AA-100/AA-120 Audio Amplifiers Installation/Operation Manual — P/N 9000-0573:C 03/12/2020
11
Section 3: Primary and Secondary Power for the Audio
Amplifiers
Primary power required the for AA-100, and AA-120 Amplifiers are 120 VAC and primary power
required for the AA-100E, and AA-120E are 220/240 VAC. Secondary power (24 VDC battery)
connections must be made at the designated terminals shown in Figure 2.2 and Figure 2.4. Second-
ary power may be obtained from any source of 24 VDC which is Listed for Fire Alarm Signaling
and has sufficient alarm and standby capacity (CHG-120). Use Table 3.1, Table 3.2 and Table 3.3
to calculate amplifier secondary (battery) power requirements.
NOTE:
AC POWER MUST BE CONNECTED TO THE SAME CIRCUIT AS THE 7100 SERIES
CONTROL PANEL.
Device
Number of
Devices
Secondary
Current Draw in
Standby
Standby Current
in Amps
AA-100/AA-100E Primary Amplifiers [ ]
x
0.050
=
AA-120/AA-120E Primary Amplifiers [ ]
x
0.050
=
AA-120/AA-120E Backup Amplifiers [ ]
x
0.050
=
Additional devices powered from the
power supply during a standby
condition
[ ]
x
[ ]
=
Total Amplifier Current Draw in
Standby
=
NOTE:
The AA-120/AA-120E must be used to back-up the AA-100/AA-100E.
Table 3.1 Secondary Current in Standby
Device
Number of
Devices
Secondary
Current Draw in
Alarm
Standby Current
in Amps
AA-100/AA-100E Primary Amplifiers [ ]
x
7.3
=
AA-120/AA-120E Primary Amplifiers [ ]
x
7.3
=
AA-120/AA-120E Backup Amplifiers
[ ]
x
0.30
=
Additional devices powered from the
power supply during a standby
condition
[ ]
x
[ ]
=
Total Amplifier Current Draw in Alarm =
Table 3.2 Secondary Current in Alarm
Secondary Current Draw in
Standby (from Table 3.1)
Required Standby Time
Battery Requirements
in Amp/Hours
[ ]
x
24 or 60 Hours
=
Secondary Current Draw
=
[ ]
x
(Enter 0.25 for 15 minutes)
=
Table 3.3 Total Amplifier Secondary Current Draw
NOTE:
Maximum alarm current from 25AH batteries must not exceed 9A.
Maximum alarm current from 55AH batteries must not exceed 20A.