T7460A,B,C,D,E,F WALL MODULES

3

95-7610-2

Mounting Procedure

1. 

Disassemble the cover as is shown in Fig. 1.

 

2. 

(T7460B,C,D,E,F only)

Remove the setpoint dial by pulling it off.

 

3. a)

 Mount the wall module onto the wall outlet box,

or

b) 

bore wall holes as is specified in Fig. 2 and 

mount the wall module with appropriate screws.

 

4. 

Connect the wires to the terminal block according

to the specifications in the “Wiring” section.

 

5. 

(T7460B,C,D,E,F only)

Insert the setpoint dial and turn it clockwise as far

as possible.

 

1. 

 (T7460B,C,D,E,F only)

Make sure that the dial's position is such that the

30 (Celsius absolute scale) or the +5 (Celsius

relative scale) point to the right-hand side of the

wall module (see Fig. 4).

   

Fig. 4. Mounting position of setpoint dial.

 

7. 

(T7460B,C,D,E,F only)

If the dial does not have the correct position, pull

the dial off again and reinsert it with the correct

orientation.

 

8. 

Remount the cover as depicted in Fig. 5 and make

sure that the tab on the underside engages.

Fig. 5. Mounting cover of T7460 wall modules.

Wiring

Attach the wires from the device sensor terminals to the

appropriate wall module terminals and set the jumpers

according to the connected controller. See Fig. 6, 7 and 8.

NOTE:

Not all of the T7460 wall modules are compatible

with W7751A,C,E,G(VAV1) and W7752D1(FCU1)

Controllers.

IMPORTANT

Screw type terminal blocks are designed to

accept no more than one 16 AWG (1.5 mm

2

)

conductor.

Wire the terminal blocks as follows:

1.

Strip 3/16 in. (5 mm) of insulation from the

conductor.

2.

Insert the wire in the required terminal location and

tighten the screw to complete the termination.

3.

Verify jumper setting with Fig. 6 and wall module

wiring with Fig. 7 and 8.

Jumper settings

According to the type of controller connected, the following

jumpers have to be set on the PCB of the T7460C,D,E,F.

NOTE:

The “W77xx” at the first jumper position stands for

the Excel 10 and Excel 12 controllers:

Const. Vol. Air Handling Unit

W7750A,B

(Smart) Variable Air Volume

W7751B,D,F,H

Fan Coil Unit (FCU2)

W7752D,E,F,G

Remote Input/Output Device

W7761A

Hydronic

W7762A,B

Chilled Ceiling

W7763C,D,E

Excel 12

W7704xx

A

Excel 10 Controller:

W7750, W7751, W7752
W7761, W7762, W7763

A

A

A

1: W77xx

1: W77xx

1: W77xx

1: W77xx

1: W77xx

1: W77xx

1: W77xx

1: W77xx

B

B

B

B

2: W7753

2: W7753

2: W7753

2: W7753

2: W7753

2: W7753

2: W7753

2: W7753

3: XL500

3: XL500

3: XL500

3: XL500

3: XL500

3: XL500

3: XL500

3: XL500

Excel 10 Controller:

W7753A (Unit Ventilator)

Excel Controller:

20, 50, 80, 100, 500, 600

without fan

Excel Controller:

20, 50, 80, 100, 500, 600

with fan

Fig 6. Jumper settings for T7460C,D,E,F Wall Modules.

Factory Default

Проектирование

Монтаж

Продажа

. - http://vskd.ru

Summary of Contents for EXCEL 5000 OPEN T7460A

Page 1: ... the other one Mount the T7460A B C D E F Wall Modules on an inside wall approximately 54 in 1 3 m from the floor or in the specified location to allow exposure to the average zone temperature NOTE Maintain a mounting clearance of approx 4 in 10 cm to the left hand side of the module in order to allow a free airflow for the temperature sensor and accessibility of the setpoint dial Do not mount the...

Page 2: ...T7460A B C D E F WALL MODULES 95 7610 2 2 NOTE Graphics show E F model Dimensions are the same for all six models Fig 3 T7460A B C D E F dimensions in in mm Проектирование Монтаж Продажа http vskd ru ...

Page 3: ...he T7460 wall modules are compatible with W7751A C E G VAV1 and W7752D1 FCU1 Controllers IMPORTANT Screw type terminal blocks are designed to accept no more than one 16 AWG 1 5 mm2 conductor Wire the terminal blocks as follows 1 Strip 3 16 in 5 mm of insulation from the conductor 2 Insert the wire in the required terminal location and tighten the screw to complete the termination 3 Verify jumper s...

Page 4: ...B C D E F WALL MODULES 95 7610 2 4 Fig 7 Wiring diagram for T7460A B Wall Modules Fig 8 Wiring diagram for T7460C D E F Wall Modules for the jumper settings see Fig 6 Проектирование Монтаж Продажа http vskd ru ...

Page 5: ...odule LONWORKS will be connected to the two LON terminals A PC connection can be established using the 3 5 mm jack plug Order quantity set with 5 pieces Fig 9 T7460 LONJACK Mounting Remove the setpoint dial and put in the T7460 LONJACK as shown in the following Fig 10 Mounting T7460 LONJACK Проектирование Монтаж Продажа http vskd ru ...

Page 6: ...eywell com http www honeywell ca http europe hbc honeywell com 95 7610 2 Rev 04 02 7157325 Printed in Germany Subject to change without notice T7460 LIMITER The T7460 LIMITER can be used to adjust the setpoint dial to particular setpoints Put the limiters approximately opposite the setpoints you want to adjust In the following example the setpoints are at about 18 and 27 C Order quantity set of 10...

Reviews: