ES-50X Series Manual —
P/N LS10129-000FL-E:D 4/26/2021
63
Master Programming Level
Programming
W or * - represents Waterflow Timer Delay (W = Waterflow Timer Delay enabled, * = Waterflow Timer Delay disabled)
ZNNN - represents the first of five possible software zones that the module is assigned to (NNN = the three digit zone number from
000 - 049)
1M002 - represents the Loop, Device type and Device address (1=SLC Loop, M=Module and 002 = Module Address 02)
To change the programming for the displayed module, press the keypad
down
arrow key to view the following Edit Control screens:
Enable/Disable Module
To Enable or Disable the control module, press the
1
key while viewing the Edit Control Screen #2. Each press
of the key will toggle the screen between
Enabled Yes
and
Enabled No
. If
Enabled No
is selected, the module
will not be polled by the control panel, preventing the module from activating its output devices. The control
panel will indicate a system trouble condition and the Disable LED will turn on if any devices are disabled.
Control Type
To select the type of control module being programmed, press the
2
key while viewing the Edit Control Screen
#2. This will cause the control panel to display the following Control Type Screens. Press the down arrow key
to view additional screens and selections.
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding keypad
number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.
The following table contains control module type codes and their functions which are displayed in the Control Type screens:
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the control
module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the
3
key
while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read
Silenceable
Yes
. Repeated presses of the
3
key will cause the display to toggle between
Silenceable Yes
and
Silenceable No
.
When set to Canadian mode of operation, a third silenceable type appears, Silenceable Auto. When set to
Auto
,
the control module will automatically silence after the Control Module Auto Silence timer expires.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually resetting
the control panel after each device activation. To enable devices, which are connected to a control module, for
the Walktest feature, press
1
while viewing the Edit Control Screen #3 until the display reads
Walktest Yes
.
Each press of the
1
key will cause the display to toggle between
Walktest Yes
and
Walktest No
test” on page 110 for additional information.
EDIT CONTROL
1=ENABLED YES
2=TYPE CONTROL
3=SILENCEABLE YES
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST YES
2=ZONE ASSIGNMENT
000
444
444
444
444
Edit Control Screen #3
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
44444444444444444444
Edit Control Screen #4
EDIT CONTROL
1=CTRL MOD DLY NO
WIRELESS NO
Edit Control Screen #5
EDIT CONTROL
1=ENABLED
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=ENABLED
2=TYPE CONTROL
3=SILENCEABLE
Edit Control Screen #2
CONTROL TYPE
FUTURE USE
2=BELL-CIRCUIT
3=HORN-CIRCUIT
Control Type Screen #1
NOTE:
A control relay module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the control
relay module is disabled.
Control Type
Special Function
Bell Circuit
NAC Type - supervised
Horn Circuit
NAC Type - supervised
Sounders
NAC Type - supervised
Relay
Ignore Open Circuit
Strobe Circuit
NAC Type - supervised
Control
NAC Type - supervised
Resettable Power
1
1 When using a control relay module to supply resettable power to
conventional 2-wire smoke detectors, the addressable monitor module
must be programmed for Smoke-Conventional operation
Relay Type - Ignore Open Circuit
HVAC Shutdown RLY
2
2 For HVAC SHUTDOWN description, refer to “Control Module Operation”
Relay Type - Ignore Open Circuit
HVAC Shutdown NAC
NAC Type - supervised
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
000
444
444
444
444
Edit Control Screen #3