TC844A1007 Filtrex
™
Intelligent Photo Smoke
Sensor Installation in XLS Fire Alarm Systems
Installation Instructions
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: This equipment
has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio fre-
quency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
GENERAL
The TC844A1007 Filtrex™ Intelligent Photo Smoke
Sensor can be used with the Honeywell XLS1000 fire
alarm control panels. The TC844A1007 is configured in
the SDU data file exactly the same as a TC806 Photo
Smoke Detector. The TC844A1007 is connected to the
3-AADC Analog Addressable Device Controller using the
Honeywell 14507371-008 base.
PRE INSTALLATION
Configure and install the XLS1000 Fire Alarm Control Panel
with a 3-AADC Analog Addressable Device Controller as
described in form no. 95-7545, XLS1000 Installation and
Service Manual. When configuring the database using
the SDU, use the TC806 Photoelectric Smoke Detector
parameters for setting up the TC844A1007 Filtrex™
Intelligent Photo Smoke Sensor. The TC844A1007
responds to the XLS1000 panel the same as a TC806
Photoelectric Smoke Detector.
WIRING
All wiring must conform to applicable local codes, ordi-
nances and regulations.
To wire the TC844A1007 Filtrex
™
Intelligent Photo Smoke
Sensor:
1. Wire the TC844A1007 Filtrex
™
Intelligent Photo Smoke
Sensor to the 3-AADC loop by using the Honeywell
14507371-008 Plug-In Detector Base. See Fig. 6.
2. Wire Terminal 1 to the positive polarity (+) side of the
loop.
3. Wire Terminal 2 to the negative polarity (–) side of the
loop.
To use the TC844A1007 Filtrex
™
Intelligent Photo Smoke
Sensor with the DeltaNet FS90 Fire & Security System,
refer to form no. 95-7421, DeltaNet FS90 Fire & Security
System Installation Instructions.
NOTE: A power source within 15 Vdc to 30 Vdc is required.
This auxiliary power is wired to the AUX + and AUX– ter-
minals of the base. This power can be provided from the
XLS1000 power supply or any other appropriately listed
source.
CHECKOUT
Standard checkout procedures are used for commission-
ing the TC844A1007 Filtrex
™
Intelligent Photo Smoke
Sensor when used with the XLS1000 and 3-AADC. The
panel should respond to the TC844A1007 the same as it
would for a TC806 Photo Smoke Detector.
H400-22-00
4
I56-1326-006R
© 2005 Honeywell
Please refer to insert for the Limitations of Fire Alarm Systems
+
–
AU
X+
AUX
ñ
AU
X+
AUX
ñ
2(-) 3(R
A) 4(S)
1(+)
1(+)
2(-)
3(RA
) 4(S)
IF SHIELD USED, MUST BE CONTINUOUS AND FREE
FROM EARTH GROUND.
NOTE: ALL WIRING SUPERVISED AND POWER LIMITED.
1
1
REQUIRED FOR
CLASS A ONLY
+
+
+
–
B
–
B
H
S
+
A
–
A
N/C
+
B
–
B
N/C
LOOP1
LOOP1
LOOP1
CIRCUIT 1
3-AADC
–
3-PPS/M OR
3-BPS/M
+
–
+
AUXILIARY POWER
TB
1
2
1
Figure 6. Typical wiring from TC844A1007 to XLS1000
C0120-00
95-7662
TC844A1007 WITH
14507371-008 BASE