Technical Data

 

OPERATING VOLTAGE: 230V ~ 50Hz (UK & Europe)
RECOMMENDED CIRCUIT PROTECTION: 10 Amps

2

TERMINAL CAPACITY: 2 x 2.5mm
MAXIMUM LOAD: 6 Amps per output [not exceeding 10A in total]
MAXIMUM RECOMMENDED MOUNTING HEIGHT: 16 metres
RANGE: Cone-shaped detection pattern, 
               diameter (at floor level) 
               = 1 x mounting height
PHOTOCELL: Adjustable 50-5000 lux via HP2000
OFF DELAY 1 & 2: 1 minute - 96 hours adjustable 
and 10 second Walk Test Mode.
[Each output independently adjustable]

COLOUR: White (RAL9010)
MATERIAL: Flame retardant PC/ABS
WEIGHT:  200g approx
IP RATING: 3X

MINIMUM MOUNTING PITCH (SPACING): 
0.5 x mounting height (when utilising the photocell 
- see note under ‘Fixing’) 

o

o

OPERATING TEMPERATURE: 0 C to 40 C

W4425E

Ex-Or

Novar ED&S Limited

 

Haydock Lane, Haydock, Merseyside WA11 9UJ

Tel: +44 (0)1942 719229 
Fax: +44 (0)1942 508753  
Email: [email protected]
www.ex-or.com

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

Setting the Photocell

1.

If the lights are not already on, switch them on manually by pressing ‘Utilities/User Remote/Lu/OK’on the 
HP2000. Fluorescent lights do not reach full output until up to 15 minutes after being switched on, so ensure that 
the lights are fully warmed up before continuing.   This stage may be omitted if the intention is to operate the 
detector’s photocell in Passive Mode only [the detector must have already been programmed to Passive Mode].

2.

Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to be on, 

and above which you 

would not

 want the lights to be on.

3.  Start the internal self-programming mechanism by pressing ‘Utilities/Set Light Level/OK’ on the HP2000. The 

detector takes a measurement, adds a small amount and stores the value in the Upper Threshold.  Then it turns 
the lights off, makes another measurement and stores the value in the Lower Threshold.  The lights now switch on 
again to acknowledge a successful programming operation.

The two switching thresholds have now been set, and the difference between them is equal to the contribution made 
by  the  electric  lighting;    this  is  the  perfect  amount  of  hysteresis  to  ensure  that  the  lights  will  not  oscillate.   The 
thresholds may be read back and fine-tuned if necessary using the HP2000.   Please note that the values are non-
specific units  i.e. not lux.

Note:

   The light level perceived by the detector at the moment immediately prior to a Download operation is shown 

momentarily on the HP2000 screen following the Download;  this is a useful mechanism for troubleshooting.

Lights ON =

Lights OFF =

Upper Threshold

Lower Threshold

Natural
Light 
Level

Duration of 

Off Delay

Note that when the natural light 
level exceeds the ‘upper threshold’ 
value, the lights do not immediately 
turn off. They will turn off only when 
the upper threshold has been 
exceeded for the duration of the 
programmed Off Delay.

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

Dimensions

100mm

10mm 

deep

(Facia)

62mm deep

(behind ceiling)

RANGE

Summary of Contents for Ex-Or MS2021PHBF

Page 1: ...021PHBF MS2021PHBSM Hi Bay Multi Function Dual Output LightSpot with photocell MS2021PHBSM MS2021PHBF Note HP2000 required for commissioning User override available via the HC7 and HC8 dedicated and HC5 general purpose Hand held Infrared Controllers ...

Page 2: ...programmable run on timer The HC7 is a dedicated hand held Infrared controller for this mode but the HC5 will also switch the two outputs as outlined in 1 above 4 Lighting Control Emergency Test Controller This operating mode allows the testing of an area of Emergency Lighting to be conveniently implemented without the expense of a special single function controller The Switched Live output remain...

Page 3: ... lights never turn off for lack of detected movement R2 Off Delay In Lighting mode this defines the period from last detected occupancy to secondary Lights Off In other modes setting this to longer than R1 Off Delay allows for an extended filling time for flush cistern or for extractor fan or air conditioning run on In Emergency Test mode it is not used so that its configured value is a don t care...

Page 4: ...tor must have already been programmed to Passive Mode 2 Wait until the time of day when the natural light level is at the point below which you would want the lights to be on and above which you would not want the lights to be on 3 Start the internal self programming mechanism by pressing Utilities Set Light Level OK on the HP2000 The detector takes a measurement adds a small amount and stores the...

Reviews: