Configuration
Step
Operation
Press
Display
6
Enter
Noise
Suppression
Frequency
MODE
Momentarily
nSUP
(
for 1 second
) then,
(
Noise Suppression Frequency Selection
)
Edit Noise
Suppression
Frequency
MODE
Hold
Flashing Display – You are now in EDIT
mode
(V
alue of current Frequency selection
)
Select desired
Frequency
Momentarily
To select 50 Hz or 60 Hz (default)
Save the Noise
Suppression
Frequency
MODE
Momentarily
Selection for frequency
7
Enter
Output
Configuration
MODE
Momentarily
OutC Enter Output Calibration
(Press MODE at anytime to return to OutC.
100% Range Value
Selection
Momentarily
rnGH
(
for 1 second
) then,
(
value of current 100 % Range Value
Selection
)
Edit 100 % Range
Value Selection
MODE
Hold
Flashing Display – You are now in EDIT
mode
V
alue of current100 % selection
)
Select desired 100
% PV Value
Momentarily
Selected 100 % PV Value in 0.50
increments
Range: 0.00 to PV Max (
default 0.00
)
Save the New 100
% Range Value
MODE
Momentarily
(
New Value
)
8
0 % Range Value
Selection
Momentarily
rnGL
(
for 1 second
) then,
(
value of current 0% Range Value
Selection
)
Edit 0 % Range
Value Selection
MODE
Hold
Flashing Display
– You are now in EDIT
mode
(
value of current 0 % selection
)
Select 0 % PV
Value
Momentarily
Selected 0 % PV Value in 0.50 increments
Range: 0.00 to PV Max (
default PV Max
)
Save the New 0 %
Range Value
continued
MODE
Momentarily
(
New Value
)
16
DirectLine® DL423 Sensor Module User Manual
9/11