Electrical installation
Installation guide 854 ATG
Page 17
Device
Cable requirements
977 Tank Side Indicator
: Twisted pair and shielded; R
max
= 5
Ω
/ line, maximum cable length
50 m (160 ft).
GFC (Foundation™ Fieldbus) : Requires external supply 9 – 24 Vdc
Nominal current 11 mA
Maximum current (startup) 16.70 mA
Water bottom probe
: Twisted pair and shielded; R
max
= 25
Ω
/ line.
(no VITO water sensor)
(only with HART
7
protocol).
Note:
If also pressure transmitters are connected, use a junction box for parallel connection of the
pressure transmitters and water bottom probe.
Figure 11 Intrinsically safe option connections