Honeywell Ex-Or CDW12U5 Installation And Commissioning Instructions Download Page 4

W

D

H

F

D
2

An Example Configuration

SW1

SW2

SW3

, (Channels 2 & 4)

, (Channel 3)

, (Channels 4 & 5)

, (Channels 1, 2 & 6)

1
2
3

, (All Channels, 1-6)

W4400O

SW1 SW2

S

W

3

Part Numbers

CDW12U5   

Programmable LCM with 12 luminaire sockets, 5 sensor 

 

 

and 5 override sockets

CDW12U5-B 

with MLS Bus operation card

CDW12U5-A 

c/w Analogue 1-10V dimming

CDW12U5-BA 

with MLS Bus card c/w Analogue 1-10V dimming

CDW12U5-BAWL 

with MLS Bus card and wireless switch card

CDW12U5-DALI 

c/w Digital DALI dimming

CDW12U5-BDALI 

with MLS Bus card c/w Digital DALI dimming

CDW12U5-BDALIWL  

with MLS Bus card & wireless switch card c/w Digital DALI dimming

CDW12U5-D 

c/w DSI dimming

CDW12U5-BD 

with MLS Bus operation card c/w Digital DSI dimming

CDW12U5-BDWL 

with MLS Bus & wireless switch card c/w Digital DSI dimming

CDWDC 

 

Plug-in Digital Dimming Card

CDWAC 

 

Plug-in Analogue Dimming Card

CDWBC 

 

Replacement MLS Bus Interface

Sensors with photocell:

MLS2500CDR 

 

Corner-mount Microwave, semi-flush mounted 

MLS2500CDRSM   

As above - surface mounted

MLS2401CDR 

 

360° Microwave, flush mounted

MLS2401CDRSM   

As above - surface mounted

MLS3000CDRF 

 

360° PIR, flush mounted

MLS300CDRSM   

As above - surface mounted

MLS3003CDRF 

 

360° PIR with tilting lens, flush mounted

MLS3003CDRSM 

As above - surface mounted

MLS3003CDRMBF 

360° Mid-Bay PIR with tilting lens, flush mounted

MLS3003CDRMBSM 

As above - surface mounted

MLS3003CDRHBF 

360° Hi-Bay PIR with tilting lens, flush mounted

MLS3003CDRHBSM 

As above - surface mounted

MLSM2002CDR   

Control module for integration within luminaire 

DHS 

 

 

360° Mini detector head for use with MLSM2002CDR - silver bezel

DHW 

 

 

360° Mini detector head for use with MLSM2002CDR - white bezel

MLSM2002CDRDHPBW Mini Detector c/w Control Module & Plasterboard Mounting Kit

Sensor Patch Leads:

BT5E030GY 

3m Patch Lead

BT5E050GY 

5m Patch Lead

BT5E100GY 

10m Patch Lead

Luminaire Leads:

CPWL633      

3m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell

CPWL635            5m, 3-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL653            3m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL655            5m, 5-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL663MF 

3m Luminaire Extenstion Cable - 6-pole, 6-core male/female GST 18/6

Emergency Luminaire Leads:

CPWL643            3m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL645            5m, 4-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL663            3m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell
CPWL665            5m, 6-core, 6-pole GST 18/6 Plug & Ex-Or Latching Shell

Plugs

CPWL6 

 

GST18/6 Plug & Ex-Or Latching Shell

CPWL6S   

GST-6 Ex-Or Plug-locking mechanism (shell only)

CDWIP 

 

Switch Input Plugs (set of 5)

Technical Data

Operational Supply:

  230V ~ 50Hz

Power Consumption:

  18W maximum

Product Rating & Recommended Circuit Protection: 

  16A

Max Switched Live Load per Channel:

  6A

Max Total Switched Live Load:  

16A            

Digital Dimming Ballasts per Channel: 

10 maximum

Digital Dimming Ballasts per LCM: 

 40 maximum

1-10V Dimming Ballasts per Channel:

  20mA (SINKING only). See manufacturer’s 

specification: worst case 10 ballasts but Philips HF-R, for example, 20 ballasts. 
Observe Switched Live Load limits above.

Maintained Live Output:

  2A total per LCM

Mains Supply Terminal Capacity:

  1x2.5mm² or 1x4.0mm²

Override Switch Input Connector:

  2.5mm²

MLS Bus Connector:

  2.5mm²

MLS Bus Cable: 

 1.5mm² unscreened twisted pair  - see Application Note AN4001

Case Material:

  Polycarbonate

Case Finish:

  Lightly textured charcoal grey RAL7016

Height (H) = 50mm (108mm including plug and lead)
Width (W) = 315mm (361mm including mounting feet)
Depth (D) = 205mm    Fixing Centres (F) = 340mm    Weight = 1.55 kg

A  school  classroom,  where  a  sophisticated  blend  of  manual  and  automatic  control  is 
required, with overall manual control by staff augmented by automatic dimming control of 
luminaires adjacent to large windows and the automatic switch-off of the lights following an 
often ragged quitting of the room at the end of a teaching session, where staff typically will 
not be the last to leave.

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with 
normal household waste.
Do not burn.

W

D

H

F

D
2

Ex-Or operates a genuine policy of continuous improvement. You may expect the specification to 
be regularly enhanced. For the latest technical information please visit  www.ex-or.com

Important Additional Notes

1.    The CDW12U5 must be earthed as it provides the only path to earth for luminaires 

connected through it.

2.    A dimming control output should be connected only to the control inputs of ballasts, 

never to another channel's dimming output and never to other types of equipment.

3.    Although nominally 12V, the dimming control outputs are not to be treated as SELV, 

due to their passage through multiple luminaire enclosures and therefore should be 
treated with the same respect as mains with regard to wiring practice.

4. 

This equipment switches lights no more frequently than would a responsible human 
occupant.  However,  manufacturers  of  some  particular  lighting  types  (e.g.  '2D' 
luminaires) may specify a maximum number of switching cycles and/or a minimum 
on-time  in  order  to  achieve  a  predicted  lamp  life.  Please  check  with  the 
manufacturer of the luminaires to ensure that they are compatible with automatic 
controls in this respect. 

Dimensions

W

H

F

D
2

Sensor

Sensor

Honeywell Ex-Or

St. Marks Court, North Street, Horsham, West Sussex, RH12 1BW, UK.

 

Tel: +44 (0)1942 719229, Fax: +44 (0)1942 508753  
Email: [email protected]
www.ex-or.com

Reviews: