Preconfiguration checklist
gtap.genetec.com | Honeywell Galaxy Control Panel Integration Guide 5.2
17
EN.550.007-V5.2.C4(3) | Last updated: March 11, 2014
Configure the control panel for IP communication
If you want the Security Center server to communicate with the local Galaxy Dimension control
panel using IP communication, you must configure the Ethernet module E080-4
communication settings on the control panel.
For more information about configuring the Ethernet module, see your Honeywell
documentation.
NOTE
If you are using RS-232 communication, you do not need to perform these steps. See
"Configure the control panel for RS-232 communication"
Before you begin:
Install the Honeywell Galaxy Ethernet module E080-4 with firmware
version 3.02.
1
Set the
IP Address
of the Ethernet module.
For more information about setting the module IP address, see “56.4.1.1 IP Address” in the
Honeywell Galaxy Dimension Installer Manual
.
2
Set the alarm signalling
Format
as
SIA
, and the
SIA level
to level 4.
SIA level 4 allows Security Center to control the Galaxy Dimension control panel.
For more information about programming the SIA format, see “56.4.2.1 = SIA (0-4)
Security Industries Association” in the
Honeywell Galaxy Dimension Installer Manual
.
3
Using a keypad on your control panel, set the trigger event status to
On
.
4
Repeat step
for each trigger event.
5
Set the destination
IP address
and
Port number
of Security Center.
By default, the Security Center port number is 10002.
For more information about configuring the Primary IP’s IP address and port number, see
“56.4.2.2 - Primary IP” in the
Honeywell Galaxy Dimension Installer Manual
.
6
Create the
Account Number (Account No.).
The account number must be a unique number that identifies the site. It can have up to six
digits.
Best practice:
Do not start the account number with a zero.
For more information about creating an account number, see “56.4.2.4 - Account No.” in the
Honeywell Galaxy Dimension Installer Manual
.
7
Using a keypad on your control panel, set the destination
Receiver
option to
Single
.
Selecting
Single
indicates that the Primary IP destination is used for signalling alarms.
For more information about setting the Receiver option, see “56.4.2.5 - Receiver” in the
Honeywell Galaxy Dimension Installer Manual
.
8
Set the
Protocol
format to
TCP
(Transmission Control Protocol).
For more information about setting the protocol, see “56.4.2.8 - Protocol” in the
Honeywell
Galaxy Dimension Installer Manual
.
9
Configure the
Remote access
settings for the control panel.