Honeywell Filtrex TC844A1007 Installation Instructions Download Page 4

TC844A1007 Filtrex

 Intelligent Photo Smoke

Sensor Installation in XLS Fire Alarm Systems

Installation Instructions

FCC Statement

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation.  Note: This equipment 
has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to 
provide reasonable  protection against harmful interference in a residential installation.  This equipment generates,  uses and can radiate radio fre-
quency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, 
there is no guarantee that interference will not occur in a particular installation.  If this equipment does cause harmful interference to radio or television 
reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of 
the following measures:
 

 

– Reorient or relocate the receiving antenna.

 

 

– Increase the separation between the equipment and receiver.

 

 

– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

 

 

– Consult the dealer or an experienced radio/TV technician for help.

GENERAL
The  TC844A1007  Filtrex™  Intelligent  Photo  Smoke 
Sensor  can  be  used  with  the  Honeywell  XLS1000  fire 
alarm  control  panels.  The  TC844A1007  is  configured  in 
the  SDU  data  file  exactly  the  same  as  a  TC806  Photo 
Smoke  Detector.  The  TC844A1007  is  connected  to  the 
3-AADC Analog Addressable Device Controller using the 
Honeywell 14507371-008 base.
PRE INSTALLATION
Configure and install the XLS1000 Fire Alarm Control Panel 
with a 3-AADC Analog Addressable Device Controller as 
described in form no. 95-7545, XLS1000 Installation and 
Service  Manual.  When  configuring  the  database  using 
the  SDU,  use  the  TC806  Photoelectric  Smoke  Detector 
parameters  for  setting  up  the  TC844A1007  Filtrex™ 
Intelligent  Photo  Smoke  Sensor.  The  TC844A1007 
responds  to  the  XLS1000  panel  the  same  as  a  TC806 
Photoelectric Smoke Detector.
WIRING
All  wiring  must  conform  to  applicable  local  codes,  ordi-
nances and regulations.
To wire the TC844A1007 Filtrex

 Intelligent Photo Smoke 

Sensor:
1. Wire the TC844A1007 Filtrex

 Intelligent Photo Smoke 

Sensor to the 3-AADC loop by using the Honeywell
14507371-008 Plug-In Detector Base. See Fig. 6.
2. Wire Terminal 1 to the positive polarity (+) side of the
loop.
3. Wire Terminal 2 to the negative polarity (–) side of the
loop.
To use the TC844A1007 Filtrex

 Intelligent Photo Smoke 

Sensor  with  the  DeltaNet  FS90  Fire  &  Security  System, 
refer to form no. 95-7421, DeltaNet FS90 Fire & Security 
System Installation Instructions.

NOTE:  A power source within 15 Vdc to 30 Vdc is required. 
This auxiliary power is wired to the AUX + and AUX– ter-
minals of the base. This power can be provided from the 
XLS1000  power  supply  or  any  other  appropriately  listed 
source.
CHECKOUT
Standard checkout procedures are used for commission-
ing  the  TC844A1007  Filtrex

  Intelligent  Photo  Smoke 

Sensor  when  used  with  the  XLS1000  and  3-AADC. The 
panel should respond to the TC844A1007 the same as it 
would for a TC806 Photo Smoke Detector.

H400-22-00 

I56-1326-006R

© 2005 Honeywell

 

 

 

 

 

 

 

      

Please refer to insert for the Limitations of Fire Alarm Systems

+

AU

X+

AUX

ñ

AU

X+

AUX

ñ

2(-) 3(R

A) 4(S)

1(+)

1(+)

2(-)

3(RA

) 4(S)

IF SHIELD USED, MUST BE CONTINUOUS AND FREE 
FROM EARTH GROUND.
NOTE: ALL WIRING SUPERVISED AND POWER LIMITED.

1

1

REQUIRED FOR 
CLASS A ONLY

+

+

+

B

B

H

S

+

A

A

N/C

+

B

B

N/C

LOOP1

LOOP1

LOOP1

CIRCUIT 1

3-AADC

3-PPS/M OR
3-BPS/M

+

+

AUXILIARY POWER

TB
1

2

1

Figure 6. Typical wiring from TC844A1007 to XLS1000

C0120-00

95-7662

TC844A1007 WITH
14507371-008 BASE

Summary of Contents for Filtrex TC844A1007

Page 1: ...rborne particulate are pres ent at elevated levels These elevated levels tend to cause false alarms and high maintenance in standard detectors Filtrex provides a protective enclosure for a photoelectric smoke detector chamber and allows smoke detection in areas where heat detection was the only practical alternative for fire sensing Filtrex requires compatible addressable communications to functio...

Page 2: ...ectronically simulates smoke in the sensing cham ber testing the detector electronics and connections to the control panel 1 Hold the test magnet in the magnet test area as shown in Figure 3 2 The detector should alarm the panel Two LEDs on the detector are controlled by the panel to indicate sensor status Coded signals transmitted from the panel can cause the LEDs to blink latch on or latch off R...

Page 3: ...f Filtrex while replacing the filter If a clogged filter was the cause of the trouble condition nor mal detector operation should resume automatically within five minutes If the trouble condition persists the detector must be returned for repair or replacement Installing Filtrex into Base 1 Align the detector at a right angle to the base with the five wires and connector adjacent to the connector ...

Page 4: ...e and install the XLS1000 FireAlarm Control Panel with a 3 AADC Analog Addressable Device Controller as described in form no 95 7545 XLS1000 Installation and Service Manual When configuring the database using the SDU use the TC806 Photoelectric Smoke Detector parameters for setting up the TC844A1007 Filtrex Intelligent Photo Smoke Sensor The TC844A1007 responds to the XLS1000 panel the same as a T...

Reviews: