background image

AA-100/AA-120 Audio Amplifiers

Installation/Operation Manual

Document: 9000-0573   Rev: C

03/12/2020    ECN: 19-0578

Summary of Contents for Gamewell-FCI AA-100

Page 1: ...AA 100 AA 120 Audio Amplifiers Installation Operation Manual Document 9000 0573 Rev C 03 12 2020 ECN 19 0578 ...

Page 2: ...f detector may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increa...

Page 3: ...oards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tighten ing may dama...

Page 4: ...ware and the appropriate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page...

Page 5: ...acts 6 1 1 4 Backup Amplifiers 6 1 1 5 Cabinet Mounting 7 1 2 Mass Notification System MNS 7 1 2 1 Mass Notification System Documentation 8 1 3 Standards 8 Section 2 Speaker Switching 9 Section 3 Primary and Secondary Power for the Audio Amplifiers 11 Section 4 Installing the Amplifiers 12 Section 5 Terminals and Connectors 13 5 1 Adjusting the Audio Gain Level 14 5 1 1 Procedure to Adjust the Aud...

Page 6: ...utput is provided The power taken from this output must not exceed 120 watts total A four wire high level output return circuit must be employed when output wiring supervision is required The AA 120 AA 120E output wiring must employ the 4 wire configuration when the output wiring con nects to the AOM modules located in another cabinet Cut R 100 to enable output wiring supervi sion in the AA 120 AA...

Page 7: ...the Gamewell FCI MNS Mass Notification System Autonomous Control Unit ACU Main Command Center E3 LOC Remote Command Center E3 Broadband System Distributed System E3 Classic System Bulk Amplifier System AM 50 Series Amplifiers AOM TELF AOM 2SF AM 50 Series Amplifiers AA 100 AA 120 Amplifiers ANU 48 Remote Annunciator ASM 16 Addressable Switch Module ANU 48 Remote Annunciator ACT 1 ACT 4 Interface t...

Page 8: ...inuing Certification Program UL 864 9th edition fire alarm control equipment will retain certification after the roll out of UL 10th edition 12 2 2018 Installations of UL 864 10th Edition certified equipment are permitted to use UL864 9th Edition certified equipment when approved by the local Authority Having Jurisdiction AHJ For product compliance refer to the UL ULC listing cards located on the ...

Page 9: ...upervision in four wire mode AA 100 AA 100E Upper Board 70 V Transformer Connection AA 120 AA 100E only R100 SLC Module polarities are shown in alarm High Level Audio Return 4 wire mode required for AA 100 AA 100E Control Module AOM AA 100 AA 100E High Level Audio Out 70 7V Supervised Class 2Power Limited Speaker Switching Circuit NFPA Class B Speakers must be Listed for fire protection Maximum Lo...

Page 10: ... to r C o n n ect m o d u les to L isted co m p atib le G am ew ell F C I co n tro l p an els o n ly C o m m u n icatio n L in e 28 V D C m ax S h ield ed tw isted p air Is reco m m en d ed A A 120 A A 120 E U p p er B o ard Speaker Sw itching C ircuit N FPA C lass A Speakers m ust be listed for fire protection M axim um Load 43 75 w atts m ax U p to 70 7 VR M S 35 pow er factor C ontrol M odule A...

Page 11: ...ary Amplifiers x 0 050 AA 120 AA 120E Primary Amplifiers x 0 050 AA 120 AA 120E Backup Amplifiers x 0 050 Additional devices powered from the power supply during a standby condition x Total Amplifier Current Draw in Standby NOTE The AA 120 AA 120E must be used to back up the AA 100 AA 100E Table 3 1 Secondary Current in Standby Device Number of Devices Secondary Current Draw in Alarm Standby Curre...

Page 12: ...AA 100E and AA 120 AA 120E amplifiers mount directly in the FCI DR C4B or DR D4B backbox Use the two 8 nuts and lock washers provided to secure the amplifier to the PEM studs on the back panel of the backbox Figure 4 1 illustrates the DR D4B cabinet installation Figure 4 1 DR Series Cabinet Diagram DR Series Cabinet 8 lockwasher Amplifier ...

Page 13: ...ow level input and high level output P connectors are primarily used for in cabinet applications where the wiring to or from the amplifier remains in the same cabinet For multiple cabinet applications hardwire the systems using Terminal blocks P3 and P8 When more than one cabinet is required cabinets must be mounted adjacent to each other and all interconnecting wiring must be installed in conduit...

Page 14: ...ll amplifiers and associated circuitry adjust the low level audio input to the amplifier set for normal standby To adjust the audio gain level do the following Figure 5 1 1 1 shows the Audio Gain switch 1 Use a small slotted screwdriver to position the rotary switch until the NORMAL LEVEL LED is lit and the INCORRECT LEVEL LED is off 2 The audio gain is properly adjusted Figure 5 1 1 1 Audio Gain ...

Page 15: ...l LED are on the audio level adjustments is too high Battery Trouble LED The battery voltage has fallen below a sufficient level Brownout LED AC power source has fallen below an acceptable level Output Trouble LED An open short circuit condition exists in the 4 wire high level output or 70 V transformer on the AA 100 AA 100E Input Trouble LED Loss of the low level audio input signal or internal am...

Page 16: ...up one or more amplifiers In the event of an amplifier failure the backup amplifier switching is automatic Figure 6 1 illustrates the back up amplifiers wiring Figure 6 1 Back up Amplifiers Wiring Diagram Audio input from INI VGE Voice Gateway AA 100 AA 100E Output AA 100 AA 100E Output AA 120 AA 120E Output Backup Amplifier AA 100 AA 100E or AA 120 AA 120E ...

Page 17: ...AA 100 AA 120 Audio Amplifiers Installation Operation Manual P N 9000 0573 C 03 12 2020 17 Using a Back up Amplifier Notes ...

Page 18: ...g 10 Terminals and Connectors 14 Trouble Contacts 6 B Backup Amplifier 17 I INI VGE Voice Gateway 6 Installation DR D4B Cabinet 13 FCI DR C4B 13 M Mass Notification System Autonomous Control Unit ACU Main Command Center 7 E3 Broadband Voice Evacuation System 7 E3 Classic Voice Evacuation 7 E3 Local Operating Console LOC Re mote Command Center 7 Mass Notification System MNS 7 P Primary Power AA 100...

Page 19: ...T TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the only warranty made b...

Page 20: ...9000 0573 C 06 20 2020 Honeywell International Inc Honeywell Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 203 484 7161 www gamewell fci com ...

Reviews: