3. MAIN FEATURES

4. INSTALLATION

INSTALLATION

It is important before starting these procedures that the detailed information

provided in the DX100 Series Termination Units Technical Handbook about

DX100 (M) installation has been carefully considered at the planning stage.

General Installation Guidelines

1. Read the Warnings and Cautions at the beginning of this document and all the

relevant instructions before starting any of the installation procedures.

2. Identify external cable requirements and the necessary cable entry ports to be used

on the Termination Unit.

3. Refer to the documentation for the associated control system for details about

external network connection information, field wiring, interconnections, etc.

4. Refer to the relevant handbooks for details about the gas detectors.
5. Isolate all associated power supplies and ensure that they remain 

OFF

during the

procedures. Ensure a gas-free atmosphere.

MECHANICAL INSTALLATION PROCEDURES

Mechanical Installation Guidelines

1. Identify a suitable location where the Termination Unit can be mounted. The

Termination Unit should be fitted to a flat surface.

2. When fitting a Termination Unit consideration should be made regarding the

probability of mechanical impacts and interference from other equipment and

apparatus.

3. The mounting plates for the Searchline Excel gas detectors, and to which the

DX100 (M) unit is attached, have fixing holes that are unthreaded. Unit and

gas detector system component mounting holes are threaded. For the identity

of other plate holes refer to the Searchline Excel Technical Handbook.

With Searchpoint Optima

This procedure describes how the

DX100 (M) 

is installed at the

mounting location and then the

Optima gas detector is fitted to the

Termination Unit.
(1) Securely fit the Termination

Unit at the required monitoring

point.

Use the two Termination Unit

mounting lugs. Ensure the

communications link entry socket connector is located at the bottom. This

fulfils the requirement to position the Optima sensor horizontally so that the

risk of fouling the gas detector's optical surfaces is reduced.

(2) Remove the Termination Unit lid.

Use the lugs on the lid to unscrew it anticlockwise from the Termination Unit

base.

(3) Fit the Optima detector to the left-hand entry.

First remove the 3/4 NPT approved blanking plug.

(4) Fit approved certified 3/4 NPT cable glands or conduit fittings to the

Termination Unit cable/conduit entries as required.

(5) Fit the external field wiring through the cable/conduit fittings and secure.
(6) Terminate the gas detector and field wiring.

Refer to 

Electrical Installation

.

With Searchline Excel Open-Path

The

DX100 (M)

 is fitted to the

Excel receiver’s mounting plate

and then the units are wired.

(

1) Securely fit the 

Termination

Unit

 to the mounting plate

so that the communications

link entry socket connector

is located at the bottom.

Use the 

Termination Unit

mounting holes marked 

G

on

the diagram below. The box

uses two of the four holes

depending on the plate’s

horizontal orientation.

(2) Remove the Termination Unit lid.

Use the lugs on the lid to unscrew it

anticlockwise from the 

Termination

Unit

 base.

(3) Attach the Searchline Excel gas

detector's cable to the 

Termination

Unit

.

Fit to the bottom left entry after

removing the 3/4 NPT blanking plug.

(4) Fit approved certified 3/4 NPT cable

glands or conduit fittings to the

Termination Unit

 cable/conduit entries as necessary.

This section shows the main features of the Termination Unit and also details

important dimensions for the unit when installing.

INSTALLATION

INSTALLATION

INSTALLATION

(5) Fit the external field wiring through the cable/conduit fittings and secure.
(6) Terminate the gas detector and field wiring.

Refer to 

Electrical Installation

.

With Searchline Excel Cross-Duct

The

DX100 (M)

 is fitted to the

Cross-Duct mounting plate and then

the units are wired.

(

1) Securely fit the 

Termination

Unit

 to the mounting plate so

that the communications link

entry socket connector is

located at the bottom.

Use the mounting holes marked

G

on the diagram below.

(2) Remove the 

Termination Unit

lid.

Use the lugs on the lid to

unscrew it anticlockwise from

the

Termination Unit

 base.

(3) Attach the two cables from the Searchline Excel Cross-Duct gas detector to

the

Termination Unit

.

Fit the transmitter's cable to the bottom left entry after

removing the 3/4 NPT blanking plug. Fit the receiver's

cable to the right-hand entry after removing the 3/4

NPT blanking plug (see the diagram). Use suitably

approved certified glands/adaptors.

(4) Fit an approved certified 3/4 NPT cable gland or

conduit fitting to the 

Termination Unit

 cable/conduit

entry as necessary.

(5) Fit the external field wiring through the cable/conduit

fitting and secure.

(6) Terminate the gas detector and field wiring.

Refer to 

Electrical Installation

.

ELECTRICAL INSTALLATION

Electrical Installation Guidelines

1. Isolate all associated power supplies and ensure that they remain 

OFF

during the procedures. Ensure a gas-free atmosphere.

2. Ensure that approved and certified cable glands have been fitted to the

Termination Unit cable entries where used for field wiring, with sealing

washers where necessary to maintain the ingress protection rating.

3. Ensure that any cable gland/conduit locking rings are fitted before terminating

the cables.

4. Make sure that a conduit sealing fitting is installed within 460mm (18in.) of the

Termination Unit on all conduit runs. The following diagram shows a vertical

conduit seal fixed in the conduit run close to a Termination Unit fitted with an

Optima unit. Excel Open-Path and Cross-Duct installations should be similar.

5.

6.
7.

8.

9.

Ensure that approved and certified blanking plugs are fitted to all unused

 

Termination Unit cable entries.

The Termination Unit mounting plate must be bonded to a protective earth.

 

Suitable crimps and/or ferrules must be fitted when connecting more than

 

one wire to a Termination Unit terminal.

The field terminals of the Termination Unit accept single or multi-stranded

 

wire

from 

22-12  AWG  (

0.326  to  3.31  m

m

2

)

,  105C

. Cables should be

 

routed carefully to avoid

 

physical and environmental hazards such as

 

mechanical stress and high

 

temperatures.

In order to ensure correct operation and to meet requirements for RFI and

 

EMC, it is recommended that all field cables are screened with the cable

 

screen connected at one end only (see the Technical Handbook).

Connect the gas detector and field wiring to the terminal blocks in the DX100 (M)

Termination Unit according to the following wiring diagrams and tables.

3

INSTALLATION

Searchpoint Optima

1

6

1

6

TB1

Optima Wires

green/yellow

(earth)

blue (B)

orange (A)

white (4-20mA)

black (0V)

red (+24VDC)

TB2

Field Wires

earths

Modbus B

Modbus A

0VDC - in

+24VDC - in

4-20mA - out

Screen - Modbus Drain

Terminal/

 Gas Detector Wiring

Field Wiring

Number

Function

Colour

TB1

1

-

-

-

2

A

Orange

-

3

B

Blue

-

4

-

-

Drain

5

-

-

Modbus B

6

-

-

Modbus A

TB2

1

+24VDC

Red

-

2

-

-

+24VDC - Supply

3

4-20mA

White

4-20mA - Output

4

-

-

-

5

0V

Black

-

6

-

-

0V - Supply

Earth

-

Earth

Green/Yellow

Earth

Posts

Barrier Earth

Searchline Excel Open-Path

1

6

1

6

TB2

TB1

Field Wires

0VDC - in

+24VDC in

Modbus A

earth

earth

4-20mA - out

Modbus B

Modbus Drain

Screen -

Excel Receiver

Wires

black (0V)

green/yellow (earth)

blue (B)

orange (A)

white (4-20mA)

red (+24VDC)

Terminal/

 Gas Detector Wiring

Field Wiring

Number

Function

Colour

TB1

1

-

-

-

2

A

Orange

-

3

B

Blue

-

4

-

-

Drain

5

-

-

Modbus B

6

-

-

Modbus A

TB2

1

+24VDC

Red

-

2

-

-

+24VDC - Supply

3

4-20mA

White

4-20mA - Output

4

-

-

-

5

0V

Black

-

6

-

-

0V - Supply

Earth

-

Earth

Green/Yellow

Earth

Posts

Barrier Earth

G

G

G

G

G

G

Searchline Excel Cross-Duct

Terminal/

    Gas Detector Wiring

Field Wiring

Number

Function Colour Receiver/Transmitter

TB1

1

-

-

-

-

2

A

Orange -

-

3

B

Blue

-

-

4

-

-

-

Drain

5

-

-

-

Modbus B

6

-

-

-

Modbus A

TB2

1

+24VDC Red

Receiver & Transmitter

-

2

-

-

-

+24VDC - Supply

3

4-20mA

White

Receiver only

4-20mA - Output

4

-

-

-

-

5

0V

Black

Receiver & Transmitter

-

6

-

-

-

0V - Supply

Earth

-

Earth

Green/ Receiver & Transmitter

Earth

Posts

Yellow

Barrier Earth

1

6

1

6

TB2

TB1

Cross-Duct

Receiver Wires

green/yellow
(earth)

orange (A)

blue (B)

white (4-20mA)

black (0V)

red (+24VDC)

Cross-Duct

Transmitter Wires

green/yellow (earth)

black (0V)

red (+24VDC)

Field Wires

0VDC - in

+24VDC - in

Modbus A

earth

earth

4-20mA - out

Modbus B

Screen -

Modbus Drain

Flexible Conduit

Cross-Duct
Mounting Plate

Field
Cable/
Conduit

DX100 (M)

Cross-Duct Receiver

Cross-Duct
Transmitter

Flexible Conduit

Searchline Excel
Mounting Plate

Field
Cable/
Conduit

DX100 (M)

Searchline
Excel
Receiver

Handheld
Interrogator Socket

Optima

DX100 (M)

Field Cable/Conduit

INSTALLATION