Honeywell DS06D Product Data Download Page 4

DS06D,G DIAL SET PRESSURE REGULATING VALVE

62-3052—1

4

Fig. 2. Adjusting Outlet Pressure

Fig. 3. Removing Bonnet.

MAINTENANCE AND REPAIR

Replacing DS06D,G Cartridge

The working parts of the DS06D,G, including diaphragm, valve 

seat, strainer, and disk, are all contained in a replaceable 

cartridge. To replace the cartridge:

1.

Close the supply valve and relieve the downstream 

pressure.

2.

Remove the dust cap. Relieve pressure on the spring by 

loosening the locking screw (do not remove) and turning 

the adjusting knob counterclockwise until no resistance 

is felt.

3.

Remove the bonnet (See Fig. 3) by turning 

counterclockwise. Remove the spring and protection 

washer (See Fig. 4).

4.

Remove the cartridge using two screwdrivers as levers 

(See Fig. 4). Remove the cartridge O-ring.

5.

Remove the strainer cup (See Fig. 5).

6.

Remove the strainer and strainer support. Remove the 

U-seal.

7.

Clean the inside of the valve and all the components. 

NOTE: Replace the U seal (provided in the repair kit) for a 

complete cartridge repair. 

8.

Replace the U-seal by placing the U-seal on the strainer 

support and pushing the assembly into place. The U-seal 

open end must face the strainer support (See Fig. 7). 

Replace the strainer onto the strainer support.

9.

Assemble the strainer cup O-ring onto the strainer cup 

and insert the assembly into the body of the valve. 

Tighten securely using the service tool. Do not over 

torque.

10.

Replace the new cartridge ensuring the O-ring is in 

place.

11.

Replace the protection washer with the lip up (away from 

the valve body). See Fig. 6.

12.

Replace the spring and bonnet. Tighten the bonnet using 

the service tool. Do not over torque.

13.

Adjust the outlet pressure following the procedure in 

Adjusting the Outlet Pressure section. 

Fig. 4. Removing Cartridge.

M11209

60

REMOVE DUST 

CAP.

LOOSEN LOCKING 

SCREW ONE TURN, 

BUT DO NOT REMOVE 

SCREW OR

ADJUSTING KNOB.

INCREASE

DECREASE

TURN ADJUSTING KNOB

TO INCREASE OR

DECREASE PRESSURE

UNTIL DIAL SCALE

INDICATES DESIRED

PRESSURE.

TIGHTEN  LOCKING

SCREW AND REPLACE

DUST CAP.

1

2

3

4

DO NOT REMOVE ADJUSTING KNOB. 

SETPOINT READOUT WAS CALIBRATED IN 

THE FACTORY AND SET AT 60 PSI. REMOVING

THE ADJUSTING KNOB CANCELS THIS 

CALIBRATION – AND REQUIRES RECALIBRATION 

USING A PRESSURE GAUGE.

MAXIMUM INLET PRESSURE IS 400 PSI. OUTLET 

PRESSURE RANGE IS 15 TO 130 PSI.

1

1

2

2

60

M11210

60

REMOVE BONNET USING

MT06A SERVICE TOOL

(ORDERED SEPARATELY) TO 

TURN COUNTERCLOCKWISE.

M11212

REMOVE CARTRIDGE USING

TWO SCREWDRIVERS 

AS LEVERS.

REMOVE SPRING

AND PROTECTION

WASHER.

Summary of Contents for DS06D

Page 1: ...ure adjustments without the use of a gauge in most applications FEATURES Built in factory calibrated outlet pressure adjustment dial Noncorroding unitized cartridge contains all working parts and is easily replaceable Outlet pressure range from 15 to 130 psi in all models inlet rating 400 psi Includes built in strainer and thermal bypass Narrow design to accommodate restricted installation require...

Page 2: ...gineered plastics Regulator Mechanism Fabric reinforced diaphragm Thermal Bypass Relief Integral thermal bypass relief mechanism on all models Seat Design Balanced single seat Inlet Pressure Maximum 400 psi Reduced Pressure Range 15 to 130 psi all models Outlet Pressure Factory set at 60 psi Dial Calibration 4 psi Differential 14 psi minimum for optimum regulation Reduced Ratio 10 1 maximum Temper...

Page 3: ...g valve if existing 3 Install the DS06D G with the arrow pointing in the direction of water flow any mounting orientation is acceptable The DS06D G can be installed directly onto a pipe using the female NPT threads on each end or by using single or double unions if required One union is provided CAUTION Heat from soldering can damage internal parts Always remove tailpiece or solder adapter prior t...

Page 4: ...iner support See Fig 7 Replace the strainer onto the strainer support 9 Assemble the strainer cup O ring onto the strainer cup and insert the assembly into the body of the valve Tighten securely using the service tool Do not over torque 10 Replace the new cartridge ensuring the O ring is in place 11 Replace the protection washer with the lip up away from the valve body See Fig 6 12 Replace the spr...

Page 5: ...ig 6 Replacing Protection Washer Fig 7 Internal Parts M11211 60 REMOVE STRAINER CUP USING MT06A SERVICE TOOL DUST CAP BONNET ASSEMBLY SPRING PROTECTION WASHER CARTRIDGE CARTRIDGE O RING UNION NUT TAILPIECE GASKET U SEAL STRAINER SUPPORT STRAINER STRAINER CUP O RING STRAINER CUP M11207 ...

Page 6: ...close the valve As downstream pressure drops due to demand the force on the diaphragm is reduced and the valve opens Adjustment is made by manually turning the adjustment knob clockwise to increase the spring force and require a higher downstream pressure to close the valve Similarly reducing the spring force lowers the outlet set pressure A factory calibrated dial is built into the adjustment mec...

Page 7: ... cartridge O ring strainer cup O ring U seal and protection washer 272852 Strainer Cup for D06G and DS06D G 1 1 2 in and 2 in includes plastic strainer cup and strainer cup O ring 272867 Bonnet kit for D06G 1 1 2 in and 2 in includes preassembled bonnet protection washer and spring Union Kits K06U5034 Union Kit Sweat 1 1 2 in includes sweat tailpiece union nut and gasket and fits all 1 1 2 in D06 ...

Page 8: ...well Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com DS06D G DIAL SET PRESSURE REGULATING VALVE U S Registered Trademark 2006 Honeywell International Inc 62 3052 1 J I Rev 11 06 ...

Reviews: