Output Power OK
Output Power Fault
Green LED
Uout
+
–
Uout
V
OUT
INSTALLATION
Safety measures before installation.
Always isolate the equipment from the mains supply before commencing installation or wiring.
Installation
Installation must be carried out according to the prevailing local conditions and safety regulations (e.g. VDE 0100) national
accident prevention regulations (e.g. UVV-VBG4 or BGV A3) and the generally accepted rules of technology. This equipment
is a component designed for installation into electrical systems and machines, and fulfils the requirements of the low voltage
guidelines (2014/35/EU).
The required minimum spacing to neighbouring components must be observed to guarantee the required cooling. When installed
into machinery, normal operation is forbidden until it is determined that the machine fulfils the requirements of the machinery
guidelines (2006/42/EG). EN 60204 must be observed. The EMC requirements (2014/30/EU) must be fulfilled before operation is
commenced. The observance of the required limitations for the EMC legislation is the responsibility of the installer.
PARALLEL CONNECTION
If units have their outputs connected in parallel, their output voltages must be adjusted to the same value (± 100 mV).
Impedances from the units to the star point must be equal.
Note that leakage current, EMI, inrush current and harmonics can increase when using multiple power supplies.