECTED TO AN ILI MB E3 OR ILI95 MB E3 DO NOT USE THESE TERMINALS WHEN THE J5 RIBBON CABLE IS CONNECTED TO J7 OF THE SLP E3 MAIN BOARD J1 J2 1 TB2 DISPLAY OVERLAY SWITCHES 1 OVERLAY LEDS J1 J2 SW1 DBG NON RESETTABLE 24 VDC POWER IN FROM ILI MB E3 TB3 TERM 6 24 VDC COMMON IN FROM ILI MB E3 TB3 TERM 7 NON RESETTABLE 24 VDC POWER OUT 24 VDC COMMON OUT EXTRA GROUND EARTH GROUND RS 485 COM A I...

Page 13: ...isual Condition Indicators Condition Audible Visual Status Indicators Alarm Alarm situations are indicated by a one half second ON and one half second OFF pattern from the system sounder the illumination of the red alarm LED Hazard Hazard situations are reported by a Coded 4 pattern Supervisory Supervisory events are indicated by a continuous tone from the system piezo sounder and the illumination...

Page 14: ...s the System Status Hazard Alarm to show a CO Alarm event If this event is activated the following appears on the display HAZARD LED lights BLUE CO ALARM displays Blue banner appears Figure 4 2 3 Example of Supervisory Displays the System Status Supervisory Off Normal to show an Off Normal event If this event is activated the following appears on the display Supervisory LED lights YELLOW Superviso...

Page 15: ...ice in the Releasing Zone went into alarm but not enough devices went into alarm to trigger the Pre Release Timer Pre Release Color RED Indicates that a pre programmed number and the type of initiating devices in the Releasing Zone have gone into alarm to activate the Pre Release Timer After the timer expires a release occurs Release Color RED Indicates that the Pre Release Timer expired and a rel...

Page 16: ...The Pre Alarm LED changes to steady RED Pre Alarm appears on the display See Note 1 in Table 5 2 1 Abort Figure 5 2 3 Pre Alarm Abort LED Activated If the Releasing Zone aborts before the Release stage after you press the Abort switch the following occurs The Abort LED turns on steady YELLOW Abort appears on the display Pre Release Figure 5 2 4 Pre Release LED Activated If more than one device in ...

Page 17: ...urs The system shuts off the solenoid Cutoff appears on the display All Releasing stage LEDs are OFF See Note 1 in Table 5 2 1 Squirt Figure 5 2 7 Release LED Red Activated If a user presses a Squirt switch the following occurs The Release LED temporarily changes to steady RED The releasing output is temporarily reactivated to open the valve The System releases the extinguishing agent After the Sq...

Page 18: ...nstructions 9000 0580 RPT E3 UTP Repeater E3 Unshielded Twisted Pair Installation Instructions 9000 0581 DACT E3 Digital Alarm Communicator Transmitter Installation Instructions 9000 0582 LCD E3 Liquid Crystal Display E3 Installation Instructions 9001 0017 ILI95 MB E3 Intelligent Loop Interface 95 Main Board Installation Instructions 9001 0018 ILI95 S E3 Intelligent Loop Interface 95 Expansion Boa...

Reviews: