Honeywell DIAL-SET DS05C Product Data Download Page 3

DS05C,D,G

3

62-3041—4

Water Capacities (See Table 1)

The suitability of a given regulator size is dependent on the 

pressure requirements where it will operate. For the pressure 

regulator valve size required for a specific installation, 

determine the following:

1.

Pressure differential between inlet and outlet pressure in 

pounds per square inch (psi),

2.

Capacity in gallons per minute, and

3.

Allowable reduced pressure falloff in psi.

Given these variables, use Table 1 to determine the proper 

size pressure regulator valve for your application.

Example: An installation has 135 psi inlet pressure, 60 psi 

outlet pressure (75 psi pressure differential). If a 12 gpm 

capacity is required with only 10 psi falloff allowable, a 1/2 in. 

DS05 is required.

Table 1. Water Capacities.

Pressure 

Regulator 

Valve Size

Reduced 

Pressure 

Falloff 

(psi)

Pressure Differential Between Inlet and Outlet

25 psi

50 psi

75 psi

100 psi or more

Flow 

Capacity 

(US gpm)

Velocity 

(ft/sec)

a

a

Velocity in feet per second is based on schedule 40 pipe size. Recommended pressure falloff for general use is approximately 

104 kPa (15 psi). Recommended velocities for the flow of water: residential and general use, 5 to 10 ft/sec; industrial use, 7 to 15 

ft/sec; boiler feed, 7 to 15 ft/sec.

Flow 

Capacity 

(US gpm)

Velocity 

(ft/sec)

a

Flow 

Capacity 

(US gpm)

Velocity 

(ft/sec)

a

Flow 

Capacity 

(US gpm)

Velocity 

(ft/sec)

a

1/2 inch

6

1.2

1.3

2.3

2.4

3.3

3.5

4.4

4.6

10

8.8

9.3

10.1

10.7

10.6

11.2

10.6

11.2

15

13.2

13.9

15.0

15.8

17.6

18.6

17.6

18.6

20

17.6

18.6

20.7

21.9

22.0

23.2

22.9

24.2

3/4 inch

6

3.6

2.1

4.0

2.4

4.0

2.4

4.0

2.4

10

8.1

4.9

9.3

5.6

9.9

6.0

9.9

6.0

15

14.7

8.8

17.6

10.6

19.8

11.9

20.6

12.4

20

23.0

13.8

27.7

16.7

32.1

19.3

4.1

20.5

1 inch

6

5.7

2.1

5.9

2.2

5.9

2.2

6.3

2.4

10

13.2

4.9

15.4

5.7

15.7

5.8

16.4

6.1

15

19.6

7.3

24.6

9.1

18.6

10.6

31.7

10.8

20

25.7

9.6

32.1

11.9

37.6

14.0

43.6

16.2

1-1/4 inch

6

13.5

2.6

16.0

3.4

20.0

4.3

22.0

4.7

10

22.0

4.7

29.0

6.2

34.0

7.3

38.0

8.1

15

37.0

7.9

56.0

12.0

62.5

13.4

73.0

15.6

20

55.0

11.8

78.0

16.7

87.0

18.6

101.0

21.6

Summary of Contents for DIAL-SET DS05C

Page 1: ...d thermal bypass Balanced seat construction provides superior pressure regulation Inlet and outlet are internally threaded female NPT and externally threaded for use with union assemblies Stand In Pipe available for temporary installation during construction or system flushing SPECIFICATIONS Model DS05 Dial Set Pressure Regulating Valves Construction Materials Body Bronze Internal Parts Stainless ...

Page 2: ...inlet to outlet Reduced Ratio 10 1 maximum Temperature Maximum Air 158 F 70 C Water 180 F 82 C Ambient Temperature Range 33 F to 140 F 1 C to 60 C Pipe Sizes Available 1 2 in 3 4 in 1 in and 1 1 4 in available Connections Can be configured as female thread by thread single union or double union NPT threaded or sweat Strainer Screen Size 0 032 in 0 8 mm Gauge Tap 1 1 4 in model only Approvals ASSE ...

Page 3: ...Capacity US gpm Velocity ft sec a a Velocity in feet per second is based on schedule 40 pipe size Recommended pressure falloff for general use is approximately 104 kPa 15 psi Recommended velocities for the flow of water residential and general use 5 to 10 ft sec industrial use 7 to 15 ft sec boiler feed 7 to 15 ft sec Flow Capacity US gpm Velocity ft sec a Flow Capacity US gpm Velocity ft sec a Fl...

Page 4: ... by turning the locking screw clockwise 4 Replace the dust cap over the dial MAINTENANCE Replacing the Cartridge See Fig 3 The working parts of the DS05 including diaphragm valve seat strainer and disk are all contained in a replaceable cartridge To replace the cartridge 1 Shut off the supply valve and open a downstream faucet to relieve the system pressure 2 Loosen the setpoint screw by turning i...

Page 5: ...er on top of the cartridge NOTE The inner lip must be pointing up to avoid damaging the diaphragm 10 Replace the spring and bonnet 11 Readjust the outlet pressure to the desired setting by using the procedure described in Changing the Outlet Pressure section Recalibration If the dial knob assembly has been dismantled recalibration is necessary Recalibrate as follows 1 Install a good quality pressu...

Page 6: ...in Figure 3 Freezes up Replace bonnet or cartridge if damaged To avoid further freeze up Temporarily slightly open a downstream faucet if the DS05 will be exposed to temperatures below 32 F 0 C The slight water flow will eliminate freeze up Move the DS05 to a location with an ambient temperature above 32 F 0 C if it is currently exposed to prolonged temperature below 32 F 0 C Pressure gauge measur...

Page 7: ...pring force and require a higher downstream pressure to close the valve Similarly reducing the spring force lowers the outlet set pressure A factory calibrated dial is built into the adjustment mechanism to allow outlet pressure no flow to be set without a gauge A locking screw maintains the setting A black plastic cover is provided to conceal the setting and protect the Dial Set from moisture and...

Page 8: ...ns Gaskets and Nuts K06U1192 1 DN25 Female NPT 1 in PRV Jumper Kit 2 Threaded Unions Gaskets and Nuts K06U1200 1 1 4 DN32 Sweat 1 1 4 in Jumper Kit 2 Sweat Unions Gaskets and Stand in Pipe K06U1218 1 1 4 DN32 Female NPT 1 1 4 in Jumper Kit 2 Threaded Unions Gaskets and Stand in Pipe PRV202 039 3 4 DN20 Male NPT 3 4 in Stand in Pipe PRV202 040 1 DN25 Male NPT 1 in PRV Stand in Pipe PRV203 034 1 1 4...