EA122A

INSTALLATION

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

Do not use tools to adjust the EA122 or dam-
age to the vent may result. Use hands only to
adjust vent. A wrench may be used only on hex
during installation.

LOCATION

Install the EA122A on the positive side of the circulator

pump at the point where air will accumulate. This is usually
the high point of the supply or the return main in the system
as shown in Fig. 3.

Fig. 3—Install EA122A at high point in system.

INSTALLATION

1. Fit EA122A vent in piping at a location as specified

in the Location section.

2. Turn EA122A until vent fits tightly on piping. Use a

wrench to securely tighten hex.

3. If safety drain connection is desired, install a pipe

between vent discharge and drain using Q122A1001 Safe
Waste Connector.

4. Make sure that the red vent cap is securely tightened,

and that the valve is in the closed position by turning vent
body clockwise. See Fig. 4. Use hands only to avoid
damaging the vent.

5. With the valve in the closed position, flush the system

as required to remove dirt, debris and contaminants.

6. Fill the system with the appropriate solution.
7. Operate the EA122A by turning the air vent body

counterclockwise to the open position. Use hands only, see
Fig. 4.

8. Make sure the red vent cap is tightened all the way

to the stop position for proper leakage guard operation.
Use hands only to tighten.

Fig. 4—Turn vent body counterclockwise to
open or clockwise to close.

3

62-3038

Installation

M5492

SAFETY CONNECTION FOR PIPING
BETWEEN VALVE DISCHARGE AND DRAIN

EA122A AIR VENT

USE WRENCH TO
TIGHTEN HEX SECURELY.

INSTALL EA122A AT HIGH POINT IN SYSTEM.

M5494

CLOSED

OPENED

!

Summary of Contents for EA122A

Page 1: ...tant materials for use with water systems containing glycol mineral oils or petro leum based oils For use with water systems up to 230 F 110 C Not suitable for steam systems Uses 1 8 in NPT male pipe thread Maintains quiet and efficient operation CONTENTS Specifications 2 Ordering Information 2 Installation 3 Operation 4 Service 4 Troubleshooting 5 EA122A AutomaticAir Vent The Honeywell Braukmann ...

Page 2: ...ption Model Number Automatic Air Vent with leakage EA122A1002 guard and Skega seal ACCESSORIES Description Part Number Cover Assembly includes cover float P122B1002 assembly and vent cap Safe Waste Connector Connects top vent Q122A1001 to 1 4 in O D tube Vent cap Red Includes leakage guard 204992 OPERATING RATINGS Maximum Pressure 90 psi Maximum Temperature 230 F 110 C SAFETY RATINGS Maximum Press...

Page 3: ...ion as specified in the Location section 2 Turn EA122A until vent fits tightly on piping Use a wrench to securely tighten hex 3 If safety drain connection is desired install a pipe between vent discharge and drain using Q122A1001 Safe Waste Connector 4 Make sure that the red vent cap is securely tightened and that the valve is in the closed position by turning vent body clockwise See Fig 4 Use han...

Page 4: ...riz ing or draining the system To clean the seat area proceed as follows 1 Turn the vent body clockwise to the closed position isolating the vent from the system See Fig 4 2 Remove the float assembly by unscrewing the outer ring at the top of the body and lifting up the black cover assembly See Fig 5 3 Carefully clean any dirt or debris from the seat area 9 Make sure the red vent cap is tightened ...

Page 5: ...tached to the vent lever as shown in Fig 5 Water is leaking from the EA122A 1 Make sure the red vent cap is tightened all the way to the stop position 2 Adjustthevalvetotheclosedpositionbyturningtheventbodyclockwise 3 Clean the vent as described in the Service section 4 If internal parts appear damaged or deteriorated replace cover assembly part no P122B1002 5 62 3038 CAUTION TheEA122Amaybehotduet...

Page 6: ...6 ...

Page 7: ...7 62 3038 ...

Page 8: ...Printed in U S A Honeywell Braukmann Helping You Control Your World Honeywell Inc 1985 Douglas Drive North Golden Valley Minnesota 55422 ...

Reviews: