Honeywell Fire-Lite Alarms ES-50XC Manual Download Page 4

        

Page 4 of 4 — Canadian DF-60954:C • 7/16/2018

This document is not intended to be used for 

installation purposes. We try to keep our product 

information up-to-date and accurate. We cannot 

cover all specific applications or anticipate all 

requirements. All specifications are subject to 

change without notice.

For more information, contact Fire•Lite Alarms.

(888) 289-1114

10 Whitmore Road

Woodbridge, Ontario LZL 7Z4

www.firelite.com

LiteSpeed™

 is a trademark and 

Fire-Lite® Alarms

 and 

System Sensor®

 are

registered trademarks of Honeywell International Inc. Microsoft® and Windows® are
registered trademarks of the Microsoft Corporation. 
©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.

SYSTEM SPECIFICATIONS

System Capacity

• Intelligent Digital Communication Loops ....................................1 
• Addressable device capacity ....................................................50
• Programmable software zones.................................................50
• Annunciators.............................................................................16

Electrical Specifications

AC Power:  

Operates in either 

120

 or 

240 VAC, 50/60 Hz, 1.75

 

A

auto-sensing-no switch required

. Wire size: minimum 14

 

AWG (2.00 

mm2) with 600 V insulation. Nonpower-limited, super-vised.

Battery:  

Two 12 V 18

 

AH lead-acid batteries. Battery Charger

 

Capacity: 7-18

 

AH (EX-50XC cabinet holds maximum of two 18

 

AH

 

batteries.) 

Digital Communication Loop:  

Supervised and power-limited.

Notification Appliance Circuits:  

Terminal Block provides connec-

tions for two NACs, Style Y (Class B) or Style Z (Class A). Special

 

Application power. Power-limited, supervised circuitry. Maximum sig-
naling current per circuit: 2.5

 

amps special application, 250mA regu-

lated. End-of-Line Resistor: 4.7k

 

ohm, ½ watt (P/N 71252 UL listed)

 

for Style Y (Class B) NAC; system capable of 1.9 k

Ω

 - 22

 

k

Ω

 ELR

 

range. Refer to the 

Fire•Lite Device Compatibility Document

 for

 

listed compatible devices.

Two Programmable Relays and One Fixed Trouble Relay:  

Con-

tact rating: 2.0

 

A @ 30 VDC (resistive), 0.5

 

A @ 30 VAC (resistive).

 

Form-C relays, non-power-limited, non-supervised.

Cabinet Specifications

Door:

 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72"

(1.82 cm.) deep. 

Backbox:

 19.00" (48.26 cm.) high x 16.65" (42.29

cm.) wide x 5.25" (13.34 cm.) deep. 

Trim Ring (TR-CE):

 22.00"

(55.88 cm.) high x 19.65" (49.91 cm.) wide.

Shipping Specifications

Weight:

 26.9 lbs. (12.20 kg.) 

Dimensions:

 20.00” (50.80 cm.) high

x 22.5” (57.15 cm.) wide x 8.5” (21.59 cm.) deep.

Temperature and Humidity Ranges

This system meets requirements for operation at 0 – 49°C  and at a
relative humidity 93% ± 2% RH (non-condensing) at 32°C ± 2°C.
However, the useful life of the system's standby batteries and the
electronic components may be adversely affected by extreme tem-
perature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a nor-
mal room temperature of 15 – 27°C. 

Agency Listings and Approvals

The listings and approvals below apply to the basic ES-50XC control
panel. In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult factory for
latest listing status.

ULC: 

S624

Summary of Contents for Fire-Lite Alarms ES-50XC

Page 1: ...rts two devices set to the same address Two independently programmable built in Style Z Class A or Style Y Class B NAC circuits Selectable strobe synchronization for System Sensor Wheelock and Gentex devices Notification Appliance Circuit End of Line resistor matching Four programmable function keys for ease of maintenance Two programmable relays and one fixed trouble relay Built in Programmer Int...

Page 2: ...rouble and Supervisory Ships with red enclosure See DF 60241 ANN RLED Provides alarm red indicators for up to 30 input zones or addressable points See DF 60241 ANN RLY Relay Module provides 10 programmable Form C relays Can be mounted inside the cabinet See DF 52431 ANN S PG Serial Parallel Printer Gateway module provides a con nection for a serial or parallel printer See DF 52429 ADDRESSABLE DEVI...

Page 3: ... up to six modules on a CHS 6 chassis in a BB 6F cabinet MMF 302 6A Six zone interface module Mount one or two mod ules in a BB 2F cabinet optional Mount up to six modules on a CHS 6 chassis in a BB 6F cabinet CMF 300 6A Six circuit supervised control module Mount one or two modules in a BB 2F cabinet optional Mount up to six modules on a CHS 6 chassis in a BB 6F cabinet CRF 300 6A Six relay contr...

Page 4: ... or Style Z Class A Special Application power Power limited supervised circuitry Maximum sig naling current per circuit 2 5 amps special application 250mA regu lated End of Line Resistor 4 7k ohm watt P N 71252 UL listed for Style Y Class B NAC system capable of 1 9 kΩ 22 kΩ ELR range Refer to the Fire Lite Device Compatibility Document for listed compatible devices Two Programmable Relays and One...

Reviews: