Honeywell Gamewell FCI Velociti Series Installation And Maintenance Instructions Download Page 1

AOM-2SF Supervised Control Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEFORE INSTALLING

This information is included as a quick reference installation guide. Refer to 
the control panel installation manual for detailed system information. If the 
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.

NOTICE: This manual should be left with the owner/user of this equipment.

GENERAL DESCRIPTION

AOM-2SF Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected us-
ing the built-in rotary switches. This module is used to switch an external 
power supply, which can be a DC power supply or an audio amplifier (up 
to 80 VRMS), to notification appliances. It also supervises the wiring to the 
connected loads and reports their status to the panel as NORMAL, OPEN, or 
SHORT CIRCUIT. The AOM-2SF has two pairs of output termination points 
available for fault-tolerant wiring and a panel-controlled LED indicator.

COMPATIBILITY REQUIREMENTS

To ensure proper operation, this module shall be connected to a compatible 
Gamewell-FCI system control panels only (list available from Gamewell-FCI).

MOUNTING

The AOM-2SF mounts directly to 4-inch square electrical boxes (see Figure 
2A). The box must have a minimum depth of 2

1

/

8

 inches. Surface mounted 

electrical boxes (SMB500) are available. The module can also mount to the 
DNR(W) housing.

SPECIFICATIONS

Normal Operating Voltage: 

15 to 32 VDC

Maximum Current Draw: 

6.5 mA (LED on)

Average Operating Current: 

375µA (LED flashing - in Velociti Mode); 350µA (LED flashing - in CLIP mode)

Maximum NAC Line Loss: 

4 VDC

External Supply Voltage (between Terminals T10 and T11)
 

Maximum (NAC): 

Regulated 24 VDC

 

Maximum (Speakers): 

70.7 V RMs, 50W

Drain on External Supply: 

1.7 mA Maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply

Temperature Range: 

32°F to 120°F (0°C to 49°C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 

4.675” H x 4.275” W x 1.4” D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box; CB500 Barrier

I56-355

0-008

Velociti

®

 Series

WIRING

NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the 
CB500 Module Barrier must be used to meet UL requirements for the separa-
tion of power-limited and nonpower-limited terminals and wiring. The barrier 
must be inserted into a 4˝ × 4˝ × 2

1

/

8

˝ junction box, and the control module 

must be placed into the barrier and attached to the junction box (Figure 2A). 
The power-limited wiring must be placed into the isolated quadrant of the 
module barrier (Figure 2B).

1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.   Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length 
is 

1

/

4

“ to 

3

/

8

”). Exposed conductor should be secured under the clamping plate 

and should not protrude beyond the terminal block area. Caution: Do not loop 
wire under terminals. Break wire run to provide supervision of connections.

IMPORTANT: When using the AOM-2SF for audio applications, remove Jumper 
(J1) and discard. The Jumper is located on the back as shown in Figure 1B. J1 
must be removed whenever power supply monitoring feature is not required.

NOTE:  All references to power limited represent “Power Limited (Class 2)”. 

All references to Class A also include Class X.

RELAY CONTACT RATINGS:

CURRENT RATING

MAXIMUM VOLTAGE

LOAD DESCRIPTION

APPLICATION

2 A

25 VAC

PF = 0.35

Non-coded

3 A

30 VDC

Resistive

Non-coded

2 A

30 VDC

Resistive

Coded

0.46 A

30 VDC

(L/R = 20ms) 

Non-coded

0.7 A

70.7 VAC

PF = 0.35

Non-coded

0.9 A

125 VDC

Resistive

Non-coded

0.5 A

125 VAC

PF = 0.75

Non-coded

0.3 A

125 VAC

PF = 0.35

Non-coded

12 Clintonville Road

Northford, CT 06472-1653

Phone: 203.484.7161; Fax: 203.484.7118

www.gamewell-fci.com

  

I56-3550-008 

 

 06/19/2018