2

LCD-SLP Product Installation Document —

 P/N LS10045-000GF-E:E  12/16/2019

Section 1: Installation

2.1 Standards

The LCD-SLP module complies and is intended to be installed in accordance with the following Standards:

National Fire Protection Association

UL Standards, UL 864 9th and 10th Edition 

Per the UL Continuing Certification Program, UL 864 9th edition fire alarm control equipment will retain certification after the 

rollout of UL 10th edition (12/2/2018). 

Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when 

approved by the local Authority Having Jurisdiction (AHJ).
For product compliance, refer to the UL listing cards located on the UL online certification directory. 

https://iq.ulprospector.com  

 

2.2  Installation Requirements

Installers must be Gamewell-FCI Factory Certified to program this product. For additional information on this product, contact the 
Gamewell-FCI Customer Support to schedule Factory Certified Training. 
All components of the S3 Series and E3 Series Systems should be installed per the following requirements:
• Installations are to be indoors only, in dry locations, protected from rain, water, and rapid changes in temperature that could cause 

condensation. Equipment must be securely mounted on rigid, permanent walls.

• Operating temperature shall not exceed the range of 32° to 120° F (0 to 49° C).
• Operating humidity not to exceed 93% non-condensing at 90° F (32° C).
• There should be adequate space around the installation to allow easy access for operation and servicing.
• All sub-assemblies and components are to be located in compliance with local, national codes and the manufacturer’s 

recommendations.

• All installation field wiring shall be in compliance with local and national codes.

2.3  LCD-SLP Assembly Installation Options

Table 2.3.1 lists the systems, cabinets, and mounting plates that use the LCD-SLP.

E3 Series

®

 is a registered trademark and CAMWorks™ is a trademark of Honeywell International Inc.

©2020 Copyright by Honeywell International Inc. All rights reserved.

• AHJ                     

Authority Having Jurisdiction    • NFPA 72                     

National Fire Alarm Code          

• NFPA 70

National Electrical Code

• NFPA 101

Life Safety Code

NOTE:

COLD WATER/EARTH GROUND STANDARD

:

All modules must be connected to an earth ground connection. Failure to make a proper earth ground connection from a 

metallic cold water pipe or driven ground rod will result in loss of surge protection, reduce the tolerance of the system to 

transients, and will adversely affect the operation of the system. Panel neutral or conduit ground is not acceptable; minimum 

wire size is 14 AWG.

System Cabinets, 

Inner/Outer Doors

Part Number       

Cabinet 

Dimensions                                 

Figure that shows the 

Installation Assembly

S3 Series Cabinets

SLP-BB Cabinet, B Cabinet

SLP-BB

14.9”W x 21.5”H x 4.5”D

Figure 2.6.1.1

S3 Series, B-Size Cabinet

E3BB-BB/RB

19 3/8”W x 19 3/8”H x 4.5”D

Figure 2.6.2.1

E3 Series Inner Doors and Plates  

Cabinet A2 Inner Door

E3BB-BA2

CAB A2: 13 1/4”W x 10”H x 4.1/2”D

Figure 2.7.1.1.1

E3BB-FLUSH-LCD Cab A2 Front Cover          E3BB-FLUSH-LCD    CAB A2” 13 1/4”W x 10”H x 4.1/2”D

Figure 2.7.1.2.1

CAB AA 2-Bay Inner Door

E3BB-BAA

CAB AA: 19 1/4”W x 10”H x 4.5”D

Figure 2.7.1.3.1

CAB B Inner Door

E3ID2-B

CAB B:   19 3/8”W x 19 3/8”H x 4.5”D Figure 2.7.2.1

CAB C INCC-E3 Plate, 7-Bay Inner Door   E3ID2-C

CAB C:   19 3/8”W x 30”H x 4.5”D

Figure 2.7.3.1

CAB D INCC CAB-D 13-Bay Inner Door       E31D2-D

CAB D:   19 3/8”W x 41”H x 4.5”D

Figure 2.7.4.1

Retrofit Cabinets

B-Slim Cab Outer Door

E3BB-RBSLIM

B-SLIM: 14”W x 20”H x 4.5”D

Figure 2.8.1.1

600XL Retrofit Inner Door

IF600-RETROFIT 600XL:  30”W x 22”H x 5.5”D

Figure 2.8.2.1

7200 Cab-B Retrofit Inner Door

7200-B-RETROFIT             7200 CAB B:21”W x 28.5”H x 4”D

Figure 2.8.3.1

7200 Cab-C Retrofit Inner Door

7200-C-RETROFIT 7200 CAB C:21”W x 38”H x 4”D

Figure 2.8.4.1

Table 2.3.1 LCD-SLP Assembly Installation Options

Summary of Contents for GAMEWELL LCD-SLP

Page 1: ...L POWER REMOVE ALL SOURCES OF POWER BEFORE SERVICING REMOVING OR INSTALLING ANY UNITS S3 Series SLP E3 Smart Loop Panel Main Board E3 Series ILI MB E3 Intelligent Loop Interface Main Board E3 Series ILI95 MB E3 Intelligent Loop Interface95 Main Board NOTE E3 RELEASING PANEL OPERATOR INTERFACE INSTALLATION REQUIREMENTS The LCD SLP display panel includes optional audio visual signaling capabilities ...

Page 2: ...1 lists the systems cabinets and mounting plates that use the LCD SLP E3 Series is a registered trademark and CAMWorks is a trademark of Honeywell International Inc 2020 Copyright by Honeywell International Inc All rights reserved AHJ Authority Having Jurisdiction NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code NFPA 101 Life Safety Code NOTE COLD WATER EARTH GROUND STANDARD All m...

Page 3: ...re refer to the following documents and Section 2 6 thru Section 2 8 S3 Series Small Addressable Fire Alarm Control Panel UL Listing Document P N LS10005 051GF E Specifications LCD SLP Operating Voltage 24 VDC Operating Current 0 030 A Alarm Current 0 065 A Ground fault test impedance Zero Ohms Impedance values and ground faults are annunciated GND Fault LED or LCD SLP Relative Humidity 0 to 93 no...

Page 4: ...on 1 of the figure below 2 Mount the LCD SLP to the inside window of the outer door Insert and secure four nuts 6 32 HEX KEPS into the four hole mounting pattern of the window as shown in Location 2 of the figure below 3 Plug in the keyswitch cable to the J6 jumper on the LCD SLP as shown in Location 3 of the figure below Refer to Note 1 on the LCD SLP Wiring Diagram in Figure 3 2 1 Figure 2 6 1 1...

Page 5: ... the LCD SLP keypad to the E3BB FLUSH LCD Flush Mount Front Cover Insert and secure eight nuts 6 32 Hex Kep into the eight hole mounting pattern as shown in Location 3 of the figure below 4 Plug in the keyswitch cable to the J6 jumper on the LCD SLP touchscreen as shown in Location 4 of the figure below For information on the location of the J6 jumper on the LCD SLP touchscreen refer to Note 1 on ...

Page 6: ...alled to the E3 Series Cabinet B Inner Door 1 Mount the LCD SLP keypad to the inner door Insert and secure eight nuts into the eight hole mounting pattern as shown in Location 1 of the figure below Figure 2 7 2 1 LCD SLP Installed to the Cabinet B Inner Door NUT HEX 6 32 12 PLACES ASM 16 1 1 1 1 2 2 2 2 3 3 1 BONDING WIRE CABINET AA 2 BAY INNER DOOR LCD SLP KEYPAD 1 2 2 1 LC D SLP K EYPA D A SM 16...

Page 7: ...six nuts 6 32 into the six hole mounting pattern as shown in Location 1 of the figure below Figure 2 7 3 1 LCD SLP Installed in a Cabinet C Inner Door Figure 2 7 4 1 LCD SLP Installed in a Cabinet D Inner Door LCD SLP KEYPAD ASM 16 4PLACES MAX TELEPHONEBOX MICROPHONE BOX CABINETC INCC E3 7 BAYINNERDOOR 1 2 2 4 4 3 3 4 1 2 3 NUT HEX 6 32 24PLACES BONDING WIRE THUMBSCREWS TOSECURETHE INNERDOORTO THE...

Page 8: ... Location 5 of the figure below Figure 2 8 1 1 LCD SLP Installed to a B Slim Cabinet Outer Door 2 8 2 LCD SLP Installed to a 600XL Retrofit Display Inner Door 1 Insert the keyswitch snap in plug into the keyhole in the LCD E3 Mounting Plate as shown in Location 1 of the figure below 2 Mount the LCD SLP keypad to the pins on the LCD E3 Mounting Plate Insert and secure eight nuts 6 32 HEX KEPS into ...

Page 9: ... below 1 Mount the LCD SLP keypad to the inner door Insert and secure eight nuts 6 32 into the eight hole mounting pattern as shown in Location 1 of the figure below Figure 2 8 3 1 LCD SLP Installed in a 7200 Cabinet B Retrofit Inner Door Figure 2 8 4 1 LCD SLP Installed in a 7200 Cabinet C Retrofit Inner Door 7200CABINETB RETROFIT INNERDOOR ASM 16 7PLACES MAXIMUM LCD SLP ASM 16 1 1 1 1 2 2 2 2 4 ...

Page 10: ...85 COMM B Communications OUT See Note 3 TB2 1 24 V 24 V non resettable power IN See Notes 1 and 2 TB2 2 GND IN GROUND IN See Notes 1 and 2 TB2 3 24 V OUT 24 V non resettable power OUT See Note 2 TB2 4 GND OUT GROUND OUT See Note 2 TB2 5 GND Extra Ground TB2 6 Earth Ground Earth Ground J5 Local Connection RS 485 communications and power ribbon cable local only See Note 3 J6 Keypad Lock Jumper or Ke...

Page 11: ...CD SLP to connect to COMM A COMM B IN of the ANU 48 ASM 16 LCD E3 LCD 7100 and or RAN 7100 Do not use J5 jumper NOTE 4 Figure 3 1 2 Binary Switches Table 3 2 1 LCD SLP Installation Wiring Designations Continued 4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1 S W 1 S W 1 S W 1 S W 1 D IS P LA Y 1 D IS P LA Y 2 D IS P LA Y 3 D IS P LA Y 4 O FF O F F O FF O F F O FF TH E P A N E L M U S T B E P R O G R A M M E D TO ...

Page 12: ...ED OR CONMNECTED TO AN ILI MB E3 OR ILI95 MB E3 DO NOT USE THESE TERMINALS WHEN THE J5 RIBBON CABLE IS CONNECTED TO J7 OF THE SLP E3 MAIN BOARD J1 J2 1 TB2 DISPLAY OVERLAY SWITCHES 1 OVERLAY LEDS J1 J2 SW1 DBG NON RESETTABLE 24 VDC POWER IN FROM ILI MB E3 TB3 TERM 6 24 VDC COMMON IN FROM ILI MB E3 TB3 TERM 7 NON RESETTABLE 24 VDC POWER OUT 24 VDC COMMON OUT EXTRA GROUND EARTH GROUND RS 485 COM A I...

Page 13: ...isual Condition Indicators Condition Audible Visual Status Indicators Alarm Alarm situations are indicated by a one half second ON and one half second OFF pattern from the system sounder the illumination of the red alarm LED Hazard Hazard situations are reported by a Coded 4 pattern Supervisory Supervisory events are indicated by a continuous tone from the system piezo sounder and the illumination...

Page 14: ...s the System Status Hazard Alarm to show a CO Alarm event If this event is activated the following appears on the display HAZARD LED lights BLUE CO ALARM displays Blue banner appears Figure 4 2 3 Example of Supervisory Displays the System Status Supervisory Off Normal to show an Off Normal event If this event is activated the following appears on the display Supervisory LED lights YELLOW Superviso...

Page 15: ...ice in the Releasing Zone went into alarm but not enough devices went into alarm to trigger the Pre Release Timer Pre Release Color RED Indicates that a pre programmed number and the type of initiating devices in the Releasing Zone have gone into alarm to activate the Pre Release Timer After the timer expires a release occurs Release Color RED Indicates that the Pre Release Timer expired and a rel...

Page 16: ...The Pre Alarm LED changes to steady RED Pre Alarm appears on the display See Note 1 in Table 5 2 1 Abort Figure 5 2 3 Pre Alarm Abort LED Activated If the Releasing Zone aborts before the Release stage after you press the Abort switch the following occurs The Abort LED turns on steady YELLOW Abort appears on the display Pre Release Figure 5 2 4 Pre Release LED Activated If more than one device in ...

Page 17: ...urs The system shuts off the solenoid Cutoff appears on the display All Releasing stage LEDs are OFF See Note 1 in Table 5 2 1 Squirt Figure 5 2 7 Release LED Red Activated If a user presses a Squirt switch the following occurs The Release LED temporarily changes to steady RED The releasing output is temporarily reactivated to open the valve The System releases the extinguishing agent After the Sq...

Page 18: ...nstructions 9000 0580 RPT E3 UTP Repeater E3 Unshielded Twisted Pair Installation Instructions 9000 0581 DACT E3 Digital Alarm Communicator Transmitter Installation Instructions 9000 0582 LCD E3 Liquid Crystal Display E3 Installation Instructions 9001 0017 ILI95 MB E3 Intelligent Loop Interface 95 Main Board Installation Instructions 9001 0018 ILI95 S E3 Intelligent Loop Interface 95 Expansion Boa...

Reviews: