EXCEL 500/600 INSTALLATION INSTRUCTIONS
—
Type XW569 13 in. (330 mm) long (for housings one
above the other)
CAUTION
Incorrectly inserted bus cables can destroy the
modules installed.
The internal bus begins at the first housing, containing the
power supply and computer modules, and ends at the last
housing.
The protective bus connection covers must be removed.
Fig. 5. Removal of bus connection cover
The overall internal bus length (bus cable and bus in the
housings) must not exceed 6 ft (2m).
Bus cables must be routed at least 2 in. (50 mm) away from
power cables to prevent possible inductive and capacitive
interference.
Module Locations (not XCL5010)
Each housing has four plug-in module locations.
Table 1. Internal module locations
Module
Type
Module location
CPU
XC5010C /
XC6010
1
st
housing, location 4
Power
supply
XP502
1
st
housing, location 1
AI
XF521A / XF526 any
AO
XF522A / XF527 any
DI
XF523A
any
DO
XF524A / XF529 not in the 1
st
housing
3-position
output
XF525A
not in the 1
st
module
housing
Coding the Terminal Block (not XCL5010)
The terminal block is coded with pins to prevent mixing the
module types during commissioning or servicing. Mixing the
modules can damage them.
You can code the terminal block by inserting pins into
designated location holes on the terminal block in the base.
Fig. 7. Inserting the code pin in the terminal block
Table 2 shows the coding pin positions for the individual
module types:
Table 2. Code pin position by module type
Module
Type
Pin position
CPU
XC5010C, XC6010
08
Power supply
XP502
06
AI
XF521A, XF526
07
AO
XF522A, XF527
11
DI
XF523A
09
DO
XF524A, XF529
10
3-position output XF525A
12
Fig. 6. Internal module numbering
Table 1 shows the plug-in location to which each module may
be assigned:
NOTE:
Distributed I/O modules are coded differently. See
Distributed I/O Product Data (EN0B-0090GE51).
7