background image

10. Seal the duct connections with duct tape.

NOTE:

To avoid sagging and stress on the humidifier, add support
when ducting is longer than 4 ft (120 cm).

11. Reinstall the humidifier pad assembly in the humidifier housing.

NOTE:

Be sure the water feed tube nozzle is not pinched or
kinked.

12. Hinge the cover in place and secure with the thumbscrew located at

the bottom of the cover.

WIRING

CAUTION

Hazardous Voltage.
Can cause personal injury or equipment damage.

Disconnect power supply before installing or servicing.

On multispeed blower applications, do not wire the high voltage
side of the transformer to the same power source that services
the furnace blower or the transformer may burn out prematurely.

All wiring must comply with applicable local codes, ordinances and
regulations.

1. Mount the transformer in a convenient location.

IMPORTANT

Install transformer on the outside of a grounded metal junction box
using only a 7/8 in. (22 mm) knockout hole. Place mounting tabs
into the knockout hole and firmly tighten the locking screw. Field
wiring connections and grounding means for the transformer and
enclosure shall be in accordance with the National Electrical Code
(NEC) and the Canadian Electrical Code (CEC).

2. Connect the wires to the 120V side of the transformer.

For humidity control wiring connections:

1. Wire the humidifier solenoid valve, current sensing relay or sail

switch, humidity control and transformer. Refer to humidity control
installation instructions for mounting and wiring information.

IMPORTANT

The humidifier must be energized during blower motor cycles for
proper operation.

Current sensing relay or sail switch is not needed with the
Automatic Humidity Control.

NOTE:

Select models of fan centers include humidifier taps so the
current sensing relay or sail switch are not needed.

PLUMBING SADDLE VALVE

Hot or cold water, either hard or softened, can be used in the humidifier.

1. Use the self-piercing saddle valve (included) to tap into the water

supply line at an appropriate location.

CAUTION

Chemical Hazard.
Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner.

IMPORTANT

The saddle valve is not designed to regulate water flow. The valve
is either open or closed.

To prevent debris from clogging the solenoid in-line filter, be sure
to install the saddle valve handle pointing toward the ceiling.

NOTE:

Lightly clean the copper tubing ends with fine sandpaper
before making any connections.

2. Use 1/4 in. O.D. copper tubing and connect the saddle valve to the

inlet side of the solenoid valve.

a.

Place the brass compression nut over the copper tubing.

NOTE:

Do not over tighten the compression nut. Moderate
tightness prevents leaking.

b.

Slide the brass ferrule over the tubing.

c.

Insert the tubing into the solenoid valve fitting and support the
valve while tightening the compression nut.

NOTE:

Slope the drain downward for correct drainage.

3. Connect a 1/2 in. drain tube to the humidifier drain fitting and run to a

suitable drain.

CHECKOUT

1. Open the saddle valve.

NOTE:

The furnace blower must be on for the humidifier to operate.

2. Set the thermostat setpoint to 10

°

F (6

°

C) above the room

temperature.

3. Set the Convertible Humidity Control to a high humidity setting, or

place the H1008A Automatic Humidity Control in the test position.

4. Observe the water running out of the drain line to be sure the

humidifier is working properly.

5. Check for leaks.
6. Reset the thermostat and Convertible Humidity Control to a

comfortable setting, or the Automatic Humidity Control to the desired
frost factor setting.

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

69-1424EF   G.H.   9-00

Home and Building Control
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422

Home and Building Control
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 429

Summary of Contents for enviracaire Elite HE265A

Page 1: ...dequate space for the solenoid valve and drain line Check that there is adequate space above the humidifier to remove and install the humidifier cover Do not install on a furnace jacket M12248B HORIZONTAL DOWN FLO LOWBOY HIGHBOY Fig 1 Typical humidifier installation locations 2 Tape this piece of paper in position as your template and trace around the template 3 Remove the template and carefully c...

Page 2: ...r cold water either hard or softened can be used in the humidifier 1 Use the self piercing saddle valve included to tap into the water supply line at an appropriate location CAUTION Chemical Hazard Can cause personal injury or equipment damage Do not use any line connected to an air conditioner IMPORTANT The saddle valve is not designed to regulate water flow The valve is either open or closed To ...

Page 3: ...ptimal de l appareil 1 Déterminer l endroit le mieux approprié pour l humidificateur et tracer une ligne de niveau sur le plenum Voir la Fig 1 M12248B HORIZONTAL DOWN FLO LOWBOY HIGHBOY Fig 1 Emplacements types de l humidificateur IMPORTANT Installer l humidificateur à une distance minimale de 76 mm 3 po au dessus du boîtier de l appareil de chauffage afin de laisser un espace suffisant pour le mo...

Page 4: ...ur à ailette REMARQUE Certains modèles de ventilateurs ont des prises pour humidificateurs Si tel est le cas il n est pas nécessaire d installer un relais de détection de courant ou un interrupteur à ailette TUYAUTERIE DU ROBINET VANNE À ÉTRIER L humidificateur fonctionne avec de l eau dure ou de l eau douce L eau peut être chaude ou froide 1 Utiliser le robinet vanne à étrier autoperceur fourni p...

Reviews: