Installation
2. Installation
2.1 Assembly and Wiring
Depending on the customer selected output cable options, the DirectLine can be
wired to an appropriate 16-42 Vdc source using 2 different methods:
1) Cordset. See Figure 2-1.
2) Field wiring connector with customer supplied cable. See page 7.
Refer to Section 7 for wiring for CE Mark applications.
2.1.1 Cordset
Electronics
Module
Black (
–
)
Brown (
+
)
Shield
Wire
(Ground)
Minimum: 16 V @ 250 ohms (max.)
Maximum: 42 V @ 1400 ohms (max.)
Power Supply
+
+
_
_
Load
Resistance
+
_
Chart Recorder,
Controller, etc.
(Use 250 ohms
for 1-5 V signal)
Cordset 6m (19.7’)
*Blue wire not used
*
Figure 2-1 Cordset Connection and Wiring
6
DirectLine® DL423 Sensor Module User Manual
9/11