Honeywell Ex-Or MS2421PF Quick Start Manual Download Page 2

Parameter

POWER UP*
RESPONSE*
R1 OFF DLY*
R2 OFF DLY
24 HOUR CYCLE*
ON RANGE*
OFF RANGE*
ENTRY SCENE

PCELL MODE*
SET-POINT LOW
SET-POINT HIGH

Default

ON
AUTO
20 mins
20 mins
OFF
HIGH
75%
Scn 1

DISABLED
1000
1023

Options

ON/OFF
Auto/Semi-auto
1 min - 96 hours (5-35 mins with HP10)
1 min - 96 hours
ON/OFF
MAX, HIGH, MED or LOW
100%, 75% or 50% off ON Range
Scn 1 - R1 On & influenced by photocell, R2 On
Scn 2 - R1 On & influenced by photocell, R2 Off
Scn 3 - R1 Off, R2 Off
Scn 4 - R1 On, R2 Off
Scn 5 - R1 On, R2 On
Scn 6 - R1 Off, R2 On
PASSIVE, ACTIVE, DISABLED
0 - 1023
0 - 1023

Programming Notes

Each of these settings
 can be re-programmed,
if desired, by use of the
infrared programming
tool HP2000.

* Selected parameters 
shown with an asterisk 
are re-programmable
with the HP10.

4.  Commissioning

Detectors are supplied with factory default settings (Power-up On / Fully Automatic 
Operation / 20-minute Off Delay / No 24hr Cycle / Photocell Disabled) as shown 
below.  They  can  be  programmed  using  the  MLS  Digital  Programmer  with  LCD 
display  (HP2000)  or  the  LightSpot  Programmer  (HP10)  incorporating  12  dil 
switches.

Factory Default Settings

8. Hand-held Controllers

HP2000

MLS Digital 
Programmer

HP10

Programmer

LightSpot 

HC6

Two-button Hand-held Controller 
(Note: HC5 Universal Hand-held
Controller is also suitable
for use with this detector.)

5.  Setting the Photocell

1.

If  the  lights  are  not  already  on,  switch  them  on  manually  by  pressing 
‘Utilities/User  Remote/Lu/OK’  [HP2000],  or  ‘Up’  [HP10]. 
Fluorescent lights do not reach full output until up to 15 minutes after being 
switched on, so ensure that the lights are fully warmed up before continuing.  
This  stage  may  be  omitted  if  the  intention  is  to  operate  the  detector’s 
photocell  in  Passive  Mode  only  [the  detector  must  have  already  been 
programmed to Passive Mode].

2.

Wait until the time of day when the natural light level is at the point below 
which you 

would

 want the lights to be on, and above which you 

would not

 

want the lights to be on.

3.  Start  the  internal  self-programming  mechanism  by  pressing  ‘Utilities/Set 

Light  Level/OK’  [HP2000],  or  ‘Store’  [HP10].    The  detector  takes  a 
measurement,  adds  a  small  amount  and  stores  the  value  in  the  Upper 
Threshold.   Then it turns the lights off, makes another measurement and 
stores the value in the Lower Threshold.  The lights now switch on again to 
acknowledge a successful programming operation.

The two switching thresholds have now been set, and the difference between 
them is equal to the contribution made by the electric lighting; this is the perfect 
amount of hysteresis to ensure that the lights will not oscillate.   The thresholds 
may be read back and fine-tuned if necessary using the HP2000.   Please note 
that the values are non-specific units i.e. not lux.

Note:

  The light level perceived by the detector at the moment immediately prior 

to a Download operation [HP2000 only] is shown momentarily on the HP2000 
screen following the Download; this is a useful mechanism for troubleshooting.

Important Additional Notes

1.

Only suitably qualified personnel should install this equipment.

2.

A means for disconnection must be incorporated in the fixed wiring in accordance with 
the current wiring regulations.

3.

This equipment switches lights no more frequently than would a responsible human 
occupant.  However,  manufacturers  of  some  particular  lighting  types  (e.g.  ‘2D’ 
luminaires) may specify a maximum number of switching cycles in order to achieve a 
predicted lamp life. Please check with the manufacturer of the luminaires to ensure that 
they are compatible with automatic controls in this respect.

HP10 Parameter Options for MS2421P 

1

2

3

4

5

6

7

8

9 10 11 12

SET RANGE

WHEN LIGHTS

OFF

SET RANGE

WHEN LIGHTS

ON

PHOTOCELL

MODE =

ACTIVE

PHOTOCELL

ENABLED

MOVEMENT
DETECTOR
AUTOMATIC
OPERATION

MOVEMENT
DETECTOR
SEMI-AUTO
OPERATION

POWER UP

ON

POWER UP

OFF

min

ON

OFF

10 

min

20 

min

OFF DELAY
   R1 & R2
Add together to
give required time
(All OFF = 10 sec
Walk Test)

100%

OFF      OFF

 75%

OFF      ON

 50%

ON        OFF

 50%

ON        ON

% of

 

    Switch  

 ON

 

   Position

Range

 ON

ON

Max

 ON

OFF

High

 OFF

ON

Medium

 OFF

OFF

Low

   

   

Range

PHOTOCELL

MODE =

PASSIVE

PHOTOCELL

DISABLED

24-HOUR

CYCLE

ON

24-HOUR

CYCLE

OFF

Switch

Position

Lights ON =
Lights OFF =

Upper Threshold

Lower Threshold

Natural
Light 
Level

Duration of 

Off Delay

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

6.  Walk-test Mode

Walk-test  mode  is  used  to  check  that  the  detector  is  operating  as  required.                   
The short Off Delay enables the installer to check that lights are switching on 
when movements are made at the edge of the detection zone.   It is easier to 
carry out a walk-test when the photocell is not holding the lights off.

1.   Change the Off Delay to 10 seconds using the HP10 or press ‘Utilities/Walk 

Test/OK’ (HP2000 only).

2.   Move around the area that is being controlled, stopping for 10 seconds to 

allow the lights to switch off, before moving and triggering the lights back on.          
Re-programme the desired Off Delay once testing is complete.  Note: If the 
HP2000 was used to engage ‘soft’ walk test mode as described above, the 
programmed Off Delay will be automatically restored after 5 minutes.

7.  Washroom Mode (24-Hour Cycle)

The unit may be used in conjunction with a 230V solenoid valve and a trickle 
valve  or ‘petcock’  to effect a  urinal flush  system.    Set  the  water  flow rate by 
adjusting the petcock so that the cistern 

just

 fills within the chosen Off Delay 

period of the detector.  Note that the urinal control operates on R2.

HP10 Parameter Options

 

(Parameter designation for HP2000 shown in capitals)

 

Off Delay - OFF DELAY

The Off Delay may be set between 5 and 35 minutes.  (Independent Off Delays of 
between 1 minute and 96 hours may be set for each output using the HP2000.)           
A 10-second Off Delay is available for walk-testing the product. In a typical office 
environment an Off Delay of 20 minutes is usually satisfactory

Movement Detector Operation (Automatic / Semi-Automatic) - RESPONSE

Where  absence  detection  is  required  (i.e.  the  user  manually  turns  lights  ON  if 
required  but  lights  still  turn  off  automatically  once  an  area  is  vacated),  semi-
automatic operation can be set via the programmer. It should be noted that this 
mode of operation affects only the switched-live output, R1. Where semi-automatic 
operation is required on both outputs, please contact Ex-Or for assistance. 

Power Up (On/Off) -  POWER UP

Set  to  ON  the  detector  will  automatically  switch  its  outputs  on  when  Mains  is 
applied. If set to OFF, the detector will power up without turning its outputs on, wait 
for 15 seconds and THEN look for movement. Only if the area is occupied will the 
outputs switch on at this time. 

(Sensitivity) Range When Lights On / Lights Off  - ON RANGE/OFF RANGE

Settings appropriate for the type of activity typical for the monitored area should be 
chosen.  It is desirable to require a larger movement to switch lights on (i.e. when 
an area is entered) than to sustain the lights in an already occupied area. The On 
Range determines the sensitivity to movement when lights are on; Off Range is 
used to set a reduced sensitivity  to movement when the lights have switched off.

Photocell Mode (Passive/Active/Disabled) - PCELL MODE

The MS2421P has an in-built photocell. The photocell does not affect the volt-free 
output, i.e. the volt-free output will turn on regardless of natural light levels when 
occupancy  is detected. The  photocell  has  three  modes  of operation  -  Passive, 
Active and Disabled. Its operational behaviour is governed by the setting chosen 
and by the values stored in the Upper and Lower thresholds (see diagram under 
Setting the Photocell).

Passive

  - The  photocell  will  inhibit  switch-on  of  the  controlled  load  if  sufficient 

natural light is available. It will not turn the load off whilst an area is occupied

Active

 - The photocell will turn the controlled load on and off as required whilst 

natural light levels fluctuate during a period of occupancy. This mode of operation 
operates in conjunction with a passing cloud timer (PCT). The PCT is asymmetrical 
in operation - the load will be switched on immediately that the light level falls below 
the lower set point, however, the load switches off only if the light level exceeds the 
upper threshold 

continuously

 for a period equal to the Off Delay.

Disabled

 - The photocell has no effect.

24-Hour Cycle (Yes/No) - 24 HOUR CYCLE

For use in ‘Washroom Mode’ only (see section 7).  In this mode it is necessary to 
have a hygiene cycle (flush) if the area has been unoccupied for 24hrs.   Select 
this feature and the output will switch on for the duration of the Off Delay once 
every 24hrs if the area remains unoccupied.  Operates on R2 (if selected).

Note that when the natural 
light level exceeds the 
‘upper threshold’ value, the 
lights do not immediately 
turn off. They will turn off 
only when the upper 
threshold has been 
exceeded for the duration of 
the programmed Off Delay.