Honeywell Ex-Or MLS2500CDR Installation And Commissioning Instructions Download Page 2

Introduction

The MLS2500CDR Mid-Range Detector offers high performance, directional presence detection 

and  contains  a  photocell  to  monitor  total  light  levels  allowing  the  light  output  of  dimmable 

luminaires to be adjusted to suit the natural light level available. It also contains an infrared port 

that  can  be  used  both  for  local  control  from  a  hand-held  device  when  in  service,  and  for 

CDW12U5/CDH4U5/CDH8U5 system commissioning. Properly installed and connected this is an 

SELV device. 

Positioning

Position the detector where it has a good "view" of the space to be controlled. An ideal location is in 

a corner adjacent to the entrance of a room or at one end of a corridor. Suitable fixing heights are 

between 2.5m and 3.5m.
This is an extremely sensitive movement detector. It is therefore essential that it be installed on a 

rigid surface that will not itself be subject to any movement or vibration.
Microwaves can penetrate lightly built partitions, glass etc and thus movement in adjacent spaces 

may  cause  spurious  triggering  if  the  orientation  and  sensitivity  setting  of  the  detector  is  not 

managed carefully.
This product  is not recommended for applications where there are large areas of metal, e.g. metal 

ceiling panels or metal flooring, as unpredictable sensitivity may result. 

Do not mount within 0.25m of a luminaire.
Fixing
The MLS2500CDR Semi Flush Version - 

Use a hole saw to cut a 76mm diameter hole into 

the ceiling tile. The flush ring is designed to clamp the ceiling tile beween its two halves.

Separate the detector from the under-ceiling half of the flush ring by loosening the locking screw so 

that about 3mm of thread is visible and twisting the detector anticlockwise

. Align the mounting screw holes of the above-ceiling half of the flush ring with those of the backbox 

and position both above the hole in the ceiling tile. Now offer the below-ceiling half of the flush ring 

to the underside of the ceiling tile and align the mounting screw holes with those above. Note that 

the locking screw tab on the under-ceiling half of the flush ring should be directly below the similar 

tab on the backbox and the arrow symbol on the inside of the backbox should point into the 

controlled area.

Insert the mounting screws through both halves of the flush ring and engage them in the brass 

inserts of the backbox. Final adjustments to the orientation of the detector can be made before the 

mounting screws are tightened to clinch the ceiling tile between the two halves of the flush ring. 

Connecting

The MLS2500CDR connects to the LCM via an eight core, RJ45 plug terminated, patch lead. 

All 

such patch leads must be segregated from mains wiring to preserve the detector SELV 

status that is provided by the LCM design.

Ready-made patch leads in lengths of, 3m, 5m and 10m are available from Ex-Or. (See back page 

for Part Numbers.)

The MLS2500CDRSM Surface Mounted Version - 

Separate the detector from its backbox by 

loosening the locking screw so that about 3mm of thread is visible and then twist the detector 

anticlockwise to release it from the backbox.

.

The fixing holes in the backbox allow for mounting onto a BESA box or directly onto a rigid surface.

The arrow symbol on the inside of the backbox should be aligned to point into the controlled area 

before the fixing screws are finally tightened.

Summary of Contents for Ex-Or MLS2500CDR

Page 1: ... MLS2500CDRSM MLS2500CDR MLS2500CDR and MLS2500CDRSM Mid range Directional Microwave Detectors with Photocell for use with CDW12U5 CDH4U5 CDH8U5 Programmable Intelligent Lighting Control Modules HC5 or HP2000 required for Photocell Commissioning ...

Page 2: ...ng half of the flush ring by loosening the locking screw so that about 3mm of thread is visible and twisting the detector anticlockwise Align the mounting screw holes of the above ceiling half of the flush ring with those of the backbox and position both above the hole in the ceiling tile Now offer the below ceiling half of the flush ring to the underside of the ceiling tile and align the mounting...

Page 3: ...arts Inside DO NOT OPEN Power consumption 10W I I I I I ta 0 40 C To CD Box Do Not Connect Socket for patch lead to LCM View on Back of MLS2500CDR Detector Bayonet Tab Receptacles Arrow Symbol Locking Screw Commissioning In the CDW12U5 and CDH4U5 CDH8U5 systems all configuration information is held within the LCMs themselves not in individual detectors Most of the configuration items are set up wi...

Page 4: ...bination of manually switching off lights and perhaps masking windows Using the HP2000 Programmer enter the Utilities menu and select User Remote Scroll down to Scene 1 and press and hold the OK button to store The luminaire s will blink to acknowledge a successful store operation Testing Detectors can be put into a temporary 10 second Off delay mode to check their sensitivity and range settings u...

Reviews: