24
Emergency Command Center Manual —
P/N LS10001-000FL-E:G 5/3/2016
Product Description
Optional Equipment
power. The amplifier functions as 50 watts with 50 watts as backup, 100 watts with no backup or
100 watts with 50 watts backup using ECC-50WBU. The unit comes standard with 8 speaker cir-
cuits. Speaker circuits are activated/de-activated manually or automatically by the ECC-50/100
main console. The unit is capable of either 25 V
RMS
or 70.7 V
RMS
operation. Refer to the
ECC Dis-
tributed Audio
manual. Not for use in Canadian applications.
ECC-RM Remote Microphone
The ECC-RM has a hand held microphone and is housed in its own cabinet with keyed lock. It
requires an external data bus connection, an external audio riser connection, and an external opera-
tor interface power connection (24 volts DC) from the ECC-50/100 main console. ALL CALL pag-
ing can be broadcast over the speaker circuits by depressing the microphone's push-to-talk switch.
Not for use in UL2572 Mass Notification or Canadian applications.
ECC-RPU Remote Page Unit
The ECC-RPU has a hand held microphone and 8 message buttons. It is housed in its own cabinet
with a keyed lock or thumb lock (requires AHJ approval). It also has a 9th button that will activate
an MMF-300 monitor module mounted inside the cabinet. This may be used for HVAC shutdown
applications when the monitor module is connected to the FACP SLC polling loop. The remote
page unit requires an external data bus connection, an external audio riser connection, and an exter-
nal operator interface power connection (24 volts DC) from the ECC-50/100 main console. ALL
CALL paging can be broadcast over the speaker circuits by depressing the microphone's push-to-
talk switch. ALL CALL broadcast of a stored message can be done by pressing a message button.
The message buttons operate in the same fashion as the message buttons on the ECC-50/100 main
console. Not for use in UL2572 Mass Notification or Canadian applications.
ECC-LOC Local Operator Console
The ECC-LOC has a complete operator interface like the ECC-50/100 main console and is housed
in its own cabinet with a keyed lock or thumb lock (requires AHJ approval). The local operator
console requires an external data bus connection, an external audio riser connection, and an exter-
nal operator interface power connection (24 volts DC) from the ECC-50/100 main console.
NOTE:
Any combination of up to eight audio boosters comprised of ECC-50DA, ECC-125DA,
and ECC-50BDA can be used in the system. Their external data bus addresses must be unique
and must be sequential. Addresses are set via dipswitches on each unit's PC board. Refer to
Section 2.14 on page 55.
NOTE:
Any combination of up to eight remote consoles comprised of ECC-RM(s), ECC-RPU(s),
and ECC-LOC(s) can be used in the system. Their external data bus addresses must be set via
dip switches on each unit's PC board. Refer to Section 2.14 on page 55.
Summary of Contents for ECC-50/100
Page 83: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 83 Notes ...
Page 95: ...Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 95 Notes ...
Page 102: ...102 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Notes ...
Page 106: ...106 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Page 108: ...108 Emergency Command Center Manual P N LS10001 000FL E G 5 3 2016 Slide in Labels ...
Page 114: ...Cut along dotted line ...