Page
2
of
8
The ExiLED is a self-contained LED exit sign with selftest function. It can be configured as maintained
or non-maintained.
Selftest functions
Every 15 days the luminaire will perform an emergency operation test, this will light the exit sign for
approx. 3 seconds. The red indicator LED will flash during this test sequence.
Every 6. month the luminaire will perform a battery condition test. The test will last for 60 minutes. The
exit sign will be lit and the yellow indicator LED will flash during this test sequence.
Manual test functions
Manual tests can only be performed if both mains and battery are connected.
By pressing the test button briefly (less than 5 seconds) an emergency operation test is performed.
The exit sign will be lit for approx. 3 seconds, the red indicator LED will flash during this test sequence.
By pressing the test button for between 5 and 10 seconds a battery condition test is performed.
This test will last for 60 minutes and can only be performed when the battery is fully charged (steady
green indicator LED). The exit sign will be lit and the yellow indicator LED will flash during this test
sequence.
Resetting errors
Push the test button for >10 seconds to delete all indicated errors. Then the luminaire enters regular
operation mode.
Dimming
By pressing the test button continuously for 15 seconds, when luminaire is connected to mains, the
luminosity will be reduced to 10% of its total luminance. In emergency mode the light output will
remain unchanged.
To restore the original settings, repeat the above procedure.
The dimming setting remains stored in the luminaire even when both mains and battery voltages are
disconnected.
ExiLED22 ExiLED34 ExiLED44
Lumen output, normal:
105 lm
125 lm 145 lm
Lumen output, emergency:
130 lm 155 lm 180 lm
Weight:
540g
690g 820g
Maximum power consumption:
8VA 9VA 9VA
Operation voltage:
220-240VAC 50/60Hz
Emergency mode duration:
Minimum 1 hour
Battery:
3,6V / 1,2Ah NiMH
Battery protection:
Overcharge and full discharge
Charging time:
13 hours
Ambient temperature range:
5 to 40°C
Relative humidity:
Up to 95%
Classification:
EN 60598-2-22
IP40
Expected battery lifetime 4 years
Indicator LEDs
GB
GREEN
YEL
LO
W
RED
Normal
Charging (battery test not possible while charging)
Mains off, battery not connected or charger fault
Battery test
Battery fault
Light source test
Light source fault
Battery fault and light source fault
Description
LED status explanation
Off
On
Flashing
Technical description
At the end of their useful life the
packaging, product and batteries
should be disposed of via a
suitable recycling centre. Do not
dispose of with your normal
household waste. Do not burn.
T45807-B4-4