SERVICE BY THE HEATING SPECIALIST
DHC 23
20
■■
Overview of further operating parameters DHC 23-2
q
Turn programming switch into position.
w
Further parameters can be displayed and changed by turning the service switch
into the positions 9....D.
e
The parameters can then be changed with the aid of the push and turn knob..
Position Operating parameter
Range
Basic setting
0
Outside temperature
only display
1
Flow temperature of the
only display
heating circuit M1
2
District heating return temperature
only display
3
Domestic hot water temperature
only display
4
Flow temperature unmixed circuit
only display
5
Flow temperature setpoint
mixed circuit
only display
6
Room temperature setpoint
only display
7
Flow temperature setpoint
unmixed circuit
only display
8
Maximum setpoint of the district
only display
heating return temperature
9
Configuration of 6th relay
2, 3
3
2 = circulation pump
3 = layered heating circuit
A = 10Room setpoint for layered
heating circuit
8...32 °C
20
B = 11
Heating characteristic slope
unmixed heating circuit
0.4...4.5
1.6
C = 12
Temperature selector input
1...3
1
1 = acts on both heating circuits
2 = acts only on mixed heating circuit
3 = acts only on unmixed heating circuit
D = 13
Automatic summer/winter time
can be switched off
05:03/05:10
E = 14
Current valve position M1
only display
F = 15
Software version
only display
Programming switch
Service switch
Push and turn knob