3.12 SP Ramp Set Up Groups
The Setpoint Ramp 1 or 2 Set Up groups let you configure two setpoint ramps. Each group (SP RAMP1
and SP RAMP 2) can be configured one of three ways: ramp, rate, or setpoint program.
Setpoint Ramp
Setpoint will ramp between the current local setpoint and a final setpoint over a time interval (SP RAMP).
Setpoint Rate
The Setpoint Ramp Set Up group also contains the function parameters that let you configure a specific
ramp rate up and ramp rate down (SP RATE). These rates are used when the local setpoint is manually
changed.
Setpoint Program
Also included under this group are prompts for configuring a Setpoint program (SP PROG). The prompts
and instructions for Setpoint programming are presented in the
Section 6 - Setpoint Ramp/Soak
Programming Option.
Function prompts
Table 3-9 lists all the function prompts in the SP RAMP 1 or SP RAMP 2 Set Up group. Configure each
ramp separately. When you enable the ramp type (SP RAMP, SP RATE, SP PROG) the other two types
are hidden from the display.
Table 3-9 SP Ramp 1 or 2 group function prompts
Function Prompt
Lower Display
Function Name
Selections or Range of Setting
Upper Display
Factory
Setting
SP RAMP*
Single Setpoint Ramp
Selection
DISABL
ENABLE
DISABL
TIME MIN
Single Setpoint Ramp Time
0 to 255 minutes
0
FINAL SP
Single Setpoint Ramp Final
Setpoint
Enter a value within the setpoint limits
100.0
SP RATE*
Setpoint Rate
DISABL
ENABLE
DISABL
EU/HR UP
Rate up value (SP Rate
enabled)
0 to 9999
in units per hour
0
EU/HR DN
Rate down value (SP Rate
enabled)
0 to 9999
in units per hour
0
SP PROG*
Setpoint Programming
(Refer to Section 6)
DISABL
ENABLE
DISABL
*Only one of these can be enabled at a time.