Excel 800
Planning
9
EN1B-0375GE51
R0910
Planning
Overview
Engineering with CARE
During CARE engineering, the type of I/O modules, terminal
assignment and module configuration are defined
depending on the application.
Planning
In this step, the following has to be defined, if applicable:
Power supply
Fusing
Earth grounding
Lightning protection
Panel Bus wiring
Design of a L
ON
W
ORKS
network
Design of a C-Bus network
Useful accessories
Cable selection
Transformer Selection
Note
In Europe the system transformer(s) must be safety isolating
transformers according to IEC61558-2-6.
In the U.S.A. and Canada, NEC Class-2 transformers must
be used.
Power Consumption
When selecting the appropriate transformer, take into
account the number of individual modules, accessories, and
field devices in determining the total power consumption.
Power consumption
Devices powered
24 VAC
24 VDC
XCL8010 with XI582
(backlight ON) and with
watchdog load (max. 500 mA)
690 mA
640 mA
XCL8010 with XI582
(backlight ON) but without
watchdog load
190 mA
140 mA
…821 130
mA
80mA
…822
160 mA
90 mA
…823
180 mA
130 mA
…824
140 mA
90 mA
…825
140 mA
90 mA
XF830A
200 mA
95 mA
XFU830A
200 mA
95 mA
Table 10 Power consumption of Excel 800 System
components depending on power supply
Connectable Power Supplies
Honeywell CRT Series (Europe)
Transformer Primary side
Secondary side
CRT 2
220/230 VAC
24 VAC, 50 VA, 2 A
CRT 6
220/230 VAC
24 VAC, 150 VA, 6 A
CRT 12
220/230 VAC
24 VAC, 300 VA, 12 A
Table 11 Honeywell CRT series transformers data