E-MON INTERVAL DATA RECORDER
23
62-0394—06
Appendix F - System Wiring Guides
NOTE: METERS 1-16 MUST BE INSTALLED WITHIN 500 FEET OF IDR.
(UP TO 16 METERS)
(UP TO
16 METERS)
~~
4-CONDUCTOR
FLAT MODULAR CABLE
UP TO 4000 FEET TOTAL
DAISY-CHAIN
UP TO 26 IDR-16S PER
CHANNEL
USB
KEY*
CONNECTS VIA
USB PORT ON PC
RJ-11
6-COND.
RJ-45
RJ-11
6-COND.
RJ-45
6-COND.
RJ-45
IDR A-B
IDR Y-Z
CONNECTION
CABLE TYPE CONNECTOR
IDR TO METERS 1-16
6-COND. 22-26 AWG
RJ-45
(PINS 1 & 8 NOT USED)
IDR TO USB KEY
4-COND. 26 AWG
RJ-11
IDR TO RS-232 KEY 2000
4-COND. 26 AWG
RJ-11
RS-232 KEY 2000 TO COMPUTER** 8-COND.
22-26
AWG RJ-45/DTE
FLAT MODULAR CABLE
IDR TO PULSE METER
2-COND. 14-22 AWG
** SUPPLIED BY HONEYWELL
NOTE: INTERIOR INTERCONNECTING COMMUNICATIONS ARE SUPPLIED
WITH THE PRE-WIRED MMU-TYPE METERING CABINETS.
NOTE: WHEN CONSTRUCTING FIELD-INSTALLED CABLES, MODULAR
CABLES MUST BE MADE SO THAT THE INDIVIDUAL WIRES GO
THROUGH ON THE SAME PIN NUMBER.
* CONTACT HONEYWELL FOR USB-ONLY CONNECTION.
3RD
PARTY
METER
3RD
PARTY
METER
3RD
PARTY
METER
PAIR OF WIRES
(#22-#14 AWG)
PC
AC ADAPTER