FL-PS Series Instruction Manual —
P/N LS10227-001FL-E:B 3/29/2021
Installation
FACP with FL-PS Power Supply in Slave Mode
2.5 FACP with FL-PS Power Supply in Slave Mode
In this application, an FL-PS power supply, configured as a Slave unit, is connected to a master FACP programmed for synchronized
output. .
The following notes apply to Figure 2.7 on page 16
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Use only devices from the same manufacturer in each system.
3.
Set Output DIP Switch: position 3=ON, 4 = OFF, 5 = ON, 6 = OFF.
4.
If the FACP has a dedicated sync output connector, wire the remote sync output connector to Input #1 terminals 2 and 3.
5.
Input#1 is mapped to Slave mode output in this example, but it can programmed to another input using the DIP switches.
6.
Notification appliances cannot be installed on the FACP control circuit connecting to the FL-PS input circuits.
2.6 FL-PS Power Supply in Master Mode Connected to FACP
In this application, a master FL-PS power supply, set for synchronization, is connected to an FACP with non-synchronized output.
The following notes apply to Figure 2.8.
1.
Refer to NFPA 72, Chapter 4-4, Visible Characteristics, Public Mode.
2.
Set Output DIP switches to the desired sync protocol as described below. Refer to the
Device Compatibility Document
for
compatible devices.
TB15
FL-PS
FACP
NAC programmed for sync
or remote sync output
ELR for
FACP
NAC
Figure 2.7 Supervised Master/Slave Connections
DIP Switch Position
Synchronization Type
3
4
5
6
ON
OFF
ON
OFF
Slave mode (NAC follower)
OFF
ON
ON
OFF
Master mode - ANSI Temporal (Temporal 3)
ON
ON
ON
OFF
Master mode - CO Temporal (Temporal 4)
OFF
OFF
OFF
ON
Master mode - Amseco/Potter
OFF
ON
OFF
ON
Master mode - Gentex
OFF
OFF
ON
ON
Master mode - System Sensor
OFF
ON
ON
ON
Master mode - Wheelock
ON
OFF
OFF
ON
Master mode, Selective Silence - Amseco/Potter
ON
ON
OFF
ON
Master mode, Selective Silence - Gentex
TB15
FL-PS
Figure 2.8 Supervised FACP to Master Connections (non-synchronized source)
FACP
(also can be triggered by a
control module or relay module)
NAC with no synchronization
NAC1
ELR for
FACP
NAC