OPERATOR MANUAL
MODBUS Address Change
NOTE:
To view or change the Modbus address, the Manning
LCD Module is required. Contact Honeywell Analytics to
obtain the module.
NOTE:
No two devices on the network can have the same
address. Each device needs to have a unique address.
Each device requires an address to communicate with the controller on the
network. The Modbus address normally comes factory programmed and
does not require to be programmed at startup. If it is determined that the
Modbus address needs to be
using the LCD module to view or change the
Modbus address
: The LCD module has two push-buttons;
Accept
and
Scroll
,
which will be utilized for this procedure (see Figure 7).
NOTE:
To display the Modbus address, press the
Scroll
button anytime
during normal operating mode.
1. Plug in the LCD module to the LCD port on the PCB (see Figure 7 on
page 26).
2. This module will power-up immediately and will display the normal
(idle) operating display.
3. Press the
Accept
button.
4. You will then be prompted for a password. The password is
MA
.
5.
Use the
Scroll
button to change the first letter to
M
.
Then press the
Accept
button.
6. You will then be prompted to change the second letter. If it is already
set to
A
, press the
Accept
button.
7. If the correct password is entered, you will be sent to the MAIN MENU.
8. In the MAIN MENU, scroll until the
ModbsID?
screen is displayed.
9. Press
Accept
to enter Modbus Address Change menu. The current
programmed Modbus address will be displayed (if not programmed at the
factory, the default address is 001).
10. If the Modbus address is correct, keep pressing the
Accept
button
until you are prompted to accept the current Modbus address. You
will then be returned to the MAIN MENU.
11. If the Modbus address is not correct, using the
Accept
and
Scroll
buttons, change the Modbus address the correct value.
12. You will then be prompted to save the changes. Press
Accept
to
save, and
Scroll
to abort. You will then be returned to the MAIN
MENU.
13. Use scroll button to navigate through the main menu. To exit the
menu, scroll until the LCD displays
Quit?
and press the
Accept
button. This will return you to normal operating mode. The LCD
module can be unplugged at this time.
26