Programming Options
uIP Code License
Section 5: Programming Options
THE FOLLOWING ARE GAMEWELL-FCI PROGRAMMING SETTINGS
THAT WILL BE MODIFIED FOR CAMWORKS PROGRAMMING.
Notice to Users, Installers, Authorities Having Jurisdiction and Other Involved Parties:
This product uses the CAMWorks™ Programming. You cannot program this product from the Display Panel. To program
this product, you must contact your Gamewell-FCI Customer Support Representative to schedule a Factory Certified
Training Class. Basic programming options are done using an AUTO CONFIG program and are described in the next
Section.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must
be limited to specific values or not used at all as indicated in the Table 5.1.
5.1 uIP Code License
From uIP
©
uIP
©
is an open source software, licensed under the following BSD-style license:
Copyright (c) 2001-2006, Adam Dunkels and the Swedish Institute of Computer Science All rights reserved.
NOTE:
NOTICE to users, installers, Authorities Having Jurisdiction (AHJ), and other involved parties:
This product incorporates field programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL Standard 864 9th Edition, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Programmable Feature
Permitted in UL 864 Possible Settings
UL Permitted
Settings
Trouble Reminder
Yes
Enabled/Disabled
Enabled (Default)
Supervisory Sounder Cadence
Yes
Steady/Pulsed
Steady/Pulsed
PAS Acknowledge Time
Yes
1 to 3600 Seconds
15 Seconds (Default)
PAS Investigate Time
Yes
1 to 3600 Seconds
180 Seconds (Default)
Standard NAC Codes:
Yes
Steady (Default)
Temporal 3 (ANSI S3.41)
Temporal 3
Temporal 3
March Time 60 BPM
March Time 60 BPM
March Time 120 BPM
March Time 120 BPM
Steady
Steady
California Code
California Code
Coded 4’S
Coded 4’S
DACT:
- Daily Max # of ALARM Reports
Yes
Unlimited or 5 to 315
by increments of 5
Unlimited (Default)
- Daily Max # of Supervisory Reports
Yes
Unlimited or 5 to 155
by increments of 5
10 (Default)
- Daily Max # of Trouble Reports
Yes
Unlimited or 5 to 155
by increments of 5
10 (Default)
AC Fail Reporting Delay by DACT
Yes
1 to 31 hours
1 to 3 hours
Alarm Event Display Priority
No
CO Highest/Fire
Highest (Default)
FIRE is Highest Priority
Releasing Delay
Yes
CAMWorks Timer User
Programmable 1 to
3600 Seconds
Up to 60 Seconds
Maximum
Table 5.1 Programming Options
NOTE:
SOFTWARE WARRANTY DISCLAIMER:
THIS SOFTWARE IS PROVIDED BY THE AUTHOR ‘AS IS’ AND ANY EXPRESS OR IMPLIED
WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE AUTHOR
BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL
DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR
SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION). HOWEVER, CAUSED
AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT
(INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS
SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE.