Setting the Photocell

1. If  the  lights  are  not  already  on,  switch  them  on  manually  by  pressing  ‘Utilities/User  Remote/Lu/OK’ 

[HP2000] or ‘On’ [HP18]. Fluorescent lights do not reach full output until up to 15 minutes after being switched on, 

so ensure that the lights are fully warmed up before continuing.  This stage may be omitted if the intention is to 

operate the detector’s photocell in Passive Mode only [the detector must have already been programmed to 

Passive Mode].

2. Wait until the time of day when the natural light level is at the point below which you 

would

 want the lights to be on, 

and above which you 

would not

 want the lights to be on.

3.  Start the internal self-programming mechanism by pressing ‘Utilities/Set Light Level/OK’ [HP2000] or ‘Set’ [HP18].  

The detector takes a measurement, adds a small amount and stores the value in the Upper Threshold.  Then it 

turns the lights off, makes another measurement and stores the value in the Lower Threshold.   The lights now 

switch on again to acknowledge a successful programming operation.

The two switching thresholds have now been set, and the difference between them is equal to the contribution made by 

the electric lighting;  this is the perfect amount of hysteresis to ensure that the lights will not oscillate.  The thresholds 

may be read back and fine-tuned if necessary using the HP2000.  Please note that the values are non-specific units  i.e. 

not lux.

Note:

   The light level perceived by the detector at the moment immediately prior to a Download operation is shown 

momentarily on the HP2000 screen following the Download;  this is a useful mechanism for troubleshooting.

Lights ON =

Lights OFF =

Upper Threshold

Lower Threshold

Natural

Light 

Level

Duration of 

Off Delay

Note that when the natural light 

level exceeds the ‘upper threshold’ 

value, the lights do not immediately 

turn off. They will turn off only when 

the upper threshold has been 

exceeded for the duration of the 

programmed Off Delay.

Active Mode

Passive Mode

Occupancy

Area Occupied =

Area Unoccupied =

Technical Data

 

OPERATING VOLTAGE: 230V 50Hz (UK & Europe)

RECOMMENDED CIRCUIT PROTECTION: 10 Amps

MAXIMUM LOAD: 6 Amps 

MAXIMUM RECOMMENDED MOUNTING HEIGHT: 12 metres

o

RANGE: 360  cone-shaped detection pattern. 

Diameter at floor level (d)

               = 1.75 x mounting height (h)

MINIMUM MOUNTING PITCH (SPACING): 0.5 x mounting height (when utilising the photocell - see note under ‘Fixing’) 

PHOTOCELL: Adjustable 50-5000 lux via HP2000/HP18 

OFF DELAY: Adjustable via Programmer - factory pre-set to 20 mins

Options: 1 min - 96 hours / Disabled (via HP2000); 5, 10 or 20 minutes (via HP18) - plus 10-second Walk-test                  

COLOUR: White

MATERIAL: Flame retardant PC/ABS

WEIGHT:  70g approx (excluding cable)

IP RATING: 4X (Estimated - not tested)

o

o

OPERATING TEMPERATURE: 0 C to 40 C

h

d

Summary of Contents for Ex-Or MS1200PMBF

Page 1: ...42 719229 Fax 44 0 1942 508753 Email technicalsales ex or honeywell com www ex or com At the end of their useful life the packaging and product should be disposed of via a suitable recycling centre Do not dispose of with normal household waste Do not burn Note HP2000 or HP18 required for commissioning Please note that the HP18 offers different limited programming options ...

Page 2: ...th a minimum clearance of 125mm between the front surface of the tile and the hard ceiling behind The detector should be mounted in the centre of the group of luminaires to be controlled Cut a 50mm diameter 64mm if using an FR64 flush ring or PB64 plasterboard fixing kit circular hole in the tile feed the flying lead and detector through the hole and secure into position with the locking ring Twis...

Page 3: ...urn the load off whilst an area is occupied Active The photocell will turn the controlled load on and off as required whilst natural light levels fluctuate during a period of occupancy This mode of operation operates in conjunction with a passing cloud timer PCT The PCT is asymmetrical in operation the load will be switched on immediately that the light level falls below the lower set point howeve...

Page 4: ...he thresholds may be read back and fine tuned if necessary using the HP2000 Please note that the values are non specific units i e not lux Note The light level perceived by the detector at the moment immediately prior to a Download operation is shown momentarily on the HP2000 screen following the Download this is a useful mechanism for troubleshooting Lights ON Lights OFF Upper Threshold Lower Thr...

Reviews: