Honeywell Fire-Lite ANN-LC Product Installation Download Page 2

2

ANN-LC Product Installation Document —

 P/N LS10158-000FL-E:C  7/28/2015

1. Place the ANN-LC flat against the inside back wall of the FACP backbox. Position both bracket mounting tabs above 

the two embossed protrusions in the backbox and slide the tabs down into the protrusions.

2. Secure the mounting bracket to the backbox by installing the supplied self-tapping screw into the top embossed 

protrusion/tab as illustrated below.

3. Attach the grounding cable from the left corner of the mounting bracket to the backbox grounding stud, securing it 

with hex nuts as illustrated below.

IMPORTANT!

 Only 7 AH or 18 AH batteries will fit in front of the ANN-LC when installed inside the FACP backbox. 

If 12 AH batteries are to be used, they must be installed vertically and sit on the left side of the bottom of the backbox.

ANN-LC

backbox

protrusions

Figure 1  Mounting the ANN-LC into the Backbox

FLL

C

m

ntt

abs.

w

m

f

self-tapping 

screw

grounding cable 
(p/n 1120-0709) 

secured with hex nuts

Figure 2  Securing the ANN-LC to the Backbox

FL

LC

mnt

.w

mf

Note: 

When securing the ANN-LC 

to ground, ensure that the ground 
cable for the AC mains is installed 
first, closest to the backbox. 

Summary of Contents for Fire-Lite ANN-LC

Page 1: ... next All ANN LC boards must be running the same version of Lite Connect module software The circuit can be wired in either Class A or Class B 2 Specifications Operating voltage 24 VDC Maximum current 150 mA 24 VDC Maximum attenuation of the optical signal between any two ANN LC cards for 62 5 125 or 50 125 multi mode fiber optic cable 5 dB For uninterrupted cable runs this will equate to a maximu...

Page 2: ...of the mounting bracket to the backbox grounding stud securing it with hex nuts as illustrated below IMPORTANT Only 7 AH or 18 AH batteries will fit in front of the ANN LC when installed inside the FACP backbox If 12 AH batteries are to be used they must be installed vertically and sit on the left side of the bottom of the backbox ANN LC backbox protrusions Figure 1 Mounting the ANN LC into the Ba...

Page 3: ...754 20 The over bending of fiber optic cables can cause breakage Consult manufacturer s guidelines for minimum radius of bend for fiber optic media 4 3 Class B Wiring Class B wiring begins at the MS 9050UD being used as the hub and ends with the last node on the circuit Figure 3 LC Connector LCconnector2side wmf ANN LC mounted in hub 1 1 1 1 1 1 2 2 2 2 2 2 First circuit node Last circuit node Fig...

Page 4: ...ass A wiring a single open will not result in fragmentation of the circuit Communication will continue while the hub and every installed node display a trouble condition on their host FACP ANN LC mounted in hub 1 1 1 1 1 1 2 2 2 2 2 2 First circuit node Last circuit node Figure 5 Class A Wiring FLLCclassA wmf 1 2 1 2 node node node node node Consult manufacturer s guidelines for minimum radius of ...

Reviews: