Setting the Photocell 

1. Wait until the time of day when the ambient light level is equal to the level at which you want the photocell to 

become active.

2. Using  the  HP2000,  select ‘Set Light  Level’  from the  Utilities  menu and  press  OK while  pointing at the 

detector to store the current light level - the lights must be on prior to starting this process. The detector 
stores two values in Lower Threshold and Upper Threshold (see diagram). This procedure can also be 
accomplished by using the HP10 Basic Programmer’s ‘Store’ button, however editing of stored threshold 
values is not possible with the HP10.

3.    If required, these values can be manually edited via the HP2000. Please note, these are not Lux levels but a 

representation of the light levels perceived by the detector at the time of the store command.

       Note: If the photocell is set to Passive, only the value in the Lower Threshold is relevant.

       If the photocell is set to Active, once the ambient light level drops below the Lower Threshold value, the                   

lights will turn ON. If the ambient level exceeds the value of the Upper Threshold for the duration of the off-
delay (Passing Cloud Timer) then the lights will turn ON. If the photocell is set to ‘Disabled’ when a Set Light 
Level operation is made, it will revert to operating in Passive mode.  

Washroom Mode

This product allows the control of water for washroom management applications (urinals). In order to maintain 
good standards of hygiene the products feature a washroom mode (24hr Cycle) that, if enabled, ensures that 
when urinals have not been used for 24 hours  (i.e. the controlled area has been unoccupied), a hygiene flush 
occurs. Please note that when controlling lighting 

and

 urinals, it is not possible to have the photocell influence the 

output status as this could prevent flushing of the urinals. 

115mm

65mm

Green/Yellow - Earth 
(no internal connection)

Blue - Neutral

Black - Live Out

Brown - Live In

UC1200PF

Electrical Connections

6.0m

2.5m

Technical Data

 

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)
RECOMMENDED CIRCUIT PROTECTION: 10 Amps
MAXIMUM LOAD: 6 Amps 
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 3 metres
RANGE: Cone-shaped detection 
               pattern, diameter (at floor level)
               = 2.4 x mounting height

PHOTOCELL: Adjustable 50-5000 lux via Programmer
OFF DELAY:  Adjustable via Programmer - factory pre-set to 20 minutes

Programmer options: 1 min - 96 hours / Disabled (via HP2000);
5 - 35 mins (via HP10); 5, 10 or 20 mins (via HP18)
- plus 10-second Walk-test Mode

COLOUR: White
MATERIAL: Flame retardant PC/ABS
WEIGHT:  70g approx (excluding cable)
IP RATING: 4X

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Ex-Or 

Novar ED&S Limited
Haydock Lane, Haydock, Merseyside WA11 9UJ

Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 508753  
Email: [email protected]
www.ex-or.com

W4253F

Summary of Contents for Ex-Or UC1200PF

Page 1: ...allation and Commissioning Instructions Note HP2000 or HP10 HP18 required for commissioning Please note that the HP10 and HP18 offer different limited programming options LightSpot Washroom Series UC1200PF ...

Page 2: ...enoid valve must be plumbed into the water feed to the urinal header tank and connected to the detector using 230V cable Multiple UC1200PF Larger areas can be covered by connecting extra units in parallel The total load current must not exceed 6Amps in case only one unit is activated N E L Permanent or switched supply LIVE IN LIVE IN NEUTRAL NEUTRAL EARTH EARTH LIGHTING FAN OR VALVE LightSpot Ligh...

Page 3: ...fficient natural light is available It will not turn the load off whilst an area is occupied Active The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the l...

Page 4: ...the control of water for washroom management applications urinals In order to maintain good standards of hygiene the products feature a washroom mode 24hr Cycle that if enabled ensures that when urinals have not been used for 24 hours i e the controlled area has been unoccupied a hygiene flush occurs Please note that when controlling lighting and urinals it is not possible to have the photocell in...

Reviews: