Mounting Details

 

Installation Guidelines

The  MLSM2000A  Control  Module  is  designed  to  be  mounted  within  the  luminaire  on  fixing  centres  of  135mm. 

2

Connections to the control module as shown above should be made using single-core wire (0.5-1.5mm  ).

The interconnect cable between the detector head and the control module should be routed away from other luminaire 
internal wiring and away from the lamp end-caps.

The recommended position for the detector is in the middle of the luminaire.  Where this is not possible and the detector 
is fitted near one end of the lamps, please ensure that the detector is at the ‘cold’ end of the lamps.

The DHW/S Mini Head should be mounted such that only the raised front section of the bezel protrudes through the 
cut out in the louvre or infill panel.  This should be constructed in accordance with the dimensions above. 

1.  The Mini Detector Head must be mounted within the luminaire. Do not mount remotely. 

2.  The connecting cable must not be extended. 

3.  Artificial light illuminating the Mini Detector Head must only be reflected from the room - i.e. there must be no direct 

illumination. 

4.  In order to achieve satisfactory light-level regulating operation, a detector must observe a substantially greater 

proportion of artificial light from the luminaire(s) under its control than from neighbouring luminaires not under its 
control.  This is particularly important when planning the installed layout of linear luminaires that have an integral 
detector positioned at one end.

Neutral
OneSwitch  Input

Live OUT
Live IN

_

+

}

1-10V

Analogue

Control

TM

Neutral
Live IN

_

+

}

1-10V

Analogue

Control

Analogue 1-10V Ballast(s)

MLS Bus
Polarity Free

Mains Supply

To next

MLS device

OneSwitch Input
for manual control

Electrical Connections

800mm 

Flying Lead

RJ12

Plug

14.9mm

21.5mm

TOP VIEW

SIDE VIEW

135mm

32mm

21.5mm

147.5mm

18.8mm 17.5mm

21.3mm

(Height = 22mm)

Live IN

Ex-Or Limited, Haydock Lane, Haydock 
Merseyside, WA11 9UJ Tel. 01942 719229

Made in EC

Please read instructions prior to installation

Live OUT

OneSwitch  Input

Operating voltage 230V 50Hz   10%
Power consumption: <2W
tc 70 C
Max Load (Live OUT): 2 Amps
Max Number of Ballasts: 4
For use only with electronic, high-frequency 
ballasts                 

Detector

Connection

TM

Neutral

+

}

1-10V

Analogue

Control

+_

0.5 - 1.5

MLS Bus
Polarity Free

_

MLSM2000A

Control Module Part No

Analogue 1-10V 
Control Module

Mini Detector 
Head 

30mm

Summary of Contents for Ex-Or MLSM2000A

Page 1: ...rollers MLSM2000A Control Module DHW DHS Mini Detector Head for use with Analogue 1 10V and Fixed Output Electronic High frequency Ballasts Installation and Commissioning Instructions Note QuickSet Pro required for commissioning ...

Page 2: ...ust be no direct illumination 4 In order to achieve satisfactory light level regulating operation a detector must observe a substantially greater proportion of artificial light from the luminaire s under its control than from neighbouring luminaires not under its control This is particularly important when planning the installed layout of linear luminaires that have an integral detector positioned...

Page 3: ...eived ambient light level with no contribution from the controlled lighting Note When setting the regulating light level as described in the previous section the Threshold is also set to the current measured level Commissioning Detectors are supplied factory pre set which ensures the lighting will switch on automatically as soon as power is applied Final commissioning of the detectors requires the...

Page 4: ...perative that the MLS bus is wired with the correct type of cable normally it should be 1 5mm unscreened twisted pair Please read ApplicationNoteAN4001 for more details 6 Due to the fact that the photocell is on the ceiling looking down it is not possible for measurementsmade with a lux meter on the working plane to remain constant when daylight illuminates the ceiling and the working plane to a d...

Reviews: