DISTRIBUTED I/O
EN0B-0090
24
Commissioning Distributed I/O Modules
Previous to V2.04.x controller firmware, Distributed I/O
modules were used only on a local L
ON
W
ORKS
bus con-
nected to a single Excel 500 controller. Concurrent with the
release of V2.04.x firmware is the release of the XFL52xB
Distributed I/O modules with updated firmware and with a
new Neuron chip which make them fully L
ON
M
ARK
compliant.
This means that multiple Excel 500 controllers, each with its
own Distributed I/O modules, as well as third-party L
ON
M
ARK
compliant devices, can coexist and interoperate on the same
L
ON
W
ORKS
bus. Furthermore, the XFL52xB modules can be
used as third-party devices with other L
ON
M
ARK
compliant
products, independently of an Excel 500 controller.
IMPORTANT:
Full L
ON
M
ARK
functionality requires an Excel 500
controller with V2.04.x firmware, a 3120E5 Neuron
chip, and Distributed I/O modules XFL52xB.
An Excel 500 controller with V2.4.x firmware and
3120E5 Neuron chip will commission earlier ver-
sions of Distributed I/O modules (XFL52x,
XFL52xA), but only in the local mode (max 16
modules per CPU and no other controllers on the
L
ON
W
ORKS
bus).
Distributed I/O modules XFL52xB can be used with
older versions of Excel 500 that support Distributed
I/O, but only if the modules are switched into a
different mode. This is accomplished by pressing the
service pin while simultaneously turning the HEX
address switch. This mode can be cancelled by
pressing the service pin for more than three
seconds.
Table 13. Controller compatibility.
Operating mode
2
of
Distributed I/O modules
Controller type CPU / Application modules
Controller
firmware
Open L
ON
W
ORKS
functionality?
XFL52x
XFL52xB
Excel 500
XC5010C / XCL5010
V2.0.x to V2.3.x
not possible
local
local
Excel 500
XC5010C / XCL5010
V2.4.x
not possible
local
local/shared
Excel 500
XC5010C
1
/ XCL5010
1
/ XC5210C
1
V2.0.x to V2.3.x
not possible
local
local
Excel 500
XC5010C
1
/ XCL5010
1
/ XC5210C
1
V2.4.x
in use
---
shared/open
Excel 500
XC5010C
1
/ XCL5010
1
/ XC5210C
1
V2.4.x
not in use
local
local/shared
1
When bearing the L
ON
M
ARK
™ logo on the module/CPU.
2
The term "local" refers to an operating mode in which a maximum of 16 modules are assigned (automatically) to each con-
troller and only a single controller is connected to each L
ON
W
ORKS
bus.
The term "shared" means that a maximum of 16 modules are assigned (manually) to each controller, but that multiple con-
trollers can be connected to a single L
ON
W
ORKS
bus.
The term "open" refers to an open L
ON
W
ORKS
system, i.e. the use of CARE to generate a L
ON
M
ARK
compliant network
interface file (XIF)
capable of providing NVs which can be bound to other devices (Excel 50 or Excel 10 controllers, third-
party devices); further, the limitation of max. 16 modules per controller can also be exceeded.
Table 14. Distributed I/O module compatibility.
L
ON
W
ORKS
Functionality, by Controller Firmware Version
Distributed I/O modules
V2.0.x to V2.3.x
V2.4.x
XFL521
XFL522A
XFL523
XFL524A
One controller to which Distributed I/O modules
are assigned on a single L
ON
W
ORKS
bus
One controller to which Distributed I/O modules
are assigned on a single L
ON
W
ORKS
bus
XFL521B
XFL522B
XFL523B
XFL524B
One controller to which Distributed I/O modules
are assigned on a single L
ON
W
ORKS
bus (press
the L
ON
W
ORKS
service pin while turning HEX
switch to enable this backwards-compatible
mode)
1
Full L
ON
W
ORKS
functionality: Multiple
Distributed I/O modules and multiple controllers
possible on a single L
ON
W
ORKS
bus
2
1
To cancel the backwards-compatible mode for Distributed I/O modules (allowing full L
ON
W
ORKS
functionality), press and hold
down the L
ON
W
ORKS
service pin for at least 3 seconds.
2
Excel 500 controller with Neuron 3120E5 chip required!
NOTE:
Compatibility of XFR522A and XFR524A Manual Override modules is affected by neither firmware nor Neuron chip
version.