ECC-50/125DA Instruction Manual —
P/N LS10027-000FL-E:D 5/21/2015
35
Installation
ECC-50BDA Backup Remote Amplifier
The AC terminals are rated as 120 VAC, 60 Hz or 240 VAC, 50 Hz.
3.2.10 Backup Battery for ECC-50BDA
The following steps explain how to connect the batteries (refer to Figure 3.12):
1. Connect the black wire of the battery harness to the (-) side of the battery #2.
2. Connect the jumper wire provided form the positive (+) side of battery #2 to the negative (-)
side of battery #1.
3. Connect the red wire from the battery harness to the positive (+) side of battery #1.