L7148F ELECTRONIC AQUASTAT

®

 CONTROLLER

5

68-0189—2

Fig. 3. External connections for L7148F.

ADJUSTMENT

A manual adjustment potentiometer is used to set the high 
limit controller. At the maximum setpoint of 240°F (116°C), the 

calibration tolerance is plus 10°F (6°C) and minus 15°F (8°C). 

(Meets ASME and UL353 Standards).

(Select models available with other ranges.)

NOTE: Setpoint Range: 130°F (54°C) to 240°F (116°C).

Differential: Fixed at 10°F (6°C). 

OPERATION

A system containing an L7148F Electronic Aquastat does 
not require a separate high limit controller. The L7148F can 

replace a Honeywell L4080 High-Limit Controller and an 

R8225 Transformer. The L7148F does not provide a low limit 
function. An external transformer, appropriately sized for the 

specific application; a sensor, and an immersion well are 

required for Aquastat¨ operation.

In the L7148F system without an advanced feature module, 

the circulator is on any time there is a thermostat call for 
heat. The addition of an advanced feature module may alter 

operation. The burner is also on during a thermostat call for 

heat unless the boiler water temperature exceeds the high 
limit setting.

The L7148F Electronic Aquastat has three states of operation: 
normal, high-limit and reset: (The control moves back and 

forth between the normal and high-limit states, as needed. 

However, the control only enters the reset state when there 
is an abnormal condition such as an internal error or shorted 

sensor.)

1. Normal:

 The control enters the normal state when the 

temperature of the boiler drops below the high limit 

setting minus 10°F (-12°C). The control exits the normal 
state and returns to the high limit state when the 

temperature of the boiler exceeds the high limit setting. 

2. High limit: 

The control enters the high limit state when 

the temperature of the boiler exceeds the high limit 

setting. The control exits the high limit state and returns 

to the normal state when the temperature of the boiler 
drops to the high limit setting minus 10°F (-12°C).

3. Reset: 

Detects an error condition such as an open 

sensor and shuts down all outputs. The control 
continues to function and automatically restarts if the 

error condition is corrected. 

High Limit

The high-limit switch shuts off the burner (B1, B2 output) when 
the boiler water temperature exceeds the high-limit setting. 

Because heating systems differ, the correct temperature 

setting for each system can vary. Follow the boiler 
manufacturer recommendations for the proper setting. Turn 

the HIGH-LIMIT dial on the control until the desired setting is 

directly below the indicator.

Sequence of Operations

The state of the burner and circulator outputs are dependent 

on the thermostat input mode (On/Off) and the current 

operation mode (High limit/Normal/Reset). See Table 2 
Sequence of Operations.

NOTE: Table 2 applies only to the operation of the Electronic 

Aquastat Controller without an advanced feature 

module. Advanced feature modules provide 

additional functions such as boiler temperature 
display and outdoor reset of high limit. Changes in 

output states and operation modes caused by these 

additional functions are not included.

COM

L7148F

HIGH LIMIT DIAL

2

L1

L2

DISCONNECT 
SWITCH

1

6

CIRCULATOR

TO ADVANCED
FEATURE
MODULE

TO BOILER
SENSOR

TO THERMOSTAT 
OR SWITCH 
CLOSURES 
FOR ZONES

24V

COM

POWER SUPPLY. PROVIDE DISCONNECT MEANS 
AND OVERLOAD PROTECTION AS REQUIRED.

GROUND MUST BE AN EARTH GROUND CONNECTION.

B1 AND S1 ARE 3/16 IN. QUICK CONNECT TERMINALS. 
ALL OTHER TERMINALS ARE 1/4 IN.

C, COM, Z, B2, G ARE ALL CONNECTED INSIDE DEVICE.

FOR EXTERNAL TRANSFORMER VA REQUIREMENTS, 
REFER TO APPLICATION SECTION.

R IS A CONVENIENCE TERMINAL FOR 24V HOT 
CONNECTION FOR USE WITH IGNITION CONTROLS.

1

2

3

4

5

6

L2X

L1X

C

R

5

M17967

OPTIONAL VENT
DAMPER PLUG

COM
BURNER
CONTROL
24V HOT

TO VALVE 
OR
IGNITION 
CONTROL

CIRC

C1

G

L1 C2

L2

L2X

L1X

B2

B1

R

C

R

DATA
PORT

ST

A

TUS

THERMOST

A

T

C

W

R

S1 S2

4

4

4

4

4

3

3

Summary of Contents for Electronic Aquastat L7148F

Page 1: ...ck connect or AMP plug connections T TV and Z terminals are provided in a terminal block with screw connections Vent damper plug optional Separate high limit control not required Software defined minimum maximum limit settings External 120 Vac to 24 Vac transformer ordered separately is field replaceable and upgradable Patented limit rated 209659A B C Sensors are separately replaceable Communicati...

Page 2: ...d feature modules L7148F Electronic Aquastat Controller with AMP plug connections with or without vent damper plug and communications port for adding advanced feature modules AMP connector on wiring board for transformer connection High Limit Setpoint Range 130 F to 240 F 54 C to 116 C Select models may be different Differential Fixed 10 F 6 C Select models may be different Operating Voltage Range...

Page 3: ...om of well IMPORTANT The L7148F is not designed for spud mounting to the sensing well Sensor and immersion well are not provided and must be purchased separately Mounting screws must be obtained locally See Table 1 for sensor specifications The sensor is adaptable to existing immersion wells with a shell I D of 3 8 in 10 mm To order an immersion well contact your distributor or Honeywell sales rep...

Page 4: ...tions 1 Strip 1 16 in of insulation from the wire end 2 Insert the wire under the terminal screw and contact plate 3 Using a standard flat headed screwdriver tighten the screw until the wire is firmly in contact with the screw and contact plate 4 Tighten the screw an additional one half turn For quick connect terminal connections Connect the quick connect to the appropriate terminal on the control...

Page 5: ...l exits the high limit state and returns to the normal state when the temperature of the boiler drops to the high limit setting minus 10 F 12 C 3 Reset Detects an error condition such as an open sensor and shuts down all outputs The control continues to function and automatically restarts if the error condition is corrected High Limit The high limit switch shuts off the burner B1 B2 output when th...

Page 6: ...ON B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 7 M11475B L1 HOT L2 1 4 3 TR TH TH TR T87F ZONE 3 T87F ZONE 2 T87F ZONE 1 END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F 3 TR TH TH TR END SWITCH V8043F COM L7148F HIGH LIMIT...

Page 7: ... 2 L1 L2 DISCONNECT SWITCH 1 6 TO ADVANCED FEATURE MODULE TO BOILER SENSOR 24V COM L2X L1X C R 5 OPTIONAL VENT DAMPER PLUG C1 G L1 C2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 4 4 4 4 4 3 3 TR TH THTR LOW VOLTAGE GAS VALVE VR8300 L1 HOT L2 1 1 2 2 3 3 4 4 4 4 3 4 5 6 5 1 2 4 6 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND...

Page 8: ...ENSOR 120V L2X L1X C R 3 OPTIONAL VENT DAMPER PLUG COM BURNER CONTROL 24V HOT TO VALVE OR IGNITION CONTROL C1 G L1 C2 L2 L2X L1X B2 B1 R C R DATA PORT STATUS THERMOSTAT C W R S1 S2 5 5 5 5 5 4 4 L1 HOT L2 1 1 2 3 1 2 3 1 2 3 1 2 3 CIRCULATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERM...

Page 9: ...NT DAMPER IS PLUGGED INTO L7148F FUSE BLOWS WHEN THERMOSTAT FIRST CLOSES AFTER FUSE BLOWS L7148F OPERATES ONLY WHEN VENT DAMPER IS CONNECTED SEE VENT DAMPER PRODUCT SPECIFICATIONS FOR INTERNAL SCHEMATICS S1 IS A 3 16 INCH QUICK CONNECT TERMINAL S2 IS 1 4 INCH THIS DEVICE HAS AMP PLUGS C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION...

Page 10: ...NS AND OVERLOAD PROTECTION AS REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R882C IS PROVIDED WITH NEC CLASS 1 ENCLOSURE B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C COM Z B2 G ARE ALL CONNECTED INSIDE DEVICE R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTR...

Page 11: ...REQUIRED GROUND MUST BE AN EARTH GROUND CONNECTION B1 AND S1 ARE 3 16 INCH QUICK CONNECT TERMINALS ALL OTHER TERMINALS ARE 1 4 INCH C Z B2 G ARE ALL CONNECTED INSIDE DEVICE FOR EXTERNAL TRANSFORMER VA REQUIREMENTS REFER TO APPLICATION SECTION R IS A CONVENIENCE TERMINAL FOR 24V HOT CONNECTION FOR USE WITH IGNITION CONTROLS 1 2 3 4 5 6 M11479B 24 VOLT COMMON 24 VOLT HOT EFT OUTPUT 24 VOLT THERMOSTA...

Page 12: ... STARTS THERMOSTAT OR THERMOSTAT WIRING PROBLEM CHECK SYSTEM PER INSTRUCTIONS PROVIDED WITH THERMOSTAT NO NO YES NO YES CHECK L7148F DIAGNOSTIC LED FLASHING TWO BLINKS CHECK SENSOR CONNECTIONS IF GOOD REPLACE SENSOR THREE OR FOUR BLINKS INTERNAL ERROR REPLACE L7148F L7148F IN RESET MODE WAIT FIVE MINUTES FOR CONTROL TO RESET VENT DAMPER OPEN CHECK FOR 24V AT B1 B2 YES CHECK VENT DAMPER CABLE AND C...

Reviews: